Electrical Engineering (EE) Exam  >  Electrical Engineering (EE) Tests  >  Electrical Engineering SSC JE (Technical)  >  Test: Estimation & Costing- 2 - Electrical Engineering (EE) MCQ

Test: Estimation & Costing- 2 - Electrical Engineering (EE) MCQ


Test Description

20 Questions MCQ Test Electrical Engineering SSC JE (Technical) - Test: Estimation & Costing- 2

Test: Estimation & Costing- 2 for Electrical Engineering (EE) 2024 is part of Electrical Engineering SSC JE (Technical) preparation. The Test: Estimation & Costing- 2 questions and answers have been prepared according to the Electrical Engineering (EE) exam syllabus.The Test: Estimation & Costing- 2 MCQs are made for Electrical Engineering (EE) 2024 Exam. Find important definitions, questions, notes, meanings, examples, exercises, MCQs and online tests for Test: Estimation & Costing- 2 below.
Solutions of Test: Estimation & Costing- 2 questions in English are available as part of our Electrical Engineering SSC JE (Technical) for Electrical Engineering (EE) & Test: Estimation & Costing- 2 solutions in Hindi for Electrical Engineering SSC JE (Technical) course. Download more important topics, notes, lectures and mock test series for Electrical Engineering (EE) Exam by signing up for free. Attempt Test: Estimation & Costing- 2 | 20 questions in 12 minutes | Mock test for Electrical Engineering (EE) preparation | Free important questions MCQ to study Electrical Engineering SSC JE (Technical) for Electrical Engineering (EE) Exam | Download free PDF with solutions
Test: Estimation & Costing- 2 - Question 1

Earth electrode used in plate earthing is a _______

Test: Estimation & Costing- 2 - Question 2

In earthed neutral system, the magnitude of transient voltage is:

Detailed Solution for Test: Estimation & Costing- 2 - Question 2

In earthed neutral system, the neutral is earthed either directly or through resistance or reactance depends on the requirement.

The advantages of neutral earthing are,

1. The arcing grounds are prevented from occurring by employing suitable switchgears

2. As the neutral point is not shifted in this system, thus the voltages of healthy phase’s remains nearly constant

3. The faulty part of the system can be isolated from the remaining system with the help of earth fault relays

4. The magnitude of transient voltage is very small

5. This is system is more reliable, provides safety to personnel and equipment with reduced operational and maintenance cost than ungrounded system 

1 Crore+ students have signed up on EduRev. Have you? Download the App
Test: Estimation & Costing- 2 - Question 3

For proper earthing, what should be the maximum value of earth resistance while carrying out the testing of earth continuity path?

Detailed Solution for Test: Estimation & Costing- 2 - Question 3

For proper earthing, the maximum value of earth resistance while carrying out the testing of earth continuity path should be around 1 ohm.

Test: Estimation & Costing- 2 - Question 4

Which material is used for wiring continuous bus bar?

i. Aluminum

ii. Copper

Detailed Solution for Test: Estimation & Costing- 2 - Question 4

Aluminum is used for wiring continuous bus bar because its cost is lesser than the copper.

Test: Estimation & Costing- 2 - Question 5

What is meant by contingencies?

i. The list of required components are included in this category

ii. The list of vague and unforeseen items is included in this category

iii. The list of components along with their discounted prices is included in this category

Detailed Solution for Test: Estimation & Costing- 2 - Question 5

The unforeseen items are the items which are unpredictable. The list of vague and unforeseen items is included in contingencies.

Test: Estimation & Costing- 2 - Question 6

What is the maximum length of the flexible conduit in motor installation?

Detailed Solution for Test: Estimation & Costing- 2 - Question 6

According to Indian Electricity rules, the maximum length of the flexible conduit in motor installation is should be less than 1.25 m

Test: Estimation & Costing- 2 - Question 7

Mixture preferred for filling around the earth electrode for effective earthing is:

Detailed Solution for Test: Estimation & Costing- 2 - Question 7

Coal salt mixture is preferred for filling around the earth electrode for effective earthing.

Coal is made of carbon which is good conductor minimizing the earth resistant. Salt use as electrolyte to form conductivity between GI Plate Coal and Earth with humidity. Sand is used to form porosity to cycle water & humidity around the mixture.

Test: Estimation & Costing- 2 - Question 8

Normally the human body resistance in totally wet and dry condition is ________ respectively.

Detailed Solution for Test: Estimation & Costing- 2 - Question 8

Under dry conditions, the resistance offered by the human body may be as high as one mega ohms. Wet or broken skin may drop the body's resistance to 1000 ohms. Adding that, high-voltage electrical energy quickly breaks down human skin, reducing the human body's resistance to 500 ohms.

Test: Estimation & Costing- 2 - Question 9

In case of electric fire, use:

Detailed Solution for Test: Estimation & Costing- 2 - Question 9

Class C type fire extinguishers can be used for electrical fires. While the extinguishment of electrical fire,

1. If possible, remove the source of energy by unplugging or disconnecting the electrical equipment

2. Use carbon dioxide, ordinary (BC rated) dry chemical, multi-purpose dry chemical and halon fire extinguishers

3. Do not use water on any energized electrical equipment

Test: Estimation & Costing- 2 - Question 10

For the measurement of the earth resistance of a given earth electrode:

Detailed Solution for Test: Estimation & Costing- 2 - Question 10

When performing a measurement, the aim is to position the auxiliary test electrode C far away from the earth electrode under test so that the auxiliary test electrode P will lie outside the effective resistance areas of both the earth system and the other test electrode

If the current test electrode C is too close, the resistance areas will overlap and there will be a steep variation in the measured resistance as the voltage test electrode is moved.

If the current test electrode is correctly positioned, there will be a flat (or very nearly so) resistance area somewhere in between it and the earth system and variations in the position of the voltage test electrode should only produce very minor changes in the resistance valu

Test: Estimation & Costing- 2 - Question 11

One among the following is the top most conductors in high voltage transmission lines, identify it.

Detailed Solution for Test: Estimation & Costing- 2 - Question 11

A guard wire or earth wire is the top most conductors in high voltage transmission lines. It is used mainly to protect lines from lightning. If in case lightning struck then it carries the excessive current inrush to ground.

Its radius is much smaller than the actual transmission wire because as the resistance is inversely proportional to area of cross section and as the cross section decreases, the resistance increases. The increased resistance of earth wire is able to withstand high inrush of current caused due to lightning and it will safely guide this inrush into ground.

Test: Estimation & Costing- 2 - Question 12

In which type of wiring vulcanized Indian rubber (VIR) and polyvinyl chloride (PVC) insulated wires are used as conductors

Detailed Solution for Test: Estimation & Costing- 2 - Question 12

Vulcanized Indian Rubber: These consists of a copper conductor covered with an insulation layer of VIR. A cotton tape covering is provided over this insulation layer to protect the wire from moisture and to provide mechanical strength to the wire. These type of wires are used in 250 V CTS wiring, casing or capping or cleat wiring.

Polyvinyl Chloride: These wires consists of a conductor over which an insulation layer made up of Polyvinyl Chloride is provided. These wires cannot resist much heat and they have relatively low melting points, so they aren’t used in hot places and also these wires are not used with heating appliances. These wires are applied in casing wiring and also used along with cleat wiring

Test: Estimation & Costing- 2 - Question 13

As per IE rules the maximum allowable variation between declared and actual voltage at consumer’s premises should be

Detailed Solution for Test: Estimation & Costing- 2 - Question 13

As per IE rules the maximum allowable variation between declared and actual voltage at consumer’s premises should be ± 3%

Test: Estimation & Costing- 2 - Question 14

Minimum distance of underground cable from the foundation of building should be

Detailed Solution for Test: Estimation & Costing- 2 - Question 14

As per IE rules Minimum distance of underground cable from the foundation of building should be 10 cm.

Test: Estimation & Costing- 2 - Question 15

While using wooden poles in a services line, the span should not exceed

Detailed Solution for Test: Estimation & Costing- 2 - Question 15

While using wooden poles in a services line, the span should not exceed 40 to 50 m.

Test: Estimation & Costing- 2 - Question 16

As per IE rules the permissible variation of voltage at the consumer end is:

Detailed Solution for Test: Estimation & Costing- 2 - Question 16

As per IE rules the permissible variation of voltage at the consumer end is ±6%.

In the case of low or medium voltage, it is more than 6 percent.

In the case of high voltage, it is more than 6 per cent on the higher side or by more than 9 per cent on the lower side.

Test: Estimation & Costing- 2 - Question 17

What is the minimum permissible size of the earth continuity conductor?

Detailed Solution for Test: Estimation & Costing- 2 - Question 17

The minimum permissible size of the earth continuity conductor is 6 sq. mm.

Test: Estimation & Costing- 2 - Question 18

Setting depth of poles is

Detailed Solution for Test: Estimation & Costing- 2 - Question 18

Setting depth of poles is 1/5 part of the length of pole. The depth for most heavy poles should be at least two feet. Another rule of thumb is that the hole’s depth should be 1/5 of the length of the poles and below the frost line.

Test: Estimation & Costing- 2 - Question 19

The earth’s potential is taken is –

Detailed Solution for Test: Estimation & Costing- 2 - Question 19

Earth is chosen as a place of zero electric potential because it has almost constant potential.

Test: Estimation & Costing- 2 - Question 20

In house wiring, black & green wires indicate

Detailed Solution for Test: Estimation & Costing- 2 - Question 20