PE Exam Exam  >  PE Exam Notes  >  Electrical & Computer Engineering for PE  >  Cheatsheet: Distribution

Cheatsheet: Distribution

1. Distribution System Basics

1.1 Voltage Levels

System Type Voltage Range
Primary Distribution 4.16 kV to 34.5 kV (common: 12.47 kV, 13.8 kV, 22.9 kV, 34.5 kV)
Secondary Distribution 120/240 V (single-phase), 208Y/120 V, 480Y/277 V (three-phase)
Utilization 120 V, 240 V, 480 V, 600 V

1.2 System Configurations

Configuration Characteristics
Radial Single path from source to load; lowest cost; least reliable
Loop (Open Ring) Normally open loop; manual or automatic switching; improved reliability
Network Multiple sources; highest reliability; highest cost; used in high-density urban areas
Primary Selective Two sources with manual/automatic transfer; improved continuity

2. Distribution Transformers

2.1 Transformer Connections

Connection Application
Delta-Wye (Δ-Y) Most common; primary delta, secondary wye; provides neutral for single-phase loads
Wye-Delta (Y-Δ) Secondary delta for three-phase loads without neutral
Delta-Delta (Δ-Δ) Open delta capability; can operate with one transformer failed at 58% capacity
Wye-Wye (Y-Y) Requires grounded neutral or tertiary winding to prevent overvoltage

2.2 Transformer Ratings and Sizing

  • kVA rating = √3 × VL-L × IL (three-phase)
  • kVA rating = V × I (single-phase)
  • Standard distribution transformer ratings: 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333, 500 kVA
  • Impedance: 1.5% to 5.75% for distribution transformers
  • Load factor affects sizing; diversity factor = 1.0 to 2.5 for residential

2.3 Transformer Losses and Efficiency

Parameter Formula/Value
Core Loss (No-load) Constant; independent of load; 0.1% to 0.3% of rating
Copper Loss (Load) I²R losses; varies with load squared; 1% to 2% at full load
Efficiency η = Pout / (Pout + Pcore + Pcopper)
All-day Efficiency ηall-day = (kWh output in 24h) / (kWh input in 24h)

3. Voltage Regulation

3.1 Voltage Drop Calculations

Formula Application
VD = I(R cosθ + X sinθ) Per-phase voltage drop (line-to-neutral)
%VD = (VD / Vnom) × 100 Percent voltage drop
VD = √3 × I × Z Line-to-line voltage drop (approximate)
VD = (2 × I × L × R) / 1000 Single-phase, two-wire (VD in volts, L in feet, R in Ω/1000 ft)

3.2 Voltage Regulation Limits

  • ANSI C84.1 Range A: ±5% of nominal (preferred)
  • ANSI C84.1 Range B: +5.8%/-8.3% (tolerable)
  • Maximum feeder drop: 3% recommended
  • Maximum branch circuit drop: 3% recommended
  • Total drop (feeder + branch): 5% maximum

3.3 Voltage Regulation Equipment

Device Description
LTC (Load Tap Changer) Substation transformer tap changer; ±10% in 32 steps (0.625% per step); automatic operation
Step Voltage Regulator ±10% in 32 steps; single-phase or three-phase; line-drop compensation
Switched Capacitor Banks Reactive power compensation; improves voltage and power factor

3.4 Line-Drop Compensation

  • R and X settings compensate for feeder impedance
  • Maintains voltage at a point beyond regulator location
  • R setting (volts) = Iload × Rline × CT ratio / PT ratio
  • X setting (volts) = Iload × Xline × CT ratio / PT ratio

4. Power Factor and Reactive Power

4.1 Power Factor Fundamentals

Parameter Formula
Power Factor PF = P / S = cos θ = kW / kVA
Apparent Power S = √(P² + Q²) or S = V × I (kVA)
Reactive Power Q = S × sin θ = P × tan θ (kVAR)
Real Power P = S × cos θ = V × I × cos θ (kW)

4.2 Capacitor Sizing

Formula Description
Qcap = P(tan θ1 - tan θ2) Required kVAR to improve PF from θ1 to θ2
Qcap = V² / XC Capacitor reactive power
XC = 1 / (2πfC) Capacitive reactance
Icap = Qcap / (√3 × VL-L) Three-phase capacitor current

4.3 Capacitor Bank Ratings

  • Standard three-phase ratings: 300, 450, 600, 900, 1200, 1800 kVAR
  • Voltage ratings: 2.4, 4.16, 4.8, 7.2, 12.47, 13.8, 14.4, 24.94, 34.5 kV
  • Grounded wye most common for distribution
  • Switched capacitors: 2-4 steps for voltage and VAR control

4.4 Benefits of Power Factor Correction

  • Reduced line losses: Loss reduction = 1 - (PFold/PFnew
  • Increased system capacity: released kVA = kW × (1/PFold - 1/PFnew)
  • Improved voltage regulation: reduces voltage drop
  • Reduced demand charges (utility billing)

5. Conductor Selection and Sizing

5.1 Conductor Ampacity

  • Based on: conductor material, insulation type, ambient temperature, number of conductors
  • Ampacity adjustment: multiply table values by correction factors
  • Temperature correction factor: 0.82 at 40°C, 0.91 at 30°C (75°C insulation)
  • Conductor bundling derating: 0.80 for 4-6 conductors, 0.70 for 7-9 conductors

5.2 Conductor Properties

Property Aluminum
Resistivity (DC at 20°C) 2.83 × 10⁻⁸ Ω·m (Cu: 1.72 × 10⁻⁸ Ω·m)
Weight 30% of copper weight for same ampacity
Cost Lower than copper per unit length
Common Types ACSR, AAC, AAAC (aluminum); Cu, THHN/THWN (copper)

5.3 Economic Conductor Size

  • Kelvin's Law: economical size when annual cost of losses equals annual fixed charges on conductor investment
  • Total cost = installed cost + present worth of losses over lifetime
  • Loss cost = 3 × I² × R × hours × $/kWh × demand factor²

5.4 Voltage Drop Limits for Conductor Sizing

  • Primary feeders: 3% maximum at peak load
  • Secondary feeders: 2% maximum
  • Service drops: 1% maximum
  • Combined primary and secondary: 5% total maximum

6. Protective Devices

6.1 Overcurrent Protection Devices

Device Characteristics
Fuses Single operation; K, T, N types; coordination by time-current curves; economical
Reclosers Automatic interruption and reclosing; 1-4 operations; oil or vacuum; 560-1120 A
Sectionalizers Counts fault current; opens after backup device operates; 3 counts standard
Circuit Breakers Manual/automatic operation; adjustable settings; reusable; higher cost

6.2 Fuse Ratings and Types

Fuse Type Speed/Application
K (Fast) 6-8 times rating melting time; lateral and transformer protection
T (Slow) 10-13 times rating melting time; feeder protection; cold-load pickup
N (Slow) Similar to T; improved coordination
  • Standard current ratings: 6, 10, 15, 25, 40, 65, 100, 140, 200 A
  • Voltage ratings: 2.4, 4.8, 7.2, 14.4, 23.0, 34.5, 46, 69 kV

6.3 Coordination Principles

  • Time-current curve separation: minimum 0.2-0.3 seconds at all current levels
  • Fuse-to-fuse: downstream fuse total clear time < upstream="" fuse="" minimum="" melt="">
  • Recloser-to-fuse: fuse saves on temporary faults; recloser fast curve < fuse="" melt;="" recloser="" slow="" curve=""> fuse clear
  • Instantaneous trip must not operate for downstream fault maximum

6.4 Recloser Operations

  • Sequence: 2 fast operations, 2 slow operations (common)
  • Fast operation: 0.1-0.3 seconds
  • Slow operation: 1-10 seconds
  • Reclosing intervals: 1-2 seconds (first), 10-30 seconds (subsequent)
  • 85% of faults are temporary; cleared by fast reclosing

7. Short Circuit Analysis

7.1 Fault Current Calculations

Formula Application
Isc = V / Ztotal Basic fault current (per-phase)
Isc-3φ = VL-L / (√3 × Z1) Three-phase fault current
Isc-SLG = 3VL-N / (Z1 + Z2 + Z0) Single line-to-ground fault
Isc-LL = √3 × VL-N / (Z1 + Z2) Line-to-line fault

7.2 Impedance Values

Component Typical Impedance
Utility Source Z = V² / MVAsc; X/R = 10-20
Transformer Z = %Z × V² / (100 × kVA); X/R = 3-7
Cable (per 1000 ft) R: 0.05-2 Ω; X: 0.02-0.08 Ω
Overhead Line R: 0.1-1.5 Ω/mile; X: 0.6-1.2 Ω/mile

7.3 Per-Unit Method

Parameter Formula
Base kVA Choose system base (e.g., 10 MVA or 100 MVA)
Base Voltage System line-to-line voltage
Base Current Ibase = kVAbase / (√3 × kVbase)
Base Impedance Zbase = kVbase² / MVAbase
Per-Unit Impedance Zpu = Zactual / Zbase
Change Base Zpu-new = Zpu-old × (kVAnew/kVAold) × (kVold/kVnew

7.4 Symmetrical Components

  • Positive sequence (Z1): normal balanced system impedance
  • Negative sequence (Z2): typically Z2 ≈ Z1 for static equipment
  • Zero sequence (Z0): ground return path; Z0 = 2-5 × Z1 for overhead lines
  • Used for unbalanced fault analysis

8. Grounding Systems

8.1 System Grounding Types

Grounding Type Characteristics
Solidly Grounded Neutral directly grounded; Z0/Z1 < 3;="" high="" fault="" current;="" most="" common="" in="">
Resistance Grounded Limits ground fault current; reduces transient overvoltages; 200-400 A limit common
Reactance Grounded Limits fault current but higher than resistance; reduces arcing ground damage
Ungrounded No intentional ground; high transient overvoltages; not used in modern distribution

8.2 Equipment Grounding

  • Grounding electrode conductor sizing: based on largest service conductor (NEC Table 250.66)
  • Grounding electrode resistance: 25 Ω maximum (NEC), 5 Ω preferred
  • Ground rod: 5/8 inch diameter, 8 ft minimum length (copper-clad steel)
  • Two rods required if single rod exceeds 25 Ω; spacing ≥ 6 ft

8.3 Ground Fault Protection

  • Ground fault relaying: residual connection (3I0) or zero-sequence CT
  • Pickup setting: 20-40% of maximum three-phase fault current at end of zone
  • Time delay: 0.1-0.5 seconds coordination margin
  • Sensitive ground fault: 5-50 A pickup for high-resistance faults

8.4 Touch and Step Potential

Parameter Formula/Value
Touch Potential Limit Vtouch = (1000 + 1.5ρs) / √ts
Step Potential Limit Vstep = (1000 + 6ρs) / √ts
  • ρs = surface layer resistivity (Ω·m); ts = shock duration (sec)
  • Crushed rock (3000 Ω·m) reduces shock hazard

9. Load Characteristics

9.1 Load Types and Power Factors

Load Type Power Factor
Incandescent Lighting 1.0 (unity)
Fluorescent Lighting 0.85-0.95 lagging (with ballast)
Induction Motors 0.75-0.85 lagging (full load); 0.2-0.5 (no load)
Resistance Heating 1.0 (unity)
Power Supplies/Electronics 0.6-0.9 (varies with harmonic content)

9.2 Demand and Diversity

Term Definition
Demand Average load over specified time interval (15-30 min)
Maximum Demand Highest demand during specified period
Demand Factor DF = Maximum Demand / Connected Load
Diversity Factor Div = Sum of Individual Max Demands / Coincident Max Demand
Load Factor LF = Average Load / Peak Load (over period)
Utilization Factor UF = Maximum Demand / Rated Capacity

9.3 Typical Demand Factors

  • Residential: 0.4-0.6 (first 10 kW at 100%, remainder at 40%)
  • Commercial: 0.75-0.85
  • Industrial: 0.8-0.9
  • Diversity factor residential feeders: 1.5-2.5

9.4 Load Growth and Forecasting

  • Annual growth rates: residential 2-4%, commercial 3-5%, industrial varies
  • Planning horizon: 5-10 years for distribution
  • Load density: urban 1500-5000 kVA/sq mi, suburban 500-1500 kVA/sq mi

10. Reliability and Power Quality

10.1 Reliability Indices

Index Formula
SAIFI System Average Interruption Frequency Index = Total Customer Interruptions / Total Customers
SAIDI System Average Interruption Duration Index = Sum Customer Interruption Durations / Total Customers (min)
CAIDI Customer Average Interruption Duration Index = SAIDI / SAIFI (min)
ASAI Average Service Availability Index = (Total Hours - Outage Hours) / Total Hours

10.2 Power Quality Disturbances

Disturbance Characteristics
Sag (Dip) 0.1-0.9 pu voltage; 0.5 cycle to 1 min duration; motor starting, faults
Swell 1.1-1.8 pu voltage; short duration; load rejection, single-phase fault
Interruption < 0.1="" pu="" voltage;="" momentary="">< 3="" sec),="" temporary="" (3="" sec="" -="" 1="" min),="" sustained="" (=""> 1 min)
Transient High magnitude, short duration; lightning, switching; 0.3-50 μs
Flicker Voltage variation 0.95-1.05 pu; < 25="" hz="" modulation;="" arc="">

10.3 Harmonics

Parameter Formula/Limit
THD (Voltage) THDV = √(V2² + V3² + ... + Vn²) / V1 × 100%
THD (Current) THDI = √(I2² + I3² + ... + In²) / I1 × 100%
IEEE 519 Voltage Limit THD < 5%="" at="" pcc="" (individual="" harmonic=""><>
IEEE 519 Current Limit Depends on Isc/IL ratio; THD 5-20%
  • Triplen harmonics (3rd, 9th, 15th): add in neutral; can exceed phase current
  • 5th and 7th harmonics: dominant in six-pulse converters
  • Harmonic filters: series or parallel tuned to specific harmonics

10.4 Voltage Unbalance

Parameter Formula
Voltage Unbalance VU% = (Max deviation from avg) / Vavg × 100
NEMA Limit 1% maximum for motors (derate 2% per 1% VU beyond)
  • Causes: unbalanced loads, single-phase laterals, open phases
  • Effects: motor overheating, negative-sequence currents, reduced life

11. Distribution Automation

11.1 Automated Switching Devices

Device Function
Automated Recloser SCADA-controlled; remote operation; fault location; 1-3 cycles
Automated Switch Remote-controlled sectionalizing; no fault interruption; service restoration
Fault Interrupter Automated protection device; 600-800 A rating

11.2 SCADA Functions

  • Supervisory Control and Data Acquisition
  • Real-time monitoring: voltage, current, power, status
  • Remote control: switch operations, tap changing, capacitor switching
  • Alarm management and event logging
  • Data acquisition interval: 2-10 seconds

11.3 Fault Location Identification

  • Impedance-based: Z = V/I; distance = Z × line length / Ztotal
  • Traveling wave: location from time-of-arrival difference; accuracy ±200 m
  • Fault indicators: visual/remote indication of fault passage
  • Smart meters: voltage sag detection and reporting

11.4 Advanced Distribution Management

  • Volt-VAR Optimization (VVO): minimize losses while maintaining voltage limits
  • Fault Location, Isolation, Service Restoration (FLISR): automatic switching to restore service
  • Conservation Voltage Reduction (CVR): reduce voltage to reduce consumption; CVR factor 0.5-1.0
  • Distribution Management System (DMS): advanced analytics and control

12. Underground Distribution

12.1 Cable Types

Type Application
XLPE (Cross-linked Polyethylene) Most common; 90°C rating; primary and secondary
EPR (Ethylene Propylene Rubber) High flexibility; 90-105°C rating; wet/dry locations
PILC (Paper Insulated Lead Covered) Older installations; being replaced; 85°C rating
Concentric Neutral Primary cable; neutral wires helically wrapped
Tape Shield Primary cable; copper tape neutral; single-point grounded

12.2 Cable Ampacity Derating

  • Soil thermal resistivity: 90 °C·cm/W standard; derate for higher values
  • Burial depth derating: 0.97 at 36 inches, 0.94 at 48 inches
  • Multiple cables: 0.80 for 2 cables, 0.70 for 3 cables, 0.65 for 4 cables (in same trench)
  • Load factor: cable can be oversized based on cyclic loading

12.3 Cable Impedance

  • RAC > RDC due to skin effect and proximity effect
  • Skin effect factor: 1.0 at 60 Hz for small conductors, up to 1.05 for large
  • Geometric mean radius (GMR) used for reactance calculations
  • Sheath/shield bonding affects impedance and losses

12.4 Underground System Configurations

Configuration Description
Radial Single feed; pad-mounted transformers; lowest cost
Loop Open loop with sectionalizing switches; improved reliability
Primary Network Grid of primary feeders; highest reliability; highest cost
Secondary Network Low-voltage grid; multiple sources; urban high-density areas; 216Y/125 V or 480Y/277 V
The document Cheatsheet: Distribution is a part of the PE Exam Course Electrical & Computer Engineering for PE.
All you need of PE Exam at this link: PE Exam
Explore Courses for PE Exam exam
Get EduRev Notes directly in your Google search
Related Searches
mock tests for examination, Cheatsheet: Distribution, Viva Questions, Semester Notes, past year papers, Cheatsheet: Distribution, Summary, video lectures, Sample Paper, ppt, Cheatsheet: Distribution, study material, Exam, Free, Previous Year Questions with Solutions, Important questions, Extra Questions, MCQs, shortcuts and tricks, practice quizzes, pdf , Objective type Questions;