Fundamental Properties of Moist Air
Dry-Bulb Temperature
- Dry-bulb temperature (Tdb or DBT): The actual temperature of air measured by a standard thermometer
- Units: °F or °C
Wet-Bulb Temperature
- Wet-bulb temperature (Twb or WBT): The temperature indicated by a thermometer covered with a water-saturated wick over which air is passed
- Units: °F or °C
- Note: Twb ≤ Tdb for unsaturated air; Twb = Tdb at saturation (100% RH)
Dew Point Temperature
- Dew point temperature (Tdp or DPT): The temperature at which condensation begins when moist air is cooled at constant pressure
- Units: °F or °C
- Note: Tdp ≤ Twb ≤ Tdb for unsaturated air
Humidity Properties
Humidity Ratio (Absolute Humidity)
- Humidity ratio (W): Mass of water vapor per unit mass of dry air
\[W = \frac{m_w}{m_a}\]
- mw = mass of water vapor (lb or kg)
- ma = mass of dry air (lb or kg)
- Units: lbw/lba or kgw/kga (dimensionless ratio)
Humidity Ratio from Partial Pressures
\[W = 0.622 \frac{p_w}{p - p_w}\]
- pw = partial pressure of water vapor (psia or kPa)
- p = total atmospheric pressure (psia or kPa)
- 0.622 = ratio of molecular weights (Mw/Ma = 18.015/28.965)
- Note: (p - pw) = partial pressure of dry air
Relative Humidity
- Relative humidity (φ or RH): Ratio of actual water vapor pressure to saturation pressure at the same temperature
\[\phi = \frac{p_w}{p_{ws}} \times 100\%\]
- pw = partial pressure of water vapor (psia or kPa)
- pws = saturation pressure of water vapor at dry-bulb temperature (psia or kPa)
- Units: % (expressed as percentage)
- Range: 0% (completely dry) to 100% (saturated)
Alternative Definition Using Humidity Ratios
\[\phi = \frac{W}{W_s} \times 100\%\]
- W = actual humidity ratio (lbw/lba)
- Ws = humidity ratio at saturation at the same temperature (lbw/lba)
Degree of Saturation
\[\mu = \frac{W}{W_s}\]
- μ = degree of saturation (dimensionless ratio)
- W = actual humidity ratio (lbw/lba)
- Ws = humidity ratio at saturation (lbw/lba)
- Note: Degree of saturation is similar to relative humidity but not identical
Saturation Humidity Ratio
\[W_s = 0.622 \frac{p_{ws}}{p - p_{ws}}\]
- Ws = saturation humidity ratio (lbw/lba)
- pws = saturation pressure at the given temperature (psia or kPa)
- p = total atmospheric pressure (psia or kPa)
Specific Volume
Specific Volume of Moist Air
\[v = \frac{V}{m_a}\]
- v = specific volume (ft³/lba or m³/kga)
- V = total volume of moist air (ft³ or m³)
- ma = mass of dry air (lba or kga)
Using Ideal Gas Law (US Customary Units)
\[v = \frac{R_a T}{p_a} = \frac{53.352 \, T}{p - p_w}\]
- Ra = gas constant for dry air = 53.352 ft·lbf/(lba·°R)
- T = absolute temperature (°R = °F + 459.67)
- pa = partial pressure of dry air (psia)
- p = total pressure (psia)
- pw = partial pressure of water vapor (psia)
- Units: ft³/lba
Using Ideal Gas Law (SI Units)
\[v = \frac{R_a T}{p_a} = \frac{287.055 \, T}{p - p_w}\]
- Ra = gas constant for dry air = 287.055 J/(kg·K)
- T = absolute temperature (K = °C + 273.15)
- pa = partial pressure of dry air (kPa)
- Units: m³/kga
Corrected for Water Vapor Content
\[v = \frac{R_a T}{p} (1 + 1.6078 \, W)\]
- W = humidity ratio (lbw/lba)
- 1.6078 = ratio Rw/Ra for water vapor to dry air
Enthalpy of Moist Air
Total Enthalpy
- Enthalpy (h): Total heat content of moist air per unit mass of dry air
\[h = h_a + W \, h_w\]
- h = total enthalpy of moist air (Btu/lba or kJ/kga)
- ha = enthalpy of dry air (Btu/lba or kJ/kga)
- W = humidity ratio (lbw/lba)
- hw = enthalpy of water vapor (Btu/lbw or kJ/kgw)
Standard Approximation (US Customary)
\[h = 0.240 \, T_{db} + W (1061 + 0.444 \, T_{db})\]
- h = enthalpy (Btu/lba)
- Tdb = dry-bulb temperature (°F)
- W = humidity ratio (lbw/lba)
- 0.240 = specific heat of dry air (Btu/(lba·°F))
- 1061 = latent heat of vaporization at 0°F (Btu/lbw)
- 0.444 = specific heat of water vapor (Btu/(lbw·°F))
Standard Approximation (SI)
\[h = 1.006 \, T_{db} + W (2501 + 1.86 \, T_{db})\]
- h = enthalpy (kJ/kga)
- Tdb = dry-bulb temperature (°C)
- W = humidity ratio (kgw/kga)
- 1.006 = specific heat of dry air (kJ/(kga·K))
- 2501 = latent heat of vaporization at 0°C (kJ/kgw)
- 1.86 = specific heat of water vapor (kJ/(kgw·K))
Enthalpy at Saturation
\[h_s = c_{pa} T + W_s (h_{fg} + c_{pw} T)\]
- hs = enthalpy at saturation (Btu/lba or kJ/kga)
- cpa = specific heat of dry air
- Ws = saturation humidity ratio
- hfg = latent heat of vaporization
- cpw = specific heat of water vapor
Psychrometric Processes
Sensible Heating or Cooling
- Process: Temperature changes with no change in moisture content (W = constant)
- Horizontal line on psychrometric chart (left to right for heating, right to left for cooling)
\[q_s = m_a \, c_{pa} (T_2 - T_1)\]
- qs = sensible heat transfer rate (Btu/hr or kW)
- ma = mass flow rate of dry air (lba/hr or kga/s)
- cpa = specific heat of dry air = 0.240 Btu/(lba·°F) or 1.006 kJ/(kga·K)
- T2, T1 = final and initial dry-bulb temperatures
Using Enthalpy Difference
\[q_s = m_a (h_2 - h_1) = 60 \, \rho \, Q (h_2 - h_1)\]
- ρ = density of air (lba/ft³ or kga/m³)
- Q = volumetric flow rate (CFM or m³/s)
- 60 = conversion factor for CFM to ft³/hr (US units only)
Humidification (Adding Moisture)
- Process: Adding water vapor to air
\[m_w = m_a (W_2 - W_1)\]
- mw = mass flow rate of water added (lbw/hr or kgw/s)
- ma = mass flow rate of dry air (lba/hr or kga/s)
- W2, W1 = final and initial humidity ratios
Energy Balance for Humidification
\[m_a h_1 + m_w h_w = m_a h_2\]
- h1 = initial enthalpy of air (Btu/lba or kJ/kga)
- h2 = final enthalpy of air (Btu/lba or kJ/kga)
- hw = enthalpy of water added (Btu/lbw or kJ/kgw)
Dehumidification (Removing Moisture)
- Process: Cooling below dew point to condense and remove water vapor
\[m_w = m_a (W_1 - W_2)\]
- mw = mass flow rate of condensate removed (lbw/hr or kgw/s)
- W1, W2 = initial and final humidity ratios
Cooling and Dehumidification Heat Transfer
\[q_t = m_a (h_1 - h_2)\]
- qt = total heat removal rate (Btu/hr or kW)
- h1 = initial enthalpy (Btu/lba or kJ/kga)
- h2 = final enthalpy (Btu/lba or kJ/kga)
Adiabatic Mixing of Air Streams
- Process: Combining two air streams with no external heat transfer
Mass Balance for Dry Air
\[m_{a3} = m_{a1} + m_{a2}\]
- ma1, ma2 = mass flow rates of dry air in streams 1 and 2
- ma3 = mass flow rate of dry air in mixed stream 3
Mass Balance for Water Vapor
\[m_{a3} W_3 = m_{a1} W_1 + m_{a2} W_2\] \[W_3 = \frac{m_{a1} W_1 + m_{a2} W_2}{m_{a1} + m_{a2}}\]
- W1, W2, W3 = humidity ratios of streams 1, 2, and 3
Energy Balance
\[m_{a3} h_3 = m_{a1} h_1 + m_{a2} h_2\] \[h_3 = \frac{m_{a1} h_1 + m_{a2} h_2}{m_{a1} + m_{a2}}\]
- h1, h2, h3 = enthalpies of streams 1, 2, and 3
Mixing Ratio
\[\frac{m_{a1}}{m_{a2}} = \frac{W_3 - W_2}{W_1 - W_3} = \frac{h_3 - h_2}{h_1 - h_3}\]
- Note: The mixed state point lies on a straight line connecting states 1 and 2 on the psychrometric chart
Adiabatic Saturation
- Process: Air passes over water in an insulated chamber until saturated
- Final temperature = wet-bulb temperature (for water)
\[h_1 + (W_s - W_1) h_w = h_s\]
- h1 = initial enthalpy of air (Btu/lba or kJ/kga)
- W1 = initial humidity ratio
- Ws = saturation humidity ratio at final temperature
- hw = enthalpy of makeup water
- hs = enthalpy at saturation (final state)
Evaporative Cooling
- Process: Adding water to unsaturated air in an adiabatic process
- Follows constant wet-bulb temperature line on psychrometric chart
- Dry-bulb temperature decreases, humidity ratio increases
- Enthalpy remains approximately constant
\[h_1 \approx h_2\]
- Note: Process follows lines of constant wet-bulb temperature sloping downward to the right
Sensible Heat Factor (SHF)
Definition
\[SHF = \frac{q_s}{q_t} = \frac{q_s}{q_s + q_l}\]
- SHF = sensible heat factor (dimensionless ratio)
- qs = sensible heat load (Btu/hr or kW)
- qt = total heat load (Btu/hr or kW)
- ql = latent heat load (Btu/hr or kW)
- Range: 0 to 1 (0 = pure latent load, 1 = pure sensible load)
Using Enthalpy and Temperature
\[SHF = \frac{c_{pa} (T_2 - T_1)}{h_2 - h_1}\]
- T2, T1 = final and initial temperatures
- h2, h1 = final and initial enthalpies
Latent Heat Load
\[q_l = m_a (W_2 - W_1) h_{fg}\]
- ql = latent heat load (Btu/hr or kW)
- W2, W1 = final and initial humidity ratios
- hfg = latent heat of vaporization ≈ 1060 Btu/lbw or 2501 kJ/kgw
Simplified Form (US Customary)
\[q_l = 4840 \, Q (W_2 - W_1)\]
- Q = volumetric flow rate (CFM)
- 4840 = conversion factor (approximately 60 × 0.075 × 1076)
- Units: Btu/hr
Psychrometric Chart Applications
Chart Components
- Horizontal axis: Dry-bulb temperature
- Vertical axis (right): Humidity ratio
- Curved lines: Constant relative humidity
- Nearly vertical lines: Constant wet-bulb temperature
- Curved saturation line: 100% relative humidity (φ = 100%)
- Diagonal lines: Constant enthalpy (nearly parallel to wet-bulb lines)
- Oblique lines: Constant specific volume
Process Lines on Chart
- Sensible heating: Horizontal line to the right (W constant, T increases)
- Sensible cooling: Horizontal line to the left (W constant, T decreases)
- Humidification (steam injection): Vertical or nearly vertical upward (W increases)
- Cooling and dehumidification: Downward and to the left
- Evaporative cooling: Along constant wet-bulb line, downward to right
- Heating and humidification: Upward and to the right
- Adiabatic mixing: Straight line connecting two state points
Density and Volumetric Flow Relationships
Density of Moist Air
\[\rho = \frac{1}{v}\]
- ρ = density of moist air (lba/ft³ or kga/m³)
- v = specific volume (ft³/lba or m³/kga)
From Ideal Gas Law
\[\rho = \frac{p}{R_a T (1 + 1.6078 \, W)}\]
- p = atmospheric pressure (psia or kPa)
- Ra = gas constant for dry air
- T = absolute temperature (°R or K)
- W = humidity ratio
Mass Flow Rate from Volumetric Flow
\[m_a = \frac{Q}{v} = \rho \, Q\]
- ma = mass flow rate of dry air (lba/min or kga/s)
- Q = volumetric flow rate (CFM or m³/s)
- v = specific volume (ft³/lba or m³/kga)
- ρ = density (lba/ft³ or kga/m³)
Conversion to Standard Flow Rate (US Customary)
\[m_a = \frac{Q \times 60}{v}\]
- Q = volumetric flow rate (CFM)
- 60 = conversion from minutes to hours
- ma = mass flow rate (lba/hr)
Heat and Mass Transfer Rates
Total Heat Transfer Rate
\[q_t = m_a (h_2 - h_1)\]
- qt = total heat transfer rate (Btu/hr or kW)
- ma = mass flow rate of dry air (lba/hr or kga/s)
- h2, h1 = final and initial enthalpies (Btu/lba or kJ/kga)
Using Volumetric Flow (US Customary)
\[q_t = 60 \, \rho \, Q (h_2 - h_1) = 4.5 \, Q (h_2 - h_1)\]
- Q = volumetric flow rate (CFM)
- ρ = density ≈ 0.075 lba/ft³ (standard air)
- 4.5 = approximate conversion factor (60 × 0.075)
- Units: Btu/hr
Sensible Heat Rate
\[q_s = m_a \, c_{pa} (T_2 - T_1)\]
- cpa = 0.240 Btu/(lba·°F) or 1.006 kJ/(kga·K)
Using Volumetric Flow (US Customary)
\[q_s = 1.08 \, Q (T_2 - T_1)\]
- Q = volumetric flow rate (CFM)
- T2, T1 = final and initial temperatures (°F)
- 1.08 = conversion factor (60 × 0.075 × 0.240)
- Units: Btu/hr
Using Volumetric Flow (SI)
\[q_s = 1.2 \, Q (T_2 - T_1)\]
- Q = volumetric flow rate (m³/s)
- T2, T1 = final and initial temperatures (°C)
- 1.2 = approximate conversion factor (ρ × cpa ≈ 1.2 × 1.006)
- Units: kW
Latent Heat Rate
\[q_l = m_a \, h_{fg} (W_2 - W_1)\]
- hfg = latent heat of vaporization ≈ 1060 Btu/lbw or 2501 kJ/kgw
Using Volumetric Flow (US Customary)
\[q_l = 4840 \, Q (W_2 - W_1)\]
- Q = volumetric flow rate (CFM)
- W2, W1 = final and initial humidity ratios (lbw/lba)
- 4840 = conversion factor (60 × 0.075 × 1076)
- Units: Btu/hr
Apparatus Dew Point (ADP)
- Apparatus dew point: The effective surface temperature of a cooling coil
- Represents the temperature at which all air would exit if the coil had 100% contact efficiency
- Located on saturation curve of psychrometric chart
Bypass Factor
\[BF = \frac{T_2 - T_{ADP}}{T_1 - T_{ADP}}\]
- BF = bypass factor (fraction of air that bypasses the coil without contact)
- T1 = entering air dry-bulb temperature
- T2 = leaving air dry-bulb temperature
- TADP = apparatus dew point temperature
- Range: 0 to 1 (0 = perfect contact, 1 = no contact)
Contact Factor
\[CF = 1 - BF = \frac{T_1 - T_2}{T_1 - T_{ADP}}\]
- CF = contact factor (fraction of air effectively contacting the coil)
- Range: 0 to 1 (1 = perfect contact)
Coil Heat Removal
\[q_{coil} = m_a (h_1 - h_2)\]
- qcoil = total heat removal by coil (Btu/hr or kW)
- h1 = enthalpy of entering air
- h2 = enthalpy of leaving air
Standard Air Conditions
Standard Air Properties (US Customary)
- Temperature: 70°F (529.67°R)
- Pressure: 14.696 psia (1 atm)
- Relative humidity: 0% (dry air)
- Density: 0.075 lb/ft³
- Specific volume: 13.33 ft³/lb
Standard Air Properties (SI)
- Temperature: 20°C (293.15 K)
- Pressure: 101.325 kPa (1 atm)
- Relative humidity: 0% (dry air)
- Density: 1.204 kg/m³
- Specific volume: 0.8305 m³/kg
Useful Conversion Factors
Temperature Conversions
- °F to °R: °R = °F + 459.67
- °C to K: K = °C + 273.15
- °F to °C: °C = (°F - 32) / 1.8
- °C to °F: °F = 1.8 × °C + 32
Pressure Conversions
- 1 atm = 14.696 psia = 101.325 kPa
- 1 psi = 6.895 kPa
- 1 in Hg = 0.4912 psi = 3.386 kPa
Common Constants
- Gas constant for dry air (Ra): 53.352 ft·lbf/(lba·°R) or 287.055 J/(kga·K)
- Gas constant for water vapor (Rw): 85.78 ft·lbf/(lbw·°R) or 461.52 J/(kgw·K)
- Molecular weight ratio (Mw/Ma): 0.622
- Specific heat of dry air (cpa): 0.240 Btu/(lba·°F) or 1.006 kJ/(kga·K)
- Specific heat of water vapor (cpw): 0.444 Btu/(lbw·°F) or 1.86 kJ/(kgw·K)
- Latent heat of vaporization (hfg): ≈ 1060 Btu/lbw at 70°F or ≈ 2501 kJ/kgw at 0°C