Electrical Engineering (EE) Exam  >  Electrical Engineering (EE) Notes  >  Power Systems  >  Previous Year Questions- Fault Analysis - 2

Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE) PDF Download

Q21: A 2-bus system and corresponding zero sequence network are shown in the figure.
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)The transformers T1 and T2 are connected as       (SET-1 (2014))
(a) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)

(b) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
(c) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
(d) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Ans: (b)
Sol: We have to use switch diagram for the zero-sequence network of transformer.
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Switch 1 or 2 is closed when winding in Yand neutral grounded.
Switch 1 or 2 is closed when winding is in Δ.
Given, for transformer T1, switch 1 is closed and 2 is open.
Therefore, transformer will be connected in primary with grounded neutral and secondary in star with isolated neutral.
For transformer T2, switch 1 is closed and 2 is closed, therefore, primary winding is star connected with neutral grounded whereas secondary will be delta connected.

Q22: Three-phase to ground fault takes place at locations F1 and Fin the system shown in the figure.Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)If the fault takes place at location F1, then the voltage and the current at bus A are VF1 and IF1 respectively. If the fault takes place at location F2, then the voltage and the current at bus A and VF2 and IF2 respectively. The correct statement about voltages and currents during faults at Fand F2 is        (SET-1  (2014))
(a) VF1 leads IF1 and VF2 leads IF2
(b) VF1 leads IF1 and VF2 lags IF2
(c) VF1 lags IF1 and VF2 leads IF2
(d) VF1lagsIF1VF1 lags IF1 and VF2 lags IF2
Ans:
(c)
Sol: Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)For the fault at location F1 the equivalent circuit is shown below.
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)For the fault at location F2 the equivalent circuit is shown below.  Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)

Q23: For a power system network with n nodes, Z33 of its bus impedance matrix is j0.5 per unit. The voltage at node 3 is 1.3 ∠ −10° per unit. If a capacitor having reactance of -j3.5 per unit is now added to the network between node 3 and the reference node, the current drawn by the capacitor per unit is      (2013)
(a) 0.325 ∠ −100°
(b) 0.325 ∠80°
(c) 0.371 ∠ −100°
(d) 0.433 ∠80°
Ans:
(d)
Sol: Thevenin's equivalent circuit between bus (3) and reference bus = Z33 = j0.5
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Thevenin's equivalent circuit between 3rd bus (3) and reference
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Q24: The sequence components of the fault current are as follows :
Ipositive = j1.5 pu, Inegative = −j0.5, Izero = −j1 pu.
The type of fault in the system is      (2012)
(a) LG
(b) LL
(c) LLG
(d) LLLG
Ans: 
(c)
Sol: Only LLG fault has a unique property that the sum of all sequence components of the fault current is zero.

Q25: Two generator units G1 and G2 are connected by 15 kV line with a bus at the mid-point as shown below
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)G1 = 250 MVA, 15kV, positive sequence reactance X = 25% on its own base
G2 = 100 MVA, 15kV, positive sequence reactance X = 10 % on its own base
L1 and L2 = 10km, positive sequence reactance X = 0.225 Ω/km
In the above system, the three-phase fault MVA at the bus 3 is     (2011)
(a) 82.55 MVA
(b) 85.11 MVA
(c) 170.91 MVA
(d) 181.82 MVA
Ans: 
(d)
Sol: Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)= 181.82 MV A

Q26: Two generator units G1 and G2 are connected by 15 kV line with a bus at the mid-point as shown below
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)G1 = 250 MVA, 15kV, positive sequence reactance X = 25% on its own base
G2 = 100 MVA, 15kV, positive sequence reactance X = 10 % on its own base
L1 and L= 10km, positive sequence reactance X = 0.225 Ω/km
For the above system, the positive sequence diagram with the p.u. values on the 100 MVA common base is       (2011)
(a) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)(b) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)(c) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)(d) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Ans:
(a)
Sol: Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Positive sequence reactance of Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Base impedance Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Hence, option (A) is correct.

Q27: The zero-sequence circuit of the three phase transformer shown in the figure     (2010)
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)(a) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)

(b) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
(c) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
(d) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Ans: (c)
Sol: Equivalent circuit for the zero sequence network depends upon the impedances met by the zero sequence currents flowing through the three phases and their sum, 3Ia0, flowing through the neutral impedance and returning through the ground or a neutral conductor.
If there is no complete path for zero sequence currents in a circuit, the zero sequence impedance is infinite.
Thus a Y-connected circuit with ungrounded neutral has infinite impedance to zero sequence currents.
A delta-connected circuit provides no path for zero sequence currents flowing in the line. The zero sequence currents being single phase, circulate within the winding. Hence viewed from its terminals its zero sequence impedance is infinite.

Q28: Consider a power system shown below:
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Given that: Vs1 = Vs2 = 1 + j0 p.u;
The positive sequence impedance are
Zs1 = Zs2 = 0.001 + j0.01 p.u and Z= 0.006 + j0.06  p.u
3-phase Base MVA = 100
voltage base = 400 kV(Line to Line)
Nominal system frequency = 50 Hz.
The reference voltage for phase 'a' is defined as V(t) = Vmcos (ωt).
A symmetrical three phase fault occurs at centre of the line, i.e. point 'F' at time 't0'. The positive sequence impedance from source S1 to point 'F' equals 0.004 + j0.04 p.u. The wave form corresponding to phase 'a' fault current from bus X reveals that decaying d.c. offset current is negative and in magnitude at its maximum initial value, Assume that the negative sequence impedances are equal to postive sequence impedance and the zero sequence impedances are three times positive sequence impedances.

Instead of the three phase fault, if a single line to ground fault occurs on phase 'a' at point 'F' with zero fault impedance, then the rms of the ac component of fault current (Ix) for phase 'a' will be     (2008)
(a) 4.97 p.u
(b) 7.0 p.u
(c) 14.93 p.u
(d) 29.85 p.u
Ans:
(c)
Sol: Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Q29: Consider a power system shown below:
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Given that: Vs1 = Vs2 = 1 + j0 p.u;
The positive sequence impedance are
Zs1 = Zs2 = 0.001 + j0.01 p.u and Z= 0.006 + j0.06  p.u
3-phase Base MVA = 100
voltage base = 400 kV(Line to Line)
Nominal system frequency = 50 Hz.
The reference voltage for phase 'a' is defined as V(t) = Vmcos (ωt).
A symmetrical three phase fault occurs at centre of the line, i.e. point 'F' at time 't0'. The positive sequence impedance from source S1 to point 'F' equals 0.004 + j0.04 p.u. The wave form corresponding to phase 'a' fault current from bus X reveals that decaying d.c. offset current is negative and in magnitude at its maximum initial value, Assume that the negative sequence impedances are equal to postive sequence impedance and the zero sequence impedances are three times positive sequence impedances.

The rms value of the component of fault current (Ix) will be       (2008)
(a)
3.59 kA
(b) 5.07 kA
(c) 7.18 kA
(d) 10.15 kA
Ans: (a)
Sol:
Fault occurs at mid point 'F'
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Thevenins equivalent,
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Q30: Consider a power system shown below:
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Given that: Vs1 = Vs2 = 1 + j0 p.u;
The positive sequence impedance are
Zs1 = Zs2 = 0.001 + j0.01 p.u and Z= 0.006 + j0.06  p.u
3-phase Base MVA = 100
voltage base = 400 kV(Line to Line)
Nominal system frequency = 50 Hz.
The reference voltage for phase 'a' is defined as V(t) = Vmcos (ωt).
A symmetrical three phase fault occurs at centre of the line, i.e. point 'F' at time 't0'. The positive sequence impedance from source S1 to point 'F' equals 0.004 + j0.04 p.u. The wave form corresponding to phase 'a' fault current from bus X reveals that decaying d.c. offset current is negative and in magnitude at its maximum initial value, Assume that the negative sequence impedances are equal to postive sequence impedance and the zero sequence impedances are three times positive sequence impedances.

The instant (t0) of the fault will be      (2008)
(a) 4.682 ms
(b) 9.667 ms
(c) 14.667 ms
(d) 19.667 ms
Ans:
(a)
Sol: Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)To find i(t) and t(0+) we can convert the above circuit in following way
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Symmetrical short circuit current,
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Now, if the initial value of dc of set (A) is Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
it requires that cos⁡ (ωt− α) = 1  
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)In problem given the circuit for 3 − ϕ fault be drawn as:
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)

According to the derrivation
For initial value of dc off set to be Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Q31: A-3-phase transmission line is shown in figure :
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Voltage drop across the transmission line is given by the following equation :
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Shunt capacitance of the line can be neglect. If the has positive sequence impedance of 15 Ω and zero sequence impedance of 48 Ω, then the values of Zs and Zm will be     (2008)
(a) Z= 31.5Ω; Z= 16.5Ω
(b) Zs = 26Ω; Zm = 11Ω
(c) Zs = 16.5Ω; Z= 31.5Ω
(d) Z= 11Ω; Z= 26Ω
Ans:
(b)
Sol: Positive sequence impedance = Negative sequence impedance
= Z− Zm = 15...(i)
Zero-sequence impedance  = Zs + 2Zm = 48...(ii)  
Solving equation (i) and (ii), we get,
Zs = 26Ω and Zm = 11Ω

Q32: Suppose we define a sequence transformation between "a - b - c" and "p - n - o" variables as follows:       (2007)
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)where Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE) and k and is a constant.
Now, if it is given that :      
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)(a) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)

(b) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
(c) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
(d) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Ans: (b)
Sol: Here,
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)where,
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)similarly, Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)comparing eq. (i) with (ii),
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Q33: A three phase balanced star connected voltage source with frequency ω rad/s is connected to a star connected balanced load which is purely inductive. The instantaneous line currents and phase to neutral voltages are denoted by (ia, ib, ic) and (van, vbn, vcn) respectively, and their rms values are denoted by V and I.
If Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE) then the magnitude of R is       (2007)
(a) 3VI
(b) VI
(c) 0.7VI
(d) 0
Ans: 
(a)
Sol: Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Assuming phase sequence abc, taking Van as the reference,
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)V is the rms value of  Van, Vbn and Vcn
I is the rms value of ia, iand ic
From equation (ii), we can say  
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)and similarly due to lagging load
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)From equation (iii) by considering line values of voltage
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)From equation (i), we have
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Q34: Three identical star connected resistors of 1.0 pu are connected to an unbalanced 3-phase supply. The load neutral is isolated. The symmetrical components of the line voltages in pu. are:
Vab1 = X∠θ1, Vab2 = Y∠θ2.
If all the pu calculations are with the respective base values, the phase to neutral sequence voltages are       (2006)
(a) Van1 = X∠(θ+ 30°), Van2 = Y(θ− 30°)
(b) Van1=X(θ130),Van1 = X∠(θ− 30°), Van2 = Y(θ+ 30°)
(c) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)

(d) Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Ans: (b)
Sol: Positive (negative ) sequence component of line voltage is √3 time of positive (negative) sequence component of phase voltage and leads (lags) by 30° in actual value but in p.u. on respective base value they are equal.,
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Q35: At a 220 kV substation of a power system, it is given that the three-phase fault level is 4000 MVA and single-line to ground fault level is 5000 MVA Neglecting the resistance and the shunt suspectances of the system.
The zero sequence driving point reactance at the bus is        (2005)
(a) 2.2 Ω
(b) 4.84  Ω
(c) 18.18  Ω
(d) 22.72  Ω
Ans:
(b)
Sol: Let negative sequence reactance = X2
Assuming, X2 = X1
and zero sequence reactance = X0
In single-line to ground fault,
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)In SLG fault
Positive sequence current
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Q36: At a 220 kV substation of a power system, it is given that the three-phase fault level is 4000 MVA and single-line to ground fault level is 5000 MVA Neglecting the resistance and the shunt suspectances of the system.
The positive sequence driving point reactance at the bus is     (2005)
(a) 2.5 Ω
(b) 4.033 Ω
(c) 5.5 Ω
(d) 12.1 Ω
Ans:
(d)
Sol: Fault level (in MVA) = √3 × prefault line voltage (kV) × fault current (in kA)
Pre-fault line voltage = Vprefault = 220kV
3 − ϕ fault level  = 4000 MVA
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Let positive sequence driving point reactance = X1
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Q37: The parameters of a transposed overhead transmission line are given as :
Self reactance Xs = 0.5Ω/km and Mutual reactance Xm = 0.1Ω/km
The positive sequence reactance X1 and zero sequence reactance X0, respectively in Ω/km are       (2005)
(a) 0.3, 0.2
(b) 0.5, 0.2
(c) 0.5, 0.6
(d) 0.3, 0.6
Ans:
(d)
Sol: For transmission line
Positive sequence impedance,
X1 = Xs − Xm = 0.4 − 0.1 = 0.3Ω/km
Zero sequence impedance,
X0 = Xs + 2Xm = 0.4 + 0.2 = 0.6Ω/km

Q38: A 500 MVA, 50 Hz, 3-phase turbo-generator produces power at 22 kV. Generator is Y-connected and its neutral is solidly grounded. It sequence reactances are X1 = X= 0.15 pu and X= 0.05 pu.It is operating at rated voltage and disconnected from the rest of the system (no load). The magnitude of the sub-transient line current for single line to ground fault at the generator terminal in pu will be        (2004)
(a) 2.851
(b) 3.333
(c) 6.667
(d) 8.553
Ans:
(d)
Sol: For single-line to ground fault,
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Since, the generator is operating at no-load and rated voltage
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Q39: A 3-phase transmission line supplies Δ-connected load Z. The conductor 'c' of the line develops an open circuit fault as shown in figure. The currents in the lines are as shown on the diagram. The positive sequence current component in line 'a' will be     (2004)
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE) (a) 5.78∠ − 30°
(b) 5.78 ∠ 90°
(c) 6.33 ∠ 90°
(d) 10.0 ∠ −30°
Ans:
(a)
Sol: Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Positive sequence current component in line 'a'
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Q40: A 3-phase generator rated at 110 MVA, 11 kV is connected through circuit breakers to a transformer. The generator is having direct axis sub-transient reactance Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)transient reactance Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE) and synchronous reactance = 130%. The generator is operating at no load and rated voltage when a three phase short circuit fault occurs between the breakers and the transformer. The magnitude of initial symmetrical rms current in the breakers will be       (2004)(a) 4.44 kA
(b) 22.20 kA
(c) 30.39 kA
(d) 38.45 kA
Ans: 
(c)
Sol: The generator is operating at no-load and rated voltage
So, Eg = 1.0∠0°p.u.
Initial symmetrical current
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Base current
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Q41: Three-phase alternator generating unbalanced voltages is connected to an unbalanced load through a 3-phase transmission line as shown in figure. The neutral of the alternator and the star point of the load are solidly grounded. The phase voltages of the alternator are  Ea = 10∠0°V,  E= 10∠−90°V, E= 10∠120°V. The positive sequence component of the load current is      (2003)
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)(a) 1.310107A1.310∠ − 107°A
(b) 0.332∠ − 120°A
(c) 0.996∠ − 120°A
(d) 3.51081A3.510∠ − 81°A
Ans: 
(d)
Sol: Since both sides are grounded, we can take it as 3 independent circuit.
Hence,
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Q42: A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive sequence, negative sequence and zero sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of the alternator is connected to ground through an inductive reactor of j0.05 p.u. The per unit positive, negative and zero sequence impedances of transmission line are j0.1, j0.1 and j0.3, respectively. All per unit values are based on the machine ratings. A solid ground fault occurs at one phase of the far end of the transmission line. The voltage of the alternator neutral with respect to ground during the fault is       (2003)
(a) 513.8 V
(b) 889.9 V
(c) 1112.0 V
(d) 642.2 V
Ans:
(d)
Sol: For alternator
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Equivalent sequence impedance:
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)For single line to ground fault
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Fault current = If = 3Ia1 = −j3.3708p.u.
Voltage of neutral w.r.t. ground
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Per phase base voltage
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)
Q43: A generator is connected to a transformer which feeds another transformer through a short feeder(as shown in figure). The zero sequence impedance values are expressed in pu on a common base and are indicated in figure. The Thevenin equivalent zero sequence impedance at point B is     (2002)
Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)(a) 0.8 + j0.6
(b) 0.75 + j0.22
(c) 0.75 + j0.25
(d) 1.5 + j0.25
Ans:
(b)
Sol: Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)ZTh = 0.75 + j0.22  

Q44: A 50 Hz alternator is rated 500 MVA, 20 kV, with Xd = 1.0 per unit and Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE) per unit. It supplies a purely resistive load of 400 MW at 20 kV. The load is connected directly across the generator terminals when a symmetrical fault occurs at the load terminals. The initial rms current in the generator in per unit is       (2001)(a) 7.22
(b) 6.4
(c) 3.22
(d) 2.2
Ans:
(b)
Sol: Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)

The document Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE) is a part of the Electrical Engineering (EE) Course Power Systems.
All you need of Electrical Engineering (EE) at this link: Electrical Engineering (EE)
21 videos|67 docs|45 tests

Top Courses for Electrical Engineering (EE)

FAQs on Previous Year Questions- Fault Analysis - 2 - Power Systems - Electrical Engineering (EE)

1. What is fault analysis in electrical engineering?
Ans. Fault analysis in electrical engineering involves identifying and analyzing faults or abnormalities in electrical systems to ensure the proper functioning and safety of the system.
2. What are the common types of faults in electrical systems?
Ans. Common types of faults in electrical systems include short circuits, open circuits, ground faults, overloads, and insulation breakdowns.
3. How is fault analysis carried out in electrical systems?
Ans. Fault analysis in electrical systems is carried out by performing tests, measurements, and inspections to pinpoint the location and nature of the fault. This may involve using specialized equipment and techniques.
4. Why is fault analysis important in electrical engineering?
Ans. Fault analysis is important in electrical engineering as it helps in maintaining the reliability and safety of electrical systems. By identifying and rectifying faults promptly, potential hazards and damage to equipment can be minimized.
5. What are the consequences of neglecting fault analysis in electrical systems?
Ans. Neglecting fault analysis in electrical systems can lead to equipment damage, power outages, safety hazards, and even fires. It is crucial to conduct regular fault analysis to prevent such issues and ensure the smooth operation of electrical systems.
21 videos|67 docs|45 tests
Download as PDF
Explore Courses for Electrical Engineering (EE) exam

Top Courses for Electrical Engineering (EE)

Signup for Free!
Signup to see your scores go up within 7 days! Learn & Practice with 1000+ FREE Notes, Videos & Tests.
10M+ students study on EduRev
Related Searches

Exam

,

mock tests for examination

,

study material

,

Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)

,

Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)

,

Summary

,

ppt

,

past year papers

,

Free

,

Important questions

,

Sample Paper

,

Viva Questions

,

Extra Questions

,

practice quizzes

,

Semester Notes

,

Objective type Questions

,

MCQs

,

pdf

,

Previous Year Questions with Solutions

,

Previous Year Questions- Fault Analysis - 2 | Power Systems - Electrical Engineering (EE)

,

video lectures

,

shortcuts and tricks

;