Page 1
Solution
V V
L
400 = O ° + ? = + = = 87 . 36 25 15 20 j Z Z
p RN
As the star-connected load is balanced, the magnitude of the phase voltage is,
V V V
L p
231 3 400 3 = = =
Taking the phase voltage, as reference, the phase voltages are,
RN
V
° + ? = ° - ? = ° ? = 120 231 ; 120 231 ; 0 231
BN YN RN
V V V
The phasor diagram is shown in Fig. 20.6b. It has been shown that the line voltage,
leads the corresponding phase voltage, by . So, the line voltages are,
RY
V
RN
V ° 30
° + ? = ° - ? = ° + ? = 150 400 ; 90 400 ; 30 400
BR YB RY
V V V
For a star-connected load, the phase and the line currents are same.
The current in R-phase is,
() ( ) A Z V I I
p RN R RN
° - ? = ° + ? ° ? = = = 87 . 36 24 . 9 87 . 36 0 . 25 0 0 . 231 /
A j ) 54 . 5 39 . 7 ( - =
Two other phase and line currents are,
13 . 83 9.24 ; 87 . 156 24 . 9 A I I A I I
B BN Y YN
° + ? = = ° - ? = =
The power factor of the load is 8 . 0 87 . 36 cos cos = ° = f lagging, with ° + = 87 . 36 f ,
as the load is inductive.
Total VA 403 . 6 24 . 9 0 . 231 3 3 = × × = · · =
p p
I V kVA
This can be taken as 403 . 6 24 . 9 400 3 3 = × × = · ·
l L
I V kVA
Total power 123 . 5 8 . 0 24 . 9 0 . 231 3 cos 3 = × × × = · · · = f
p p
I V kW
Total reactive VA 842 . 3 87 . 36 sin 24 . 9 0 . 231 3 sin 3 = ° × × × = · · · = f
p p
I V kVAR
The readings of the two wattmeters are,
45 . 1 87 . 66 cos 24 . 9 400 ) 30 ( cos
1
= ° × × = + ° · · = f
R RY
I V W kW
The phase angle between and is , obtained using two phasors.
RY
V
R
I ° 87 . 66
67 . 3 87 . 6 cos 24 . 9 400 ) 30 ( cos
2
= ° × × = - ° · · = f
B BY
I V W kW
The phase angle between and is , obtained using two phasors, where
.
BY
V
B
I ° 87 . 6
° + ? = 90 400
BY
V
The sum of two readings is 12 . 5 ) 67 . 3 45 . 1 ( = + kW, which is same as the total power
computed earlier
Example 20.2
Calculate the readings of the wattmeter (W) connected as shown in Fig. 20.7a. The
load is the same, as in Fig. 20.7a (Ex. 20.1), i.e., balanced star-connected one, with
impedance of per phase, fed from a three-phase, 400 V, balanced supply,
with the phase sequence as R-Y-B.
O + ) 15 20 ( j
Version 2 EE IIT, Kharagpur
Page 2
Solution
V V
L
400 = O ° + ? = + = = 87 . 36 25 15 20 j Z Z
p RN
As the star-connected load is balanced, the magnitude of the phase voltage is,
V V V
L p
231 3 400 3 = = =
Taking the phase voltage, as reference, the phase voltages are,
RN
V
° + ? = ° - ? = ° ? = 120 231 ; 120 231 ; 0 231
BN YN RN
V V V
The phasor diagram is shown in Fig. 20.6b. It has been shown that the line voltage,
leads the corresponding phase voltage, by . So, the line voltages are,
RY
V
RN
V ° 30
° + ? = ° - ? = ° + ? = 150 400 ; 90 400 ; 30 400
BR YB RY
V V V
For a star-connected load, the phase and the line currents are same.
The current in R-phase is,
() ( ) A Z V I I
p RN R RN
° - ? = ° + ? ° ? = = = 87 . 36 24 . 9 87 . 36 0 . 25 0 0 . 231 /
A j ) 54 . 5 39 . 7 ( - =
Two other phase and line currents are,
13 . 83 9.24 ; 87 . 156 24 . 9 A I I A I I
B BN Y YN
° + ? = = ° - ? = =
The power factor of the load is 8 . 0 87 . 36 cos cos = ° = f lagging, with ° + = 87 . 36 f ,
as the load is inductive.
Total VA 403 . 6 24 . 9 0 . 231 3 3 = × × = · · =
p p
I V kVA
This can be taken as 403 . 6 24 . 9 400 3 3 = × × = · ·
l L
I V kVA
Total power 123 . 5 8 . 0 24 . 9 0 . 231 3 cos 3 = × × × = · · · = f
p p
I V kW
Total reactive VA 842 . 3 87 . 36 sin 24 . 9 0 . 231 3 sin 3 = ° × × × = · · · = f
p p
I V kVAR
The readings of the two wattmeters are,
45 . 1 87 . 66 cos 24 . 9 400 ) 30 ( cos
1
= ° × × = + ° · · = f
R RY
I V W kW
The phase angle between and is , obtained using two phasors.
RY
V
R
I ° 87 . 66
67 . 3 87 . 6 cos 24 . 9 400 ) 30 ( cos
2
= ° × × = - ° · · = f
B BY
I V W kW
The phase angle between and is , obtained using two phasors, where
.
BY
V
B
I ° 87 . 6
° + ? = 90 400
BY
V
The sum of two readings is 12 . 5 ) 67 . 3 45 . 1 ( = + kW, which is same as the total power
computed earlier
Example 20.2
Calculate the readings of the wattmeter (W) connected as shown in Fig. 20.7a. The
load is the same, as in Fig. 20.7a (Ex. 20.1), i.e., balanced star-connected one, with
impedance of per phase, fed from a three-phase, 400 V, balanced supply,
with the phase sequence as R-Y-B.
O + ) 15 20 ( j
Version 2 EE IIT, Kharagpur
•
•
R
Y
B
Balanced
star-
connected
load as in
Fig. 20.6(a)
W
(a)
I
R
30°
V
RY
V
RN
I
RN
V
YB
90°- F
F
(b)
Fig. 20.7 (a) Circuit diagram (Example 20.2)
(b) Phasor diagram
Solution
The steps are not repeated here, but taken from previous example (20.1).
The phasor diagram is shown in Fig. 20.7b.
The phase voltage, is taken as reference as in Ex. 20.1.
RN
V
The phase current, is
RN
I A I
RN
° - ? = 87 . 36 24 .9
The phase angle, f of the load impedance is ° + = 87 . 36 f
The line voltage, is
RY
V V V
RY
° + ? = 30 400
Version 2 EE IIT, Kharagpur
Page 3
Solution
V V
L
400 = O ° + ? = + = = 87 . 36 25 15 20 j Z Z
p RN
As the star-connected load is balanced, the magnitude of the phase voltage is,
V V V
L p
231 3 400 3 = = =
Taking the phase voltage, as reference, the phase voltages are,
RN
V
° + ? = ° - ? = ° ? = 120 231 ; 120 231 ; 0 231
BN YN RN
V V V
The phasor diagram is shown in Fig. 20.6b. It has been shown that the line voltage,
leads the corresponding phase voltage, by . So, the line voltages are,
RY
V
RN
V ° 30
° + ? = ° - ? = ° + ? = 150 400 ; 90 400 ; 30 400
BR YB RY
V V V
For a star-connected load, the phase and the line currents are same.
The current in R-phase is,
() ( ) A Z V I I
p RN R RN
° - ? = ° + ? ° ? = = = 87 . 36 24 . 9 87 . 36 0 . 25 0 0 . 231 /
A j ) 54 . 5 39 . 7 ( - =
Two other phase and line currents are,
13 . 83 9.24 ; 87 . 156 24 . 9 A I I A I I
B BN Y YN
° + ? = = ° - ? = =
The power factor of the load is 8 . 0 87 . 36 cos cos = ° = f lagging, with ° + = 87 . 36 f ,
as the load is inductive.
Total VA 403 . 6 24 . 9 0 . 231 3 3 = × × = · · =
p p
I V kVA
This can be taken as 403 . 6 24 . 9 400 3 3 = × × = · ·
l L
I V kVA
Total power 123 . 5 8 . 0 24 . 9 0 . 231 3 cos 3 = × × × = · · · = f
p p
I V kW
Total reactive VA 842 . 3 87 . 36 sin 24 . 9 0 . 231 3 sin 3 = ° × × × = · · · = f
p p
I V kVAR
The readings of the two wattmeters are,
45 . 1 87 . 66 cos 24 . 9 400 ) 30 ( cos
1
= ° × × = + ° · · = f
R RY
I V W kW
The phase angle between and is , obtained using two phasors.
RY
V
R
I ° 87 . 66
67 . 3 87 . 6 cos 24 . 9 400 ) 30 ( cos
2
= ° × × = - ° · · = f
B BY
I V W kW
The phase angle between and is , obtained using two phasors, where
.
BY
V
B
I ° 87 . 6
° + ? = 90 400
BY
V
The sum of two readings is 12 . 5 ) 67 . 3 45 . 1 ( = + kW, which is same as the total power
computed earlier
Example 20.2
Calculate the readings of the wattmeter (W) connected as shown in Fig. 20.7a. The
load is the same, as in Fig. 20.7a (Ex. 20.1), i.e., balanced star-connected one, with
impedance of per phase, fed from a three-phase, 400 V, balanced supply,
with the phase sequence as R-Y-B.
O + ) 15 20 ( j
Version 2 EE IIT, Kharagpur
•
•
R
Y
B
Balanced
star-
connected
load as in
Fig. 20.6(a)
W
(a)
I
R
30°
V
RY
V
RN
I
RN
V
YB
90°- F
F
(b)
Fig. 20.7 (a) Circuit diagram (Example 20.2)
(b) Phasor diagram
Solution
The steps are not repeated here, but taken from previous example (20.1).
The phasor diagram is shown in Fig. 20.7b.
The phase voltage, is taken as reference as in Ex. 20.1.
RN
V
The phase current, is
RN
I A I
RN
° - ? = 87 . 36 24 .9
The phase angle, f of the load impedance is ° + = 87 . 36 f
The line voltage, is
RY
V V V
RY
° + ? = 30 400
Version 2 EE IIT, Kharagpur
The line voltage, is
YB
V V V
YB
° - ? = 90 400
The reading of the wattmeter (W) is,
f ? sin 3 ) 90 ( cos ) , ( cos · · · - = + ° · · == · · =
p p p L RN YB RN YB
I V I V I V I V W
kW 218 . 2 87 . 36 sin 24 . 9 400 - = ° × × - =
The value is negative, as the load is inductive.
The reading (W) is 577 . 0 3 / 1 = times the total reactive power as,
f f sin 3 sin 3 · · · = · · ·
L L p p
I V I V ,
or 3 times the reactive power per phase.
Example 20.3
Calculate the readings of the two wattmeters ( & ) connected to measure the
total power for a balanced delta-connected load shown in Fig. 20.8a, fed from a three-
phase, 200 V balanced supply with phase sequence as R-Y-B. The load impedance per
phase is
1
W
2
W
O - ) 14 14 ( j . Also find the line and phase currents, power factor, total power,
total reactive VA and total VA.
X
C
= 14 O / R = 14 O
R
Y
B
W
2
•
•
I
B
I
Y
I
R
(a)
Z
1
I
RY
Z
1
Z
1
I
BR
I
YB
I
RY
Z
1
Version 2 EE IIT, Kharagpur
Page 4
Solution
V V
L
400 = O ° + ? = + = = 87 . 36 25 15 20 j Z Z
p RN
As the star-connected load is balanced, the magnitude of the phase voltage is,
V V V
L p
231 3 400 3 = = =
Taking the phase voltage, as reference, the phase voltages are,
RN
V
° + ? = ° - ? = ° ? = 120 231 ; 120 231 ; 0 231
BN YN RN
V V V
The phasor diagram is shown in Fig. 20.6b. It has been shown that the line voltage,
leads the corresponding phase voltage, by . So, the line voltages are,
RY
V
RN
V ° 30
° + ? = ° - ? = ° + ? = 150 400 ; 90 400 ; 30 400
BR YB RY
V V V
For a star-connected load, the phase and the line currents are same.
The current in R-phase is,
() ( ) A Z V I I
p RN R RN
° - ? = ° + ? ° ? = = = 87 . 36 24 . 9 87 . 36 0 . 25 0 0 . 231 /
A j ) 54 . 5 39 . 7 ( - =
Two other phase and line currents are,
13 . 83 9.24 ; 87 . 156 24 . 9 A I I A I I
B BN Y YN
° + ? = = ° - ? = =
The power factor of the load is 8 . 0 87 . 36 cos cos = ° = f lagging, with ° + = 87 . 36 f ,
as the load is inductive.
Total VA 403 . 6 24 . 9 0 . 231 3 3 = × × = · · =
p p
I V kVA
This can be taken as 403 . 6 24 . 9 400 3 3 = × × = · ·
l L
I V kVA
Total power 123 . 5 8 . 0 24 . 9 0 . 231 3 cos 3 = × × × = · · · = f
p p
I V kW
Total reactive VA 842 . 3 87 . 36 sin 24 . 9 0 . 231 3 sin 3 = ° × × × = · · · = f
p p
I V kVAR
The readings of the two wattmeters are,
45 . 1 87 . 66 cos 24 . 9 400 ) 30 ( cos
1
= ° × × = + ° · · = f
R RY
I V W kW
The phase angle between and is , obtained using two phasors.
RY
V
R
I ° 87 . 66
67 . 3 87 . 6 cos 24 . 9 400 ) 30 ( cos
2
= ° × × = - ° · · = f
B BY
I V W kW
The phase angle between and is , obtained using two phasors, where
.
BY
V
B
I ° 87 . 6
° + ? = 90 400
BY
V
The sum of two readings is 12 . 5 ) 67 . 3 45 . 1 ( = + kW, which is same as the total power
computed earlier
Example 20.2
Calculate the readings of the wattmeter (W) connected as shown in Fig. 20.7a. The
load is the same, as in Fig. 20.7a (Ex. 20.1), i.e., balanced star-connected one, with
impedance of per phase, fed from a three-phase, 400 V, balanced supply,
with the phase sequence as R-Y-B.
O + ) 15 20 ( j
Version 2 EE IIT, Kharagpur
•
•
R
Y
B
Balanced
star-
connected
load as in
Fig. 20.6(a)
W
(a)
I
R
30°
V
RY
V
RN
I
RN
V
YB
90°- F
F
(b)
Fig. 20.7 (a) Circuit diagram (Example 20.2)
(b) Phasor diagram
Solution
The steps are not repeated here, but taken from previous example (20.1).
The phasor diagram is shown in Fig. 20.7b.
The phase voltage, is taken as reference as in Ex. 20.1.
RN
V
The phase current, is
RN
I A I
RN
° - ? = 87 . 36 24 .9
The phase angle, f of the load impedance is ° + = 87 . 36 f
The line voltage, is
RY
V V V
RY
° + ? = 30 400
Version 2 EE IIT, Kharagpur
The line voltage, is
YB
V V V
YB
° - ? = 90 400
The reading of the wattmeter (W) is,
f ? sin 3 ) 90 ( cos ) , ( cos · · · - = + ° · · == · · =
p p p L RN YB RN YB
I V I V I V I V W
kW 218 . 2 87 . 36 sin 24 . 9 400 - = ° × × - =
The value is negative, as the load is inductive.
The reading (W) is 577 . 0 3 / 1 = times the total reactive power as,
f f sin 3 sin 3 · · · = · · ·
L L p p
I V I V ,
or 3 times the reactive power per phase.
Example 20.3
Calculate the readings of the two wattmeters ( & ) connected to measure the
total power for a balanced delta-connected load shown in Fig. 20.8a, fed from a three-
phase, 200 V balanced supply with phase sequence as R-Y-B. The load impedance per
phase is
1
W
2
W
O - ) 14 14 ( j . Also find the line and phase currents, power factor, total power,
total reactive VA and total VA.
X
C
= 14 O / R = 14 O
R
Y
B
W
2
•
•
I
B
I
Y
I
R
(a)
Z
1
I
RY
Z
1
Z
1
I
BR
I
YB
I
RY
Z
1
Version 2 EE IIT, Kharagpur
I
R
V
RY
I
YB
V
YB
I
BR
V
BR
V
BY
I
Y
I
B
30°
30°
( F-30 °)
( F+30 °)
60°
F
F
I
RY
(b)
F
Fig. 20.8 (a) Circuit diagram for a three-phase system with balanced delta-
connected load (Example 20.3)
(b) Phasor diagram
Solution
O ° - ? = - = = 45 8 . 19 14 14 j Z Z
p RY
For delta-connected load, V V V
p L
200 = =
Taking the line or phase voltage as reference, the line or phase voltages are,
RY
V
° + ? = ° - ? = ° ? = 120 200 ; 120 200 ; 0 200
BR YB RY
V V V
The phasor diagram is shown in Fig. 20.8b. The phase current, is,
RY
I
() ( ) A j Z V I
p RY RY
) 142 . 7 142 . 7 ( 45 1 . 10 45 9.8 1 / 0 0 . 200 / + = ° + ? = ° - ? ° ? = =
The other two phase currents are,
165 .1 10 ; 75 1 . 10 A I A I
BR YN
° + ? = ° - ? =
The power factor of the load is 707 . 0 45 cos cos = ° = f leading, with ° - = 45 f , as
the load is capacitive.
As the phase currents are balanced, the magnitude of the line current is 3 times the
magnitude of the phase current, and the value is
A I I
RY R
5 . 17 1 . 10 3 3 = × = · =
It has been shown that the line current, lags the corresponding phase current,
by .
R
I
RY
I
° 30
So, the line currents are,
15 5 . 17 165 1 . 10 45 1 . 10 A I I I
BR RY R
° + ? = ° + ? - ° + ? = - =
135 .5 17 ; 105 5 . 17 A I I I A I I I
YB BR B RY YB Y
° + ? = - = ° - ? = - =
Version 2 EE IIT, Kharagpur
Page 5
Solution
V V
L
400 = O ° + ? = + = = 87 . 36 25 15 20 j Z Z
p RN
As the star-connected load is balanced, the magnitude of the phase voltage is,
V V V
L p
231 3 400 3 = = =
Taking the phase voltage, as reference, the phase voltages are,
RN
V
° + ? = ° - ? = ° ? = 120 231 ; 120 231 ; 0 231
BN YN RN
V V V
The phasor diagram is shown in Fig. 20.6b. It has been shown that the line voltage,
leads the corresponding phase voltage, by . So, the line voltages are,
RY
V
RN
V ° 30
° + ? = ° - ? = ° + ? = 150 400 ; 90 400 ; 30 400
BR YB RY
V V V
For a star-connected load, the phase and the line currents are same.
The current in R-phase is,
() ( ) A Z V I I
p RN R RN
° - ? = ° + ? ° ? = = = 87 . 36 24 . 9 87 . 36 0 . 25 0 0 . 231 /
A j ) 54 . 5 39 . 7 ( - =
Two other phase and line currents are,
13 . 83 9.24 ; 87 . 156 24 . 9 A I I A I I
B BN Y YN
° + ? = = ° - ? = =
The power factor of the load is 8 . 0 87 . 36 cos cos = ° = f lagging, with ° + = 87 . 36 f ,
as the load is inductive.
Total VA 403 . 6 24 . 9 0 . 231 3 3 = × × = · · =
p p
I V kVA
This can be taken as 403 . 6 24 . 9 400 3 3 = × × = · ·
l L
I V kVA
Total power 123 . 5 8 . 0 24 . 9 0 . 231 3 cos 3 = × × × = · · · = f
p p
I V kW
Total reactive VA 842 . 3 87 . 36 sin 24 . 9 0 . 231 3 sin 3 = ° × × × = · · · = f
p p
I V kVAR
The readings of the two wattmeters are,
45 . 1 87 . 66 cos 24 . 9 400 ) 30 ( cos
1
= ° × × = + ° · · = f
R RY
I V W kW
The phase angle between and is , obtained using two phasors.
RY
V
R
I ° 87 . 66
67 . 3 87 . 6 cos 24 . 9 400 ) 30 ( cos
2
= ° × × = - ° · · = f
B BY
I V W kW
The phase angle between and is , obtained using two phasors, where
.
BY
V
B
I ° 87 . 6
° + ? = 90 400
BY
V
The sum of two readings is 12 . 5 ) 67 . 3 45 . 1 ( = + kW, which is same as the total power
computed earlier
Example 20.2
Calculate the readings of the wattmeter (W) connected as shown in Fig. 20.7a. The
load is the same, as in Fig. 20.7a (Ex. 20.1), i.e., balanced star-connected one, with
impedance of per phase, fed from a three-phase, 400 V, balanced supply,
with the phase sequence as R-Y-B.
O + ) 15 20 ( j
Version 2 EE IIT, Kharagpur
•
•
R
Y
B
Balanced
star-
connected
load as in
Fig. 20.6(a)
W
(a)
I
R
30°
V
RY
V
RN
I
RN
V
YB
90°- F
F
(b)
Fig. 20.7 (a) Circuit diagram (Example 20.2)
(b) Phasor diagram
Solution
The steps are not repeated here, but taken from previous example (20.1).
The phasor diagram is shown in Fig. 20.7b.
The phase voltage, is taken as reference as in Ex. 20.1.
RN
V
The phase current, is
RN
I A I
RN
° - ? = 87 . 36 24 .9
The phase angle, f of the load impedance is ° + = 87 . 36 f
The line voltage, is
RY
V V V
RY
° + ? = 30 400
Version 2 EE IIT, Kharagpur
The line voltage, is
YB
V V V
YB
° - ? = 90 400
The reading of the wattmeter (W) is,
f ? sin 3 ) 90 ( cos ) , ( cos · · · - = + ° · · == · · =
p p p L RN YB RN YB
I V I V I V I V W
kW 218 . 2 87 . 36 sin 24 . 9 400 - = ° × × - =
The value is negative, as the load is inductive.
The reading (W) is 577 . 0 3 / 1 = times the total reactive power as,
f f sin 3 sin 3 · · · = · · ·
L L p p
I V I V ,
or 3 times the reactive power per phase.
Example 20.3
Calculate the readings of the two wattmeters ( & ) connected to measure the
total power for a balanced delta-connected load shown in Fig. 20.8a, fed from a three-
phase, 200 V balanced supply with phase sequence as R-Y-B. The load impedance per
phase is
1
W
2
W
O - ) 14 14 ( j . Also find the line and phase currents, power factor, total power,
total reactive VA and total VA.
X
C
= 14 O / R = 14 O
R
Y
B
W
2
•
•
I
B
I
Y
I
R
(a)
Z
1
I
RY
Z
1
Z
1
I
BR
I
YB
I
RY
Z
1
Version 2 EE IIT, Kharagpur
I
R
V
RY
I
YB
V
YB
I
BR
V
BR
V
BY
I
Y
I
B
30°
30°
( F-30 °)
( F+30 °)
60°
F
F
I
RY
(b)
F
Fig. 20.8 (a) Circuit diagram for a three-phase system with balanced delta-
connected load (Example 20.3)
(b) Phasor diagram
Solution
O ° - ? = - = = 45 8 . 19 14 14 j Z Z
p RY
For delta-connected load, V V V
p L
200 = =
Taking the line or phase voltage as reference, the line or phase voltages are,
RY
V
° + ? = ° - ? = ° ? = 120 200 ; 120 200 ; 0 200
BR YB RY
V V V
The phasor diagram is shown in Fig. 20.8b. The phase current, is,
RY
I
() ( ) A j Z V I
p RY RY
) 142 . 7 142 . 7 ( 45 1 . 10 45 9.8 1 / 0 0 . 200 / + = ° + ? = ° - ? ° ? = =
The other two phase currents are,
165 .1 10 ; 75 1 . 10 A I A I
BR YN
° + ? = ° - ? =
The power factor of the load is 707 . 0 45 cos cos = ° = f leading, with ° - = 45 f , as
the load is capacitive.
As the phase currents are balanced, the magnitude of the line current is 3 times the
magnitude of the phase current, and the value is
A I I
RY R
5 . 17 1 . 10 3 3 = × = · =
It has been shown that the line current, lags the corresponding phase current,
by .
R
I
RY
I
° 30
So, the line currents are,
15 5 . 17 165 1 . 10 45 1 . 10 A I I I
BR RY R
° + ? = ° + ? - ° + ? = - =
135 .5 17 ; 105 5 . 17 A I I I A I I I
YB BR B RY YB Y
° + ? = - = ° - ? = - =
Version 2 EE IIT, Kharagpur
The procedure is only presented, with the steps given in brief.
Total VA 06 . 6 1 . 10 0 . 200 3 3 = × × = · · =
p p
I V kVA
This can be taken as 06 . 6 5 . 17 200 3 3 = × × = · ·
l L
I V kVA
Total power 285 . 4 707 . 0 1 . 10 0 . 200 3 cos 3 = × × × = · · · = f
p p
I V kW
Total reactive VA 285 . 4 . 45 sin 1 . 10 0 . 200 3 sin 3 = ° × × × = · · · = f
p p
I V kVAR
The readings of the two wattmeters are,
38 . 3 ) 15 cos( 5 . 17 200 ) 30 ( cos
1
= ° - × × = + ° · · = f
R RY
I V W kW
The phase angle between and is , obtained using two phasors.
RY
V
R
I ° 15
906 . 0 75 cos 5 . 17 200 ) 30 ( cos
2
= ° × × = - ° · · = f
B BY
I V W kW
The phase angle between and is , obtained using two phasors, where
.
BY
V
B
I ° 75
° + ? = 60 200
BY
V
The sum of two readings is 286 . 4 ) 906 . 0 38 . 3 ( = + kW, which is same as the total
power computed earlier
Alternatively, the phase current, can be taken as reference, with the corres-
ponding phase voltage, leading the current by the angle of the load impedance,
RY
I
RY
V
° = 45 f . So, the phase current and voltage are,
; 0 1 . 10 A I
RY
° ? = V Z I V
p RY RY
° ? = ° ? × = ? · ° ? = 45 200 45 ) 8 . 19 1 . 10 ( 0 f
Two other phase currents and voltages are,
° + ? = ° - ? = 120 1 . 10 ; 120 1 . 10
BR YB
I I
° + ? = ° - ? = 165 200 ; 75 200
BR YB
V V
The line current, is,
R
I
30 5 . 17 120 1 . 10 0 1 . 10 A I I I
BR RY R
° + ? = ° + ? - ° ? = - =
Two other line currents are,
° + ? = ° - ? = 150 .5 17 ; 90 5 . 17
B Y
I I
The other steps are not shown here. The readers are requested to study the previous
lesson (No. 19) in this module.
The measurement of power using two wattmeters for load (unbalanced or balanced),
fed from a balanced three-phase supply, is discussed in this lesson. Also presented are the
readings of the two wattmeters for balanced load, along with the determination of the
load power factor from the two readings, and some comments on the way, the two
readings vary with change in power factor of the load, with the magnitude of the load
impedance remaining constant. Some examples are also described here. This is the last
lesson in this module (No.5). In the next module (No.6) consisting of two lessons (no. 21-
22) only, the discussion on magnetic circuits will be taken up.
20.1 Calculate the reading of the two wattmeter’s (W
1
, and W
2
) connected to measure
the power for a balanced three-phase load as given in the following. The supply
voltage is 200V and the phase.
Version 2 EE IIT, Kharagpur
Read More