PE Exam Exam  >  PE Exam Notes  >  Mechanical Engineering for PE  >  Formula Sheet: HVAC Systems

Formula Sheet: HVAC Systems

Psychrometrics

Properties of Moist Air

Humidity Ratio (Specific Humidity): \[W = \frac{m_w}{m_a} = 0.622 \frac{p_w}{p - p_w}\]
  • W = humidity ratio (lbw/lbda or kgw/kgda)
  • mw = mass of water vapor (lb or kg)
  • ma = mass of dry air (lb or kg)
  • pw = partial pressure of water vapor (psia or kPa)
  • p = total atmospheric pressure (psia or kPa)
  • Valid for ideal gas behavior
Relative Humidity: \[\phi = \frac{p_w}{p_{ws}} = \frac{W \cdot p}{(0.622 + W) \cdot p_{ws}}\]
  • φ = relative humidity (decimal or %)
  • pws = saturation pressure of water vapor at dry-bulb temperature (psia or kPa)
  • 0 ≤ φ ≤ 1 (or 0% to 100%)
Degree of Saturation: \[\mu = \frac{W}{W_s}\]
  • μ = degree of saturation (decimal)
  • Ws = humidity ratio at saturation
Dew Point Temperature:
  • Temperature at which water vapor begins to condense at constant pressure and humidity ratio
  • Found from saturation tables where pws(Tdp) = pw
  • Tdp = dew point temperature (°F or °C)

Enthalpy of Moist Air

Total Enthalpy: \[h = h_a + W \cdot h_g\] \[h = c_p \cdot T + W(h_{fg} + c_{pw} \cdot T)\] Simplified (common approximation): \[h = 0.240 \cdot T + W(1061 + 0.444 \cdot T)\]
  • h = enthalpy of moist air (Btu/lbda or kJ/kgda)
  • ha = enthalpy of dry air (Btu/lbda or kJ/kgda)
  • hg = enthalpy of water vapor (Btu/lbw or kJ/kgw)
  • cp = specific heat of dry air = 0.240 Btu/lb·°F (0.24 Btu/lbda·°F or 1.006 kJ/kgda·K)
  • cpw = specific heat of water vapor = 0.444 Btu/lb·°F (1.86 kJ/kg·K)
  • T = dry-bulb temperature (°F or °C)
  • hfg = latent heat of vaporization at 0°F ≈ 1061 Btu/lb (2501 kJ/kg at 0°C)

Specific Volume and Density

Specific Volume of Moist Air: \[v = \frac{R_a \cdot T}{p - p_w} = \frac{53.35(T + 460)}{144 \cdot p} (1 + 1.6078W)\]
  • v = specific volume (ft³/lbda or m³/kgda)
  • Ra = gas constant for dry air = 53.35 ft·lbf/lb·°R (287 J/kg·K)
  • T = absolute temperature (°R or K)
  • For US units: T in °R = °F + 460, p in psia
Density of Moist Air: \[\rho = \frac{1}{v} = \frac{1 + W}{v}\]
  • ρ = density of moist air (lb/ft³ or kg/m³)

Wet-Bulb Temperature

Relationship (approximate): \[W_s - W = \frac{c_p(T - T_{wb})}{h_{fg}}\]
  • Twb = wet-bulb temperature (°F or °C)
  • Ws = saturation humidity ratio at wet-bulb temperature
  • Typically found using psychrometric chart or tables

Cooling and Heating Load Calculations

Sensible Heat Transfer

Sensible Heat Load: \[q_s = \dot{m}_a \cdot c_p \cdot \Delta T = 1.08 \cdot Q \cdot \Delta T\]
  • qs = sensible heat load (Btu/hr or kW)
  • a = mass flow rate of dry air (lbda/hr or kgda/s)
  • Q = volumetric flow rate (cfm or L/s)
  • ΔT = temperature difference (°F or °C)
  • 1.08 = conversion factor for standard air (60 × 0.075 × 0.24)
  • For SI units: qs = 1.23 × Q × ΔT (Q in L/s, result in watts)
Alternative Form: \[q_s = 60 \cdot \rho \cdot Q \cdot c_p \cdot \Delta T\]
  • ρ = air density (lb/ft³ or kg/m³)
  • 60 = conversion factor (minutes per hour)

Latent Heat Transfer

Latent Heat Load: \[q_l = \dot{m}_a \cdot h_{fg} \cdot \Delta W = 4840 \cdot Q \cdot \Delta W\]
  • ql = latent heat load (Btu/hr or kW)
  • ΔW = humidity ratio difference (lbw/lbda or kgw/kgda)
  • 4840 = conversion factor (60 × 0.075 × 1076)
  • For SI units: ql = 3010 × Q × ΔW (Q in L/s, result in watts)
Alternative using moisture addition rate: \[q_l = \dot{m}_w \cdot h_{fg}\]
  • w = rate of moisture addition (lb/hr or kg/s)

Total Heat Transfer

Total Heat Load: \[q_t = q_s + q_l = \dot{m}_a \cdot \Delta h = 4.45 \cdot Q \cdot \Delta h\]
  • qt = total heat load (Btu/hr or kW)
  • Δh = enthalpy difference (Btu/lbda or kJ/kgda)
  • 4.45 = conversion factor (60 × 0.075)
  • For SI units: qt = 1.2 × Q × Δh (Q in L/s, result in watts)

Sensible Heat Ratio

Sensible Heat Ratio (SHR): \[SHR = \frac{q_s}{q_t} = \frac{q_s}{q_s + q_l}\]
  • SHR = sensible heat ratio (dimensionless)
  • 0 ≤ SHR ≤ 1
  • SHR = 1 indicates purely sensible load
  • SHR = 0 indicates purely latent load

Building Load Components

Conduction Heat Gain/Loss: \[q = U \cdot A \cdot \Delta T\]
  • q = heat transfer rate (Btu/hr or W)
  • U = overall heat transfer coefficient (Btu/hr·ft²·°F or W/m²·K)
  • A = area (ft² or m²)
  • ΔT = temperature difference (°F or K)
Solar Heat Gain: \[q_{solar} = A \cdot SHGC \cdot SHGF\]
  • SHGC = solar heat gain coefficient (dimensionless)
  • SHGF = solar heat gain factor (Btu/hr·ft² or W/m²)
Alternative using SC: \[q_{solar} = A \cdot SC \cdot SCL\]
  • SC = shading coefficient (dimensionless)
  • SCL = solar cooling load (Btu/hr·ft² or W/m²)
Internal Heat Gains:
  • People: q = N × qperson (sensible and latent components)
  • Lighting: q = W × Fu × Fsa
  • Equipment: q = P × η (power × usage factor)
Infiltration/Ventilation Load: \[q_{inf} = \rho \cdot Q_{inf} \cdot c_p \cdot \Delta T + \rho \cdot Q_{inf} \cdot h_{fg} \cdot \Delta W\]
  • Qinf = infiltration air flow rate (cfm or L/s)

Air Mixing Processes

Mixing of Air Streams

Conservation of Mass (Dry Air): \[\dot{m}_{a,3} = \dot{m}_{a,1} + \dot{m}_{a,2}\]
  • a,3 = mass flow rate of mixed air stream
  • a,1, ṁa,2 = mass flow rates of inlet streams
Conservation of Moisture: \[\dot{m}_{a,3} \cdot W_3 = \dot{m}_{a,1} \cdot W_1 + \dot{m}_{a,2} \cdot W_2\] Conservation of Energy: \[\dot{m}_{a,3} \cdot h_3 = \dot{m}_{a,1} \cdot h_1 + \dot{m}_{a,2} \cdot h_2\] Mixed State Properties: \[W_3 = \frac{\dot{m}_{a,1} \cdot W_1 + \dot{m}_{a,2} \cdot W_2}{\dot{m}_{a,1} + \dot{m}_{a,2}}\] \[h_3 = \frac{\dot{m}_{a,1} \cdot h_1 + \dot{m}_{a,2} \cdot h_2}{\dot{m}_{a,1} + \dot{m}_{a,2}}\] \[T_3 = \frac{\dot{m}_{a,1} \cdot T_1 + \dot{m}_{a,2} \cdot T_2}{\dot{m}_{a,1} + \dot{m}_{a,2}}\] Bypass Factor for Mixing: \[BF = \frac{\dot{m}_{bypass}}{\dot{m}_{total}}\]
  • Used in coil analysis where some air bypasses the coil

Cooling Coil Performance

Coil Load Calculations

Total Cooling Capacity: \[q_c = \dot{m}_a(h_1 - h_2)\]
  • qc = total cooling capacity (Btu/hr or kW)
  • h1 = entering air enthalpy
  • h2 = leaving air enthalpy
Sensible Cooling Capacity: \[q_{c,s} = \dot{m}_a \cdot c_p(T_1 - T_2)\] Latent Cooling Capacity: \[q_{c,l} = \dot{m}_a \cdot h_{fg}(W_1 - W_2)\]

Apparatus Dew Point (ADP)

Coil Bypass Factor: \[BF = \frac{T_2 - T_{ADP}}{T_1 - T_{ADP}}\]
  • TADP = apparatus dew point temperature
  • T1 = entering air temperature
  • T2 = leaving air temperature
  • BF represents inefficiency of the coil
Contact Factor: \[CF = 1 - BF = \frac{T_1 - T_2}{T_1 - T_{ADP}}\]

Mean Temperature Difference

Log Mean Temperature Difference (LMTD): \[\Delta T_{lm} = \frac{(T_{a,in} - T_{w,out}) - (T_{a,out} - T_{w,in})}{\ln\left(\frac{T_{a,in} - T_{w,out}}{T_{a,out} - T_{w,in}}\right)}\]
  • Ta,in = entering air temperature
  • Ta,out = leaving air temperature
  • Tw,in = entering water temperature
  • Tw,out = leaving water temperature
Heat Transfer: \[q = U \cdot A \cdot \Delta T_{lm}\]
  • U = overall heat transfer coefficient
  • A = heat transfer surface area

Heating Processes

Heating Coil Performance

Sensible Heating: \[q_h = \dot{m}_a \cdot c_p(T_2 - T_1) = 1.08 \cdot Q \cdot (T_2 - T_1)\]
  • qh = heating load (Btu/hr or kW)
  • Humidity ratio remains constant for sensible heating (W2 = W1)
Steam or Hot Water Heating Coil: \[q_h = \dot{m}_w \cdot c_{p,w} \cdot \Delta T_w\]
  • w = water flow rate (lb/hr or kg/s)
  • cp,w = specific heat of water = 1.0 Btu/lb·°F (4.18 kJ/kg·K)
  • ΔTw = water temperature drop

Humidification

Steam Injection (Isothermal Humidification): \[\dot{m}_s = \dot{m}_a(W_2 - W_1)\]
  • s = steam injection rate (lb/hr or kg/s)
  • Temperature remains approximately constant
Adiabatic Humidification (Evaporative Cooling): \[h_2 \approx h_1\]
  • Enthalpy remains constant (follows constant wet-bulb line)
  • Temperature decreases as humidity increases
Water Spray Humidifier: \[\dot{m}_w = \dot{m}_a(W_2 - W_1)\]
  • Process follows constant wet-bulb temperature line if adiabatic

Fan and Duct Systems

Fan Power and Efficiency

Fan Power (Air Power): \[P_{air} = \frac{Q \cdot \Delta p}{6356 \cdot \eta_f}\]
  • Pair = fan power (hp)
  • Q = volumetric flow rate (cfm)
  • Δp = pressure rise across fan (in. w.g.)
  • ηf = fan total efficiency (decimal)
  • 6356 = conversion constant for US units
Alternative (SI Units): \[P_{air} = \frac{Q \cdot \Delta p}{1000 \cdot \eta_f}\]
  • Pair = fan power (kW)
  • Q = flow rate (m³/s)
  • Δp = pressure rise (Pa)
Motor Power: \[P_{motor} = \frac{P_{air}}{\eta_m}\]
  • ηm = motor efficiency (decimal)
Fan Total Efficiency: \[\eta_f = \eta_{static} \times \frac{\Delta p_{total}}{\Delta p_{static}}\]
  • ηstatic = static efficiency
  • Δptotal = total pressure rise
  • Δpstatic = static pressure rise

Duct Pressure Losses

Friction Loss (Darcy-Weisbach): \[\Delta p_f = f \cdot \frac{L}{D} \cdot \frac{\rho \cdot v^2}{2}\]
  • Δpf = friction pressure loss (lbf/ft² or Pa)
  • f = friction factor (dimensionless)
  • L = duct length (ft or m)
  • D = duct diameter (ft or m)
  • ρ = air density (lb/ft³ or kg/m³)
  • v = air velocity (ft/s or m/s)
Velocity Pressure: \[p_v = \frac{\rho \cdot v^2}{2} = \left(\frac{v}{4005}\right)^2\]
  • pv = velocity pressure (in. w.g.)
  • v = velocity (fpm)
  • 4005 = conversion constant for standard air
Total Pressure: \[p_t = p_s + p_v\]
  • pt = total pressure
  • ps = static pressure
Dynamic Loss (Fittings): \[\Delta p_d = C \cdot p_v\]
  • C = loss coefficient (dimensionless)
  • Values from ASHRAE tables for specific fittings

Equivalent Duct Diameter

Rectangular to Round (Equal Friction): \[D_e = 1.30 \frac{(ab)^{0.625}}{(a+b)^{0.25}}\]
  • De = equivalent round diameter (in. or mm)
  • a, b = rectangular duct sides (in. or mm)
Hydraulic Diameter: \[D_h = \frac{4A}{P}\]
  • Dh = hydraulic diameter
  • A = cross-sectional area
  • P = perimeter

Refrigeration Cycles

Vapor Compression Cycle

Coefficient of Performance (Cooling): \[COP_c = \frac{q_e}{W_{comp}} = \frac{h_1 - h_4}{h_2 - h_1}\]
  • COPc = coefficient of performance for cooling
  • qe = refrigeration effect (Btu/lb or kJ/kg)
  • Wcomp = compressor work (Btu/lb or kJ/kg)
  • h1 = enthalpy at compressor inlet
  • h2 = enthalpy at compressor outlet
  • h4 = enthalpy at evaporator inlet
Coefficient of Performance (Heating): \[COP_h = \frac{q_c}{W_{comp}} = \frac{h_2 - h_3}{h_2 - h_1}\]
  • qc = condenser heat rejection
  • h3 = enthalpy at condenser outlet
Energy Balance Relationship: \[COP_h = COP_c + 1\] Refrigeration Effect: \[q_e = h_1 - h_4\]
  • Heat absorbed in evaporator per unit mass of refrigerant
Compressor Work: \[W_{comp} = h_2 - h_1\]
  • For isentropic compression: s2 = s1
Isentropic Efficiency: \[\eta_{isen} = \frac{h_{2s} - h_1}{h_2 - h_1}\]
  • h2s = enthalpy at compressor outlet for isentropic process
  • h2 = actual enthalpy at compressor outlet
Condenser Heat Rejection: \[q_c = h_2 - h_3\]

Refrigeration Capacity

Cooling Capacity: \[Q_{ref} = \dot{m}_r(h_1 - h_4)\]
  • Qref = refrigeration capacity (Btu/hr or tons or kW)
  • r = refrigerant mass flow rate (lb/hr or kg/s)
  • 1 ton = 12,000 Btu/hr = 3.517 kW
Compressor Power: \[P_{comp} = \dot{m}_r(h_2 - h_1)\] Energy Efficiency Ratio (EER): \[EER = \frac{Q_{ref}(Btu/hr)}{P_{comp}(W)}\]
  • Units: Btu/hr per watt
  • Higher values indicate better efficiency
Seasonal Energy Efficiency Ratio (SEER): \[SEER = \frac{\text{Total cooling output (Btu)}}{\text{Total electrical input (Wh)}}\]

Carnot Refrigeration Cycle

Carnot COP (Cooling): \[COP_{Carnot,c} = \frac{T_L}{T_H - T_L}\]
  • TL = absolute temperature of low-temperature reservoir (°R or K)
  • TH = absolute temperature of high-temperature reservoir (°R or K)
Carnot COP (Heating): \[COP_{Carnot,h} = \frac{T_H}{T_H - T_L}\]

Evaporative Cooling

Direct Evaporative Cooling

Saturation Effectiveness: \[\varepsilon = \frac{T_1 - T_2}{T_1 - T_{wb,1}}\]
  • ε = saturation effectiveness (decimal)
  • T1 = entering air dry-bulb temperature
  • T2 = leaving air dry-bulb temperature
  • Twb,1 = entering air wet-bulb temperature
  • Process follows constant wet-bulb line on psychrometric chart
Water Evaporation Rate: \[\dot{m}_w = \dot{m}_a(W_2 - W_1)\]

Indirect Evaporative Cooling

Wet-Bulb Effectiveness: \[\varepsilon_{wb} = \frac{T_1 - T_2}{T_1 - T_{wb,outdoor}}\]
  • No moisture is added to the process air stream
  • Temperature reduction without humidity increase

Variable Air Volume (VAV) Systems

VAV Box Control

Supply Air Flow: \[Q = \frac{q_s}{1.08 \cdot (T_s - T_r)}\]
  • Q = required supply air flow (cfm)
  • Ts = supply air temperature
  • Tr = room temperature
Minimum Flow Ratio: \[\text{Min Flow} = \frac{Q_{vent,min}}{Q_{design}}\]
  • Qvent,min = minimum ventilation requirement
  • Qdesign = design maximum flow

Fan Energy in VAV

Fan Affinity Laws: \[\frac{Q_2}{Q_1} = \frac{N_2}{N_1}\] \[\frac{\Delta p_2}{\Delta p_1} = \left(\frac{N_2}{N_1}\right)^2\] \[\frac{P_2}{P_1} = \left(\frac{N_2}{N_1}\right)^3\]
  • Q = volumetric flow rate
  • N = fan speed (rpm)
  • Δp = pressure rise
  • P = power
  • Valid for same fan and fluid density

Ventilation and Indoor Air Quality

Outdoor Air Requirements

Ventilation Rate Procedure: \[V_{ot} = \sum_{z} V_{oz}\]
  • Vot = total outdoor air flow required
  • Voz = outdoor air flow for zone z
Zone Outdoor Air Flow: \[V_{oz} = R_p \cdot P_z + R_a \cdot A_z\]
  • Rp = outdoor air flow rate per person (cfm/person)
  • Pz = zone population
  • Ra = outdoor air flow rate per unit area (cfm/ft²)
  • Az = zone floor area (ft²)

Air Change Rate

Air Changes per Hour: \[ACH = \frac{60 \cdot Q}{V}\]
  • ACH = air changes per hour (hr⁻¹)
  • Q = volumetric flow rate (cfm or m³/min)
  • V = room volume (ft³ or m³)
  • 60 = minutes per hour

Contaminant Dilution

Steady-State Concentration: \[C_{ss} = \frac{G}{Q} + C_o\]
  • Css = steady-state concentration
  • G = contaminant generation rate (mass/time)
  • Q = ventilation flow rate (volume/time)
  • Co = outdoor air contaminant concentration
Transient Concentration (Decay): \[C(t) = C_o + (C_i - C_o)e^{-Qt/V}\]
  • C(t) = concentration at time t
  • Ci = initial indoor concentration
  • t = time

Economizer Operation

Economizer Control Strategies

Dry-Bulb Economizer:
  • Use 100% outdoor air when Toutdoor <>return
  • Simple control but may bring in high humidity
Enthalpy Economizer:
  • Use 100% outdoor air when houtdoor <>return
  • More energy-efficient control considering both temperature and humidity
Mixed Air Temperature: \[T_{mixed} = \frac{Q_{oa} \cdot T_{oa} + Q_{ra} \cdot T_{ra}}{Q_{oa} + Q_{ra}}\]
  • Qoa = outdoor air flow rate
  • Qra = return air flow rate
  • Toa = outdoor air temperature
  • Tra = return air temperature
Outdoor Air Fraction: \[X = \frac{Q_{oa}}{Q_{sa}} = \frac{T_{mixed} - T_{ra}}{T_{oa} - T_{ra}}\]
  • X = outdoor air fraction (decimal)
  • Qsa = supply air flow rate

Heat Recovery Systems

Heat Exchanger Effectiveness

Sensible Effectiveness: \[\varepsilon_s = \frac{T_{oa,leaving} - T_{oa,entering}}{T_{ea,entering} - T_{oa,entering}}\]
  • εs = sensible effectiveness
  • Toa,leaving = outdoor air temperature leaving heat exchanger
  • Toa,entering = outdoor air temperature entering heat exchanger
  • Tea,entering = exhaust air temperature entering heat exchanger
Latent Effectiveness: \[\varepsilon_l = \frac{W_{oa,leaving} - W_{oa,entering}}{W_{ea,entering} - W_{oa,entering}}\]
  • εl = latent effectiveness
Total (Enthalpy) Effectiveness: \[\varepsilon_t = \frac{h_{oa,leaving} - h_{oa,entering}}{h_{ea,entering} - h_{oa,entering}}\] Recovered Heat: \[q_{recovered} = \varepsilon \cdot \dot{m}_a \cdot c_p \cdot (T_{ea} - T_{oa})\]

Cooling Towers

Cooling Tower Performance

Range: \[\text{Range} = T_{w,in} - T_{w,out}\]
  • Tw,in = hot water inlet temperature
  • Tw,out = cold water outlet temperature
  • Measure of tower load
Approach: \[\text{Approach} = T_{w,out} - T_{wb,air}\]
  • Twb,air = entering air wet-bulb temperature
  • Measure of tower effectiveness
Cooling Tower Effectiveness: \[\varepsilon_{ct} = \frac{T_{w,in} - T_{w,out}}{T_{w,in} - T_{wb,air}} = \frac{\text{Range}}{\text{Range} + \text{Approach}}\] Heat Rejection: \[q_{ct} = \dot{m}_w \cdot c_{p,w} \cdot (T_{w,in} - T_{w,out})\]
  • qct = heat rejection rate (Btu/hr or kW)
  • w = water flow rate (lb/hr or kg/s)
Evaporation Rate: \[\dot{m}_{evap} \approx 0.001 \times \dot{m}_w \times \text{Range}\]
  • Approximate formula for evaporation loss
  • evap = evaporation rate (lb/hr or kg/s)
  • Range in °F (multiply by 0.0008 for °C)
Makeup Water: \[\dot{m}_{makeup} = \dot{m}_{evap} + \dot{m}_{drift} + \dot{m}_{blowdown}\]
  • drift = drift loss (typically 0.1-0.2% of circulation rate)
  • blowdown = blowdown for water quality control

Liquid-to-Air Ratio

L/G Ratio: \[\frac{L}{G} = \frac{\dot{m}_w}{\dot{m}_a}\]
  • L = liquid (water) flow rate
  • G = gas (air) flow rate
  • Affects tower size and performance

Chillers and Heat Pumps

Chiller Performance

Chiller Capacity: \[Q_{chiller} = \dot{m}_{chw} \cdot c_{p,w} \cdot \Delta T_{chw}\]
  • Qchiller = chiller cooling capacity (Btu/hr or tons or kW)
  • chw = chilled water flow rate (lb/hr or kg/s)
  • ΔTchw = chilled water temperature difference (typically 10-12°F or 5-7°C)
Alternative Form: \[Q_{chiller} = 500 \times GPM \times \Delta T_{chw}\]
  • GPM = gallons per minute (water flow)
  • ΔTchw = temperature difference (°F)
  • Result in Btu/hr (divide by 12,000 for tons)
Kilowatts per Ton (kW/ton): \[\text{kW/ton} = \frac{P_{comp}(kW)}{Q_{chiller}(tons)}\]
  • Lower values indicate better efficiency
  • Typical range: 0.5-0.8 kW/ton for centrifugal chillers
Condenser Heat Rejection: \[Q_{cond} = Q_{evap} + P_{comp}\]
  • Qcond = condenser heat rejection
  • Qevap = evaporator cooling load

Part Load Performance

Part Load Ratio (PLR): \[PLR = \frac{Q_{actual}}{Q_{design}}\]
  • Used in performance curves
Integrated Part Load Value (IPLV): \[IPLV = 0.01A + 0.42B + 0.45C + 0.12D\]
  • A, B, C, D = EER or COP at 100%, 75%, 50%, 25% load
  • Weighted average efficiency metric

Pumping Systems

Pump Power and Head

Pump Head: \[H = \frac{\Delta p}{\rho \cdot g}\]
  • H = pump head (ft or m)
  • Δp = pressure rise (lbf/ft² or Pa)
  • ρ = fluid density (lb/ft³ or kg/m³)
  • g = gravitational acceleration (32.2 ft/s² or 9.81 m/s²)
Pump Power (Water Horsepower): \[WHP = \frac{Q \cdot H \cdot \rho}{33000}\]
  • WHP = water horsepower (hp)
  • Q = flow rate (ft³/min)
  • H = total head (ft)
  • 33,000 = conversion constant (ft·lbf/min per hp)
Alternative Form (GPM): \[WHP = \frac{GPM \times H \times SG}{3960}\]
  • GPM = gallons per minute
  • SG = specific gravity
Brake Horsepower: \[BHP = \frac{WHP}{\eta_p}\]
  • BHP = brake horsepower
  • ηp = pump efficiency (decimal)
Motor Power: \[P_{motor} = \frac{BHP}{\eta_m}\]

System Head Curve

Total Head: \[H_{total} = H_{static} + H_{friction}\] \[H_{total} = H_{static} + K \cdot Q^2\]
  • Hstatic = static head (elevation difference)
  • Hfriction = friction head loss
  • K = system resistance coefficient

Pump Affinity Laws

For Same Impeller Diameter: \[\frac{Q_2}{Q_1} = \frac{N_2}{N_1}\] \[\frac{H_2}{H_1} = \left(\frac{N_2}{N_1}\right)^2\] \[\frac{P_2}{P_1} = \left(\frac{N_2}{N_1}\right)^3\] For Same Speed: \[\frac{Q_2}{Q_1} = \frac{D_2}{D_1}\] \[\frac{H_2}{H_1} = \left(\frac{D_2}{D_1}\right)^2\] \[\frac{P_2}{P_1} = \left(\frac{D_2}{D_1}\right)^3\]
  • D = impeller diameter

Pipe and Piping System Losses

Friction Losses in Pipes

Darcy-Weisbach Equation: \[h_f = f \cdot \frac{L}{D} \cdot \frac{v^2}{2g}\]
  • hf = head loss due to friction (ft or m)
  • f = friction factor (dimensionless)
  • L = pipe length (ft or m)
  • D = pipe diameter (ft or m)
  • v = flow velocity (ft/s or m/s)
  • g = gravitational acceleration
Hazen-Williams Equation: \[h_f = \frac{4.52 \times L \times Q^{1.85}}{C^{1.85} \times D^{4.87}}\]
  • C = Hazen-Williams coefficient (120-140 for typical water pipes)
  • Q = flow rate (gpm)
  • D = pipe diameter (in.)
  • hf = head loss (ft)
  • Valid for water flow only
Velocity in Pipe: \[v = \frac{Q}{A} = \frac{4Q}{\pi D^2}\] For GPM and inches: \[v = \frac{0.4085 \times GPM}{D^2}\]
  • v = velocity (ft/s)
  • D = diameter (inches)

Minor Losses

Loss Coefficient Method: \[h_m = K \cdot \frac{v^2}{2g}\]
  • hm = minor head loss (ft or m)
  • K = loss coefficient (dimensionless, from tables)
Equivalent Length Method: \[L_e = K \cdot \frac{D}{f}\]
  • Le = equivalent length of straight pipe
  • Add to actual pipe length for total friction calculation

Thermal Energy Storage

Storage Capacity

Sensible Heat Storage: \[Q_{storage} = m \cdot c_p \cdot \Delta T\]
  • Qstorage = storage capacity (Btu or kJ)
  • m = mass of storage medium (lb or kg)
  • ΔT = temperature change (°F or K)
Latent Heat Storage (Ice): \[Q_{storage} = m_{ice} \cdot h_{fusion}\]
  • mice = mass of ice (lb or kg)
  • hfusion = latent heat of fusion = 144 Btu/lb (334 kJ/kg)
Ton-Hours: \[Q_{storage}(\text{ton-hr}) = \frac{Q_{storage}(\text{Btu})}{12000}\]
  • 1 ton-hr = 12,000 Btu

Discharge Rate

Available Cooling: \[\dot{Q}_{discharge} = \frac{Q_{storage}}{\Delta t}\]
  • Δt = discharge time period

Energy Recovery and Efficiency

Annual Energy Usage

Annual Energy Consumption: \[E_{annual} = P_{avg} \times h_{annual}\]
  • Eannual = annual energy consumption (kWh or Btu)
  • Pavg = average power consumption
  • hannual = annual operating hours
Equivalent Full Load Hours: \[EFLH = \frac{E_{annual}}{P_{design}}\]
  • EFLH = equivalent full load hours
  • Pdesign = design (peak) power

Heat Pipe Effectiveness

Effectiveness: \[\varepsilon = \frac{T_{supply,leaving} - T_{supply,entering}}{T_{exhaust,entering} - T_{supply,entering}}\]
  • For air-to-air heat pipe heat exchanger

Boilers and Steam Systems

Boiler Efficiency

Combustion Efficiency: \[\eta_{comb} = \frac{Q_{output}}{Q_{fuel}} = \frac{\dot{m}_{steam}(h_{steam} - h_{feedwater})}{\dot{m}_{fuel} \times HHV}\]
  • ηcomb = combustion efficiency
  • Qoutput = useful heat output
  • Qfuel = heat input from fuel
  • HHV = higher heating value of fuel
Stack Loss: \[Q_{stack} = \dot{m}_{flue} \times c_{p,flue} \times (T_{stack} - T_{ambient})\]
  • Major component of boiler heat loss

Steam Properties and Flow

Steam Flow Rate for Heating: \[\dot{m}_{steam} = \frac{Q}{h_{fg}}\]
  • For steam heating applications where condensate forms
Condensate Return: \[\dot{m}_{condensate} = \dot{m}_{steam}\]
  • Mass balance for closed steam systems

Control Systems and Sequences

Proportional Control

Proportional Band: \[PB = \frac{100}{\text{Gain}}\]
  • PB = proportional band (%)
  • Range of input change for full output change
Control Output: \[CO = K_p \times (SP - PV) + CO_{bias}\]
  • CO = control output
  • Kp = proportional gain
  • SP = setpoint
  • PV = process variable
  • CObias = bias or offset

Reset Control

Supply Air Temperature Reset: \[T_{sa,reset} = T_{sa,design} + K \times (T_{oa} - T_{oa,design})\]
  • Tsa,reset = reset supply air temperature
  • K = reset ratio (slope)
  • Toa = outdoor air temperature

Piping System Design

Expansion and Contraction

Thermal Expansion: \[\Delta L = \alpha \times L \times \Delta T\]
  • ΔL = change in length (ft or m)
  • α = coefficient of linear thermal expansion (in/in·°F or m/m·K)
  • L = original length (ft or m)
  • ΔT = temperature change (°F or K)
  • For steel: α ≈ 6.5 × 10⁻⁶ in/in·°F

System Fill and Expansion Tank

Expansion Tank Volume (Closed System): \[V_t = \frac{V_s \times \Delta v}{1 - \frac{P_1}{P_2}}\]
  • Vt = expansion tank volume
  • Vs = system water volume
  • Δv = change in specific volume of water
  • P1 = fill pressure
  • P2 = maximum operating pressure
Net Positive Suction Head (NPSH): \[NPSH_a = h_s + h_p - h_{vp} - h_f\]
  • NPSHa = available net positive suction head
  • hs = static head on suction
  • hp = pressure head on liquid surface
  • hvp = vapor pressure head
  • hf = friction head loss in suction piping
  • Must have NPSHa > NPSHr (required) to avoid cavitation
The document Formula Sheet: HVAC Systems is a part of the PE Exam Course Mechanical Engineering for PE.
All you need of PE Exam at this link: PE Exam
Explore Courses for PE Exam exam
Get EduRev Notes directly in your Google search
Related Searches
Important questions, ppt, Previous Year Questions with Solutions, pdf , video lectures, Formula Sheet: HVAC Systems, Sample Paper, study material, Objective type Questions, Formula Sheet: HVAC Systems, practice quizzes, Free, mock tests for examination, Summary, Extra Questions, MCQs, past year papers, shortcuts and tricks, Semester Notes, Formula Sheet: HVAC Systems, Viva Questions, Exam;