When two synchronous generators are connected in parallel to supply a common load, small differences in their angular positions (electrical phase) produce circulating currents and an internal torque that tends to restore synchronism. This restoring interaction is called synchronizing power (or synchronizing torque when expressed as torque). The synchronizing action makes parallel operation inherently stable within limits determined by the machines' reactances and the prime-mover control (governor) characteristics.
Consider two synchronous machines, labelled 1 and 2, connected in parallel and delivering power to the same external load. With respect to the supply/load busbars their generated e.m.f.s (internal generated voltages) are normally intended to be in phase. With respect to the local loop formed by the two armature windings, the e.m.f.s may be in near opposition. If one machine (say machine 1) momentarily accelerates so that its internal e.m.f. leads that of machine 2 by a small angle, a phase difference develops between the two internal e.m.f.s. This phase difference produces a circulating or local e.m.f. in the closed circuit of the two armatures and causes a circulating current Is to flow between the machines.
The circulating current flows through the synchronous impedances of the machines. Because the synchronous armature impedance is usually predominantly reactive (Xs ≫ r), the current Is lags the circulating e.m.f. by an angle close to 90°. As a result, the current leaving the faster machine is nearly in phase with its internal e.m.f. and enters the slower machine nearly in opposition to its internal e.m.f. Consequently the faster machine supplies additional electrical power to the slower machine (so the faster one is further loaded and the slower one is driven). This exchange of power produces a restoring torque that tends to reduce the phase difference and return both machines to synchronous running.
For two machines with internal generated e.m.f.s E1 and E2 (phasor magnitudes) and an electrical angular displacement δ between their internal e.m.f.s, the synchronizing power developed between them is given (for the usual model where synchronous reactance dominates) by the standard relation:
Ps = (E1·E2 / Xs) · sin δ
where Xs is the synchronous reactance (or the effective reactance in the path of the circulating current). Important points:
The argument in the classic description (qualitative) notes that the local e.m.f. arising from the phase difference is partly opposed by the synchronous reactances, so the circulating current lags by θ = arctan(Xs/r) ≈ 90° when reactance predominates. The effect is that the faster machine delivers electrical power to the slower one until speeds (and the internal phase) are again aligned.
Within the limits set by Ps,max, the two machines cannot be driven permanently out of step by small perturbations: any small angular divergence produces a synchronizing power that tends to restore synchronism. If the machines are too weakly coupled (large Xs, small E1·E2/Xs) or the perturbation is large enough to produce δ beyond the stable region, loss of synchronism (out-of-step) can occur.
If the armature impedance were not predominantly reactive (i.e., if resistance were large compared with reactance), the circulating current would not lag by near 90° and would not supply the required active power component to slow the faster machine and accelerate the slower one; stable parallel operation would then be compromised.
When both machines supply an external load and are equally loaded initially, a small phase displacement between their internal e.m.f.s produces the same type of synchronizing current as in the no-load case. The synchronizing current redistributes the load: the faster machine takes slightly more of the external load while the slower machine takes slightly less, until the angle settles at a value that balances synchronizing power and mechanical torque supplied by prime movers.
Notation often used: I1, I2 are the load currents before phase displacement, and I1′, I2′ are the currents after synchronizing circulation Is has superimposed. The circulating current adds algebraically to each machine's external load current (vectorially), altering the share of the load for each generator.
To safely and satisfactorily close the parallel breaker between two synchronous generators the following conditions must be satisfied:
Common practical synchronisation devices or methods are the synchronoscope and the lamp (dark-light) method, and protective synchonising/iscochronous relays. The usual procedure is to adjust prime-mover speed and excitation so that frequency, voltage and phase align, then close the breaker when the phase difference is near zero (or when lamps go dark in the lamp method).
Once paralleled, the way active (real) and reactive power are shared between machines depends on different controls:
If the governors or excitation characteristics of the machines are not identical, the steady share of real and reactive power will reflect those characteristic differences rather than the nameplate ratings. Synchronous machines must run at the same speed; therefore load sharing is achieved by suitable adjustment of prime-mover torque and excitation settings.
The typical governor characteristic (droop) shows that to increase power output some reduction of speed (or a change in governor setpoint) occurs; with unequal governor characteristics the machines will share total load according to the relative load values at the operating speed.
Real power stations seldom have perfectly identical machines. Differences in synchronous impedances (Zs1, Zs2), internal e.m.f.s (E1, E2), governor droop and excitation mean that parallel operation still works but the load distribution and transient behaviour depend on these parameters. Important practical points:
Key limitations and failure modes include:
Parallel operation of synchronous generators relies on the natural synchronizing power that appears when small phase differences develop between their internal e.m.f.s. This synchronizing power, which depends on machine e.m.f. magnitudes and synchronous reactance, tends to restore machines to the same electrical angle and maintain stable parallel operation within limits. Proper synchronising procedure, correct excitation and governor settings, and adequate protection are essential for safe and satisfactory sharing of active and reactive loads.
| 1. What is the purpose of parallel operation of two generators? | ![]() |
| 2. How does parallel operation of generators work? | ![]() |
| 3. What are the benefits of parallel operation of generators? | ![]() |
| 4. What precautions should be taken during parallel operation of generators? | ![]() |
| 5. Can generators with different power ratings be operated in parallel? | ![]() |
![]() | Explore Courses for Electrical Engineering (EE) exam |
![]() | Get EduRev Notes directly in your Google search |