PE Exam Exam  >  PE Exam Notes  >  Mechanical Engineering for PE  >  Formula Sheet: Psychrometrics

Formula Sheet: Psychrometrics

Fundamental Properties of Moist Air

Dry-Bulb Temperature

  • Dry-bulb temperature (Tdb or DBT): The actual temperature of air measured by a standard thermometer
  • Units: °F or °C

Wet-Bulb Temperature

  • Wet-bulb temperature (Twb or WBT): The temperature indicated by a thermometer covered with a water-saturated wick over which air is passed
  • Units: °F or °C
  • Note: Twb ≤ Tdb for unsaturated air; Twb = Tdb at saturation (100% RH)

Dew Point Temperature

  • Dew point temperature (Tdp or DPT): The temperature at which condensation begins when moist air is cooled at constant pressure
  • Units: °F or °C
  • Note: Tdp ≤ Twb ≤ Tdb for unsaturated air

Humidity Properties

Humidity Ratio (Absolute Humidity)

  • Humidity ratio (W): Mass of water vapor per unit mass of dry air
\[W = \frac{m_w}{m_a}\]
  • mw = mass of water vapor (lb or kg)
  • ma = mass of dry air (lb or kg)
  • Units: lbw/lba or kgw/kga (dimensionless ratio)

Humidity Ratio from Partial Pressures

\[W = 0.622 \frac{p_w}{p - p_w}\]
  • pw = partial pressure of water vapor (psia or kPa)
  • p = total atmospheric pressure (psia or kPa)
  • 0.622 = ratio of molecular weights (Mw/Ma = 18.015/28.965)
  • Note: (p - pw) = partial pressure of dry air

Relative Humidity

  • Relative humidity (φ or RH): Ratio of actual water vapor pressure to saturation pressure at the same temperature
\[\phi = \frac{p_w}{p_{ws}} \times 100\%\]
  • pw = partial pressure of water vapor (psia or kPa)
  • pws = saturation pressure of water vapor at dry-bulb temperature (psia or kPa)
  • Units: % (expressed as percentage)
  • Range: 0% (completely dry) to 100% (saturated)

Alternative Definition Using Humidity Ratios

\[\phi = \frac{W}{W_s} \times 100\%\]
  • W = actual humidity ratio (lbw/lba)
  • Ws = humidity ratio at saturation at the same temperature (lbw/lba)

Degree of Saturation

\[\mu = \frac{W}{W_s}\]
  • μ = degree of saturation (dimensionless ratio)
  • W = actual humidity ratio (lbw/lba)
  • Ws = humidity ratio at saturation (lbw/lba)
  • Note: Degree of saturation is similar to relative humidity but not identical

Saturation Humidity Ratio

\[W_s = 0.622 \frac{p_{ws}}{p - p_{ws}}\]
  • Ws = saturation humidity ratio (lbw/lba)
  • pws = saturation pressure at the given temperature (psia or kPa)
  • p = total atmospheric pressure (psia or kPa)

Specific Volume

Specific Volume of Moist Air

\[v = \frac{V}{m_a}\]
  • v = specific volume (ft³/lba or m³/kga)
  • V = total volume of moist air (ft³ or m³)
  • ma = mass of dry air (lba or kga)

Using Ideal Gas Law (US Customary Units)

\[v = \frac{R_a T}{p_a} = \frac{53.352 \, T}{p - p_w}\]
  • Ra = gas constant for dry air = 53.352 ft·lbf/(lba·°R)
  • T = absolute temperature (°R = °F + 459.67)
  • pa = partial pressure of dry air (psia)
  • p = total pressure (psia)
  • pw = partial pressure of water vapor (psia)
  • Units: ft³/lba

Using Ideal Gas Law (SI Units)

\[v = \frac{R_a T}{p_a} = \frac{287.055 \, T}{p - p_w}\]
  • Ra = gas constant for dry air = 287.055 J/(kg·K)
  • T = absolute temperature (K = °C + 273.15)
  • pa = partial pressure of dry air (kPa)
  • Units: m³/kga

Corrected for Water Vapor Content

\[v = \frac{R_a T}{p} (1 + 1.6078 \, W)\]
  • W = humidity ratio (lbw/lba)
  • 1.6078 = ratio Rw/Ra for water vapor to dry air

Enthalpy of Moist Air

Total Enthalpy

  • Enthalpy (h): Total heat content of moist air per unit mass of dry air
\[h = h_a + W \, h_w\]
  • h = total enthalpy of moist air (Btu/lba or kJ/kga)
  • ha = enthalpy of dry air (Btu/lba or kJ/kga)
  • W = humidity ratio (lbw/lba)
  • hw = enthalpy of water vapor (Btu/lbw or kJ/kgw)

Standard Approximation (US Customary)

\[h = 0.240 \, T_{db} + W (1061 + 0.444 \, T_{db})\]
  • h = enthalpy (Btu/lba)
  • Tdb = dry-bulb temperature (°F)
  • W = humidity ratio (lbw/lba)
  • 0.240 = specific heat of dry air (Btu/(lba·°F))
  • 1061 = latent heat of vaporization at 0°F (Btu/lbw)
  • 0.444 = specific heat of water vapor (Btu/(lbw·°F))

Standard Approximation (SI)

\[h = 1.006 \, T_{db} + W (2501 + 1.86 \, T_{db})\]
  • h = enthalpy (kJ/kga)
  • Tdb = dry-bulb temperature (°C)
  • W = humidity ratio (kgw/kga)
  • 1.006 = specific heat of dry air (kJ/(kga·K))
  • 2501 = latent heat of vaporization at 0°C (kJ/kgw)
  • 1.86 = specific heat of water vapor (kJ/(kgw·K))

Enthalpy at Saturation

\[h_s = c_{pa} T + W_s (h_{fg} + c_{pw} T)\]
  • hs = enthalpy at saturation (Btu/lba or kJ/kga)
  • cpa = specific heat of dry air
  • Ws = saturation humidity ratio
  • hfg = latent heat of vaporization
  • cpw = specific heat of water vapor

Psychrometric Processes

Sensible Heating or Cooling

  • Process: Temperature changes with no change in moisture content (W = constant)
  • Horizontal line on psychrometric chart (left to right for heating, right to left for cooling)
\[q_s = m_a \, c_{pa} (T_2 - T_1)\]
  • qs = sensible heat transfer rate (Btu/hr or kW)
  • ma = mass flow rate of dry air (lba/hr or kga/s)
  • cpa = specific heat of dry air = 0.240 Btu/(lba·°F) or 1.006 kJ/(kga·K)
  • T2, T1 = final and initial dry-bulb temperatures

Using Enthalpy Difference

\[q_s = m_a (h_2 - h_1) = 60 \, \rho \, Q (h_2 - h_1)\]
  • ρ = density of air (lba/ft³ or kga/m³)
  • Q = volumetric flow rate (CFM or m³/s)
  • 60 = conversion factor for CFM to ft³/hr (US units only)

Humidification (Adding Moisture)

  • Process: Adding water vapor to air
\[m_w = m_a (W_2 - W_1)\]
  • mw = mass flow rate of water added (lbw/hr or kgw/s)
  • ma = mass flow rate of dry air (lba/hr or kga/s)
  • W2, W1 = final and initial humidity ratios

Energy Balance for Humidification

\[m_a h_1 + m_w h_w = m_a h_2\]
  • h1 = initial enthalpy of air (Btu/lba or kJ/kga)
  • h2 = final enthalpy of air (Btu/lba or kJ/kga)
  • hw = enthalpy of water added (Btu/lbw or kJ/kgw)

Dehumidification (Removing Moisture)

  • Process: Cooling below dew point to condense and remove water vapor
\[m_w = m_a (W_1 - W_2)\]
  • mw = mass flow rate of condensate removed (lbw/hr or kgw/s)
  • W1, W2 = initial and final humidity ratios

Cooling and Dehumidification Heat Transfer

\[q_t = m_a (h_1 - h_2)\]
  • qt = total heat removal rate (Btu/hr or kW)
  • h1 = initial enthalpy (Btu/lba or kJ/kga)
  • h2 = final enthalpy (Btu/lba or kJ/kga)

Adiabatic Mixing of Air Streams

  • Process: Combining two air streams with no external heat transfer

Mass Balance for Dry Air

\[m_{a3} = m_{a1} + m_{a2}\]
  • ma1, ma2 = mass flow rates of dry air in streams 1 and 2
  • ma3 = mass flow rate of dry air in mixed stream 3

Mass Balance for Water Vapor

\[m_{a3} W_3 = m_{a1} W_1 + m_{a2} W_2\] \[W_3 = \frac{m_{a1} W_1 + m_{a2} W_2}{m_{a1} + m_{a2}}\]
  • W1, W2, W3 = humidity ratios of streams 1, 2, and 3

Energy Balance

\[m_{a3} h_3 = m_{a1} h_1 + m_{a2} h_2\] \[h_3 = \frac{m_{a1} h_1 + m_{a2} h_2}{m_{a1} + m_{a2}}\]
  • h1, h2, h3 = enthalpies of streams 1, 2, and 3

Mixing Ratio

\[\frac{m_{a1}}{m_{a2}} = \frac{W_3 - W_2}{W_1 - W_3} = \frac{h_3 - h_2}{h_1 - h_3}\]
  • Note: The mixed state point lies on a straight line connecting states 1 and 2 on the psychrometric chart

Adiabatic Saturation

  • Process: Air passes over water in an insulated chamber until saturated
  • Final temperature = wet-bulb temperature (for water)
\[h_1 + (W_s - W_1) h_w = h_s\]
  • h1 = initial enthalpy of air (Btu/lba or kJ/kga)
  • W1 = initial humidity ratio
  • Ws = saturation humidity ratio at final temperature
  • hw = enthalpy of makeup water
  • hs = enthalpy at saturation (final state)

Evaporative Cooling

  • Process: Adding water to unsaturated air in an adiabatic process
  • Follows constant wet-bulb temperature line on psychrometric chart
  • Dry-bulb temperature decreases, humidity ratio increases
  • Enthalpy remains approximately constant
\[h_1 \approx h_2\]
  • Note: Process follows lines of constant wet-bulb temperature sloping downward to the right

Sensible Heat Factor (SHF)

Definition

\[SHF = \frac{q_s}{q_t} = \frac{q_s}{q_s + q_l}\]
  • SHF = sensible heat factor (dimensionless ratio)
  • qs = sensible heat load (Btu/hr or kW)
  • qt = total heat load (Btu/hr or kW)
  • ql = latent heat load (Btu/hr or kW)
  • Range: 0 to 1 (0 = pure latent load, 1 = pure sensible load)

Using Enthalpy and Temperature

\[SHF = \frac{c_{pa} (T_2 - T_1)}{h_2 - h_1}\]
  • T2, T1 = final and initial temperatures
  • h2, h1 = final and initial enthalpies

Latent Heat Load

\[q_l = m_a (W_2 - W_1) h_{fg}\]
  • ql = latent heat load (Btu/hr or kW)
  • W2, W1 = final and initial humidity ratios
  • hfg = latent heat of vaporization ≈ 1060 Btu/lbw or 2501 kJ/kgw

Simplified Form (US Customary)

\[q_l = 4840 \, Q (W_2 - W_1)\]
  • Q = volumetric flow rate (CFM)
  • 4840 = conversion factor (approximately 60 × 0.075 × 1076)
  • Units: Btu/hr

Psychrometric Chart Applications

Chart Components

  • Horizontal axis: Dry-bulb temperature
  • Vertical axis (right): Humidity ratio
  • Curved lines: Constant relative humidity
  • Nearly vertical lines: Constant wet-bulb temperature
  • Curved saturation line: 100% relative humidity (φ = 100%)
  • Diagonal lines: Constant enthalpy (nearly parallel to wet-bulb lines)
  • Oblique lines: Constant specific volume

Process Lines on Chart

  • Sensible heating: Horizontal line to the right (W constant, T increases)
  • Sensible cooling: Horizontal line to the left (W constant, T decreases)
  • Humidification (steam injection): Vertical or nearly vertical upward (W increases)
  • Cooling and dehumidification: Downward and to the left
  • Evaporative cooling: Along constant wet-bulb line, downward to right
  • Heating and humidification: Upward and to the right
  • Adiabatic mixing: Straight line connecting two state points

Density and Volumetric Flow Relationships

Density of Moist Air

\[\rho = \frac{1}{v}\]
  • ρ = density of moist air (lba/ft³ or kga/m³)
  • v = specific volume (ft³/lba or m³/kga)

From Ideal Gas Law

\[\rho = \frac{p}{R_a T (1 + 1.6078 \, W)}\]
  • p = atmospheric pressure (psia or kPa)
  • Ra = gas constant for dry air
  • T = absolute temperature (°R or K)
  • W = humidity ratio

Mass Flow Rate from Volumetric Flow

\[m_a = \frac{Q}{v} = \rho \, Q\]
  • ma = mass flow rate of dry air (lba/min or kga/s)
  • Q = volumetric flow rate (CFM or m³/s)
  • v = specific volume (ft³/lba or m³/kga)
  • ρ = density (lba/ft³ or kga/m³)

Conversion to Standard Flow Rate (US Customary)

\[m_a = \frac{Q \times 60}{v}\]
  • Q = volumetric flow rate (CFM)
  • 60 = conversion from minutes to hours
  • ma = mass flow rate (lba/hr)

Heat and Mass Transfer Rates

Total Heat Transfer Rate

\[q_t = m_a (h_2 - h_1)\]
  • qt = total heat transfer rate (Btu/hr or kW)
  • ma = mass flow rate of dry air (lba/hr or kga/s)
  • h2, h1 = final and initial enthalpies (Btu/lba or kJ/kga)

Using Volumetric Flow (US Customary)

\[q_t = 60 \, \rho \, Q (h_2 - h_1) = 4.5 \, Q (h_2 - h_1)\]
  • Q = volumetric flow rate (CFM)
  • ρ = density ≈ 0.075 lba/ft³ (standard air)
  • 4.5 = approximate conversion factor (60 × 0.075)
  • Units: Btu/hr

Sensible Heat Rate

\[q_s = m_a \, c_{pa} (T_2 - T_1)\]
  • cpa = 0.240 Btu/(lba·°F) or 1.006 kJ/(kga·K)

Using Volumetric Flow (US Customary)

\[q_s = 1.08 \, Q (T_2 - T_1)\]
  • Q = volumetric flow rate (CFM)
  • T2, T1 = final and initial temperatures (°F)
  • 1.08 = conversion factor (60 × 0.075 × 0.240)
  • Units: Btu/hr

Using Volumetric Flow (SI)

\[q_s = 1.2 \, Q (T_2 - T_1)\]
  • Q = volumetric flow rate (m³/s)
  • T2, T1 = final and initial temperatures (°C)
  • 1.2 = approximate conversion factor (ρ × cpa ≈ 1.2 × 1.006)
  • Units: kW

Latent Heat Rate

\[q_l = m_a \, h_{fg} (W_2 - W_1)\]
  • hfg = latent heat of vaporization ≈ 1060 Btu/lbw or 2501 kJ/kgw

Using Volumetric Flow (US Customary)

\[q_l = 4840 \, Q (W_2 - W_1)\]
  • Q = volumetric flow rate (CFM)
  • W2, W1 = final and initial humidity ratios (lbw/lba)
  • 4840 = conversion factor (60 × 0.075 × 1076)
  • Units: Btu/hr

Cooling Coil Performance

Apparatus Dew Point (ADP)

  • Apparatus dew point: The effective surface temperature of a cooling coil
  • Represents the temperature at which all air would exit if the coil had 100% contact efficiency
  • Located on saturation curve of psychrometric chart

Bypass Factor

\[BF = \frac{T_2 - T_{ADP}}{T_1 - T_{ADP}}\]
  • BF = bypass factor (fraction of air that bypasses the coil without contact)
  • T1 = entering air dry-bulb temperature
  • T2 = leaving air dry-bulb temperature
  • TADP = apparatus dew point temperature
  • Range: 0 to 1 (0 = perfect contact, 1 = no contact)

Contact Factor

\[CF = 1 - BF = \frac{T_1 - T_2}{T_1 - T_{ADP}}\]
  • CF = contact factor (fraction of air effectively contacting the coil)
  • Range: 0 to 1 (1 = perfect contact)

Coil Heat Removal

\[q_{coil} = m_a (h_1 - h_2)\]
  • qcoil = total heat removal by coil (Btu/hr or kW)
  • h1 = enthalpy of entering air
  • h2 = enthalpy of leaving air

Standard Air Conditions

Standard Air Properties (US Customary)

  • Temperature: 70°F (529.67°R)
  • Pressure: 14.696 psia (1 atm)
  • Relative humidity: 0% (dry air)
  • Density: 0.075 lb/ft³
  • Specific volume: 13.33 ft³/lb

Standard Air Properties (SI)

  • Temperature: 20°C (293.15 K)
  • Pressure: 101.325 kPa (1 atm)
  • Relative humidity: 0% (dry air)
  • Density: 1.204 kg/m³
  • Specific volume: 0.8305 m³/kg

Useful Conversion Factors

Temperature Conversions

  • °F to °R: °R = °F + 459.67
  • °C to K: K = °C + 273.15
  • °F to °C: °C = (°F - 32) / 1.8
  • °C to °F: °F = 1.8 × °C + 32

Pressure Conversions

  • 1 atm = 14.696 psia = 101.325 kPa
  • 1 psi = 6.895 kPa
  • 1 in Hg = 0.4912 psi = 3.386 kPa

Common Constants

  • Gas constant for dry air (Ra): 53.352 ft·lbf/(lba·°R) or 287.055 J/(kga·K)
  • Gas constant for water vapor (Rw): 85.78 ft·lbf/(lbw·°R) or 461.52 J/(kgw·K)
  • Molecular weight ratio (Mw/Ma): 0.622
  • Specific heat of dry air (cpa): 0.240 Btu/(lba·°F) or 1.006 kJ/(kga·K)
  • Specific heat of water vapor (cpw): 0.444 Btu/(lbw·°F) or 1.86 kJ/(kgw·K)
  • Latent heat of vaporization (hfg): ≈ 1060 Btu/lbw at 70°F or ≈ 2501 kJ/kgw at 0°C
The document Formula Sheet: Psychrometrics is a part of the PE Exam Course Mechanical Engineering for PE.
All you need of PE Exam at this link: PE Exam
Explore Courses for PE Exam exam
Get EduRev Notes directly in your Google search
Related Searches
MCQs, pdf , Previous Year Questions with Solutions, Objective type Questions, Formula Sheet: Psychrometrics, Extra Questions, video lectures, Exam, Free, Viva Questions, shortcuts and tricks, Summary, Important questions, mock tests for examination, Sample Paper, practice quizzes, study material, Formula Sheet: Psychrometrics, Formula Sheet: Psychrometrics, ppt, Semester Notes, past year papers;