PE Exam Exam  >  PE Exam Notes  >  Electrical & Computer Engineering for PE  >  Cheatsheet: Protection Systems

Cheatsheet: Protection Systems

1. Protection System Fundamentals

1.1 Basic Definitions

1.1 Basic Definitions

1.2 Protection System Requirements

  • Reliability: Must operate when required and avoid false trips
  • Selectivity: Isolate only faulted section, minimize outage area
  • Speed: Fast operation to minimize equipment damage and maintain stability
  • Sensitivity: Detect minimum fault current within zone of protection
  • Dependability: Operate for all faults within protected zone
  • Security: Avoid operation for faults outside protected zone

1.3 CT and PT Specifications

1.3 CT and PT Specifications

2. Overcurrent Protection

2.1 Overcurrent Relay Types

2.1 Overcurrent Relay Types

2.2 Inverse Time Characteristics

2.2 Inverse Time Characteristics

Where: t = operating time (s), TD = time dial setting, I = fault current, Ip = pickup current

2.3 Coordination Principles

  • Coordination Time Interval (CTI): 0.2-0.4s for electromechanical, 0.1-0.3s for electronic relays
  • Instantaneous vs Time Overcurrent: Set instantaneous at 150-200% of maximum through fault
  • Pickup Setting: 125-150% of maximum load current for phase relays
  • Ground Relay Pickup: 10-40% of phase CT rating for solidly grounded systems
  • Fuse-Relay Coordination: Minimum 0.2s separation; use fuse minimum melt vs relay curve

3. Distance Protection

3.1 Distance Relay Fundamentals

3.1 Distance Relay Fundamentals

3.2 Distance Relay Types

3.2 Distance Relay Types

3.3 Distance Relay Settings

  • Zone 1 Reach: 0.8-0.9 × ZL (line impedance)
  • Zone 2 Reach: 1.2 × ZL + 0.5 × ZL2 (shortest adjacent line)
  • Zone 3 Reach: 1.2 × (ZL + ZL2)
  • Load Impedance Check: Zload_min = Vmin² / (√3 × Pmax); relay reach must be < 0.5="" ×="">
  • Power Swing Blocking: Required when Zswing enters relay characteristic; uses rate of impedance change

3.4 Impedance Calculations

3.4 Impedance Calculations

4. Differential Protection

4.1 Differential Protection Principles

4.1 Differential Protection Principles

4.2 Transformer Differential (87T)

4.2 Transformer Differential (87T)

4.3 Generator Differential (87G)

  • CT Location: Neutral CT and terminal CT; must have identical ratios
  • Minimum Pickup: 0.2-0.5 pu on generator base; lower for large units
  • Slope: 10-25% for low resistance grounded; 25-40% for high resistance grounded
  • Stator Ground Fault: Separate 100% stator ground (87GN) using voltage or 3rd harmonic method
  • Coordination: Must be faster than backup impedance relay (21); instantaneous operation

4.4 Bus Differential (87B)

4.4 Bus Differential (87B)

4.5 Line Differential (87L)

  • Pilot Wire: Uses communication channel; fiber optic or digital communication preferred
  • Phase Comparison: Compares phase angle of currents at terminals; trip if out of phase
  • Current Differential: Digital comparison of current magnitudes and angles; GPS time sync
  • Slope Settings: 15-50% depending on line length and CT errors; dual or triple slope
  • Communication Delay: Must account for channel delay (typically <10ms for="">

5. Ground Fault Protection

5.1 Grounding System Types

5.1 Grounding System Types

5.2 Residual and Neutral Protection

5.2 Residual and Neutral Protection

5.3 Ground Fault Settings

  • Solidly Grounded Pickup: 0.1-0.4 × phase CT rating; coordinate with maximum unbalance
  • Low Resistance Grounded: 50-70% of resistor current rating; definite time 0.5-1.0s
  • High Resistance Grounded: 10-30% of resistor current; pulsing type alerts operator
  • SEL Pickup: ≥ 1.5 × maximum unbalance current, ≥ 2 × CT error
  • Time Delay: 0.1-0.5s for selectivity; instantaneous if coordination permits

5.4 Restricted Earth Fault (REF/64)

5.4 Restricted Earth Fault (REF/64)

6. Pilot Protection Schemes

6.1 Pilot Scheme Types

6.1 Pilot Scheme Types

6.2 Communication Channels

6.2 Communication Channels

6.3 Pilot Scheme Settings

  • Zone 2 Reach for POTT: 120-150% protected line + 50% adjacent line (minimum)
  • Zone 1 Reach: 85-90% of protected line; instantaneous with no communication delay
  • Communication Delay: 8-15ms for PLC, 4-8ms for microwave, <5ms for="">
  • Carrier Check: Monitors channel; blocks trip if channel fails (security)
  • Echo Logic: Confirms received signal matches sent signal; added security

7. Generator Protection

7.1 Generator Protection Functions

7.1 Generator Protection Functions

7.2 Loss of Field Protection (40)

7.2 Loss of Field Protection (40)

7.3 Negative Sequence Protection (46)

I2²t Calculation: Thermal limit based on rotor heating

  • K Constant: I2²t = K where K = 5-40 for large turbine generators, K = 10-60 for hydro
  • Continuous I2 Limit: 5-10% of rated current for turbine generators, 15-25% for hydro
  • Alarm Setting: 50-60% of trip setting; warn before trip
  • Calculation: I2 = (Ia² + Ib² + Ic² - (Ia+Ib+Ic)²/3)^0.5 / 3
  • Time Curve: Inverse time characteristic; t = K/I2² seconds

7.4 Stator Ground Fault Protection

7.4 Stator Ground Fault Protection

8. Transformer Protection

8.1 Transformer Protection Scheme

8.1 Transformer Protection Scheme

8.2 Transformer Differential Settings (87T)

8.2 Transformer Differential Settings (87T)

8.3 Inrush Current Characteristics

  • Peak Magnitude: 8-15× rated current for large power transformers
  • Duration: Decays from seconds to minutes; primarily 2nd harmonic initially
  • Harmonic Content: 2nd harmonic 30-70% of fundamental during inrush
  • Sympathetic Inrush: Occurs in parallel transformers when one is energized
  • Recovery Inrush: After fault clearing; may be 3-5× rated current

8.4 Thermal Protection (49)

8.4 Thermal Protection (49)

9. Motor Protection

9.1 Motor Protection Functions

9.1 Motor Protection Functions

9.2 Thermal Overload Settings (49)

9.2 Thermal Overload Settings (49)

9.3 Starting and Locked Rotor Protection

  • Starting Current: 5-7× FLA for across-the-line starting; 2-4× for reduced voltage
  • Starting Time: 5-15 seconds typical; depends on load inertia
  • Locked Rotor Current: 5.5-6.5× FLA at rated voltage (Code G-V)
  • 51LR Pickup: 1.5-2.5× FLA; operates if motor fails to accelerate
  • 51LR Time Delay: 10-30s; must exceed maximum starting time by 20-30%
  • Safe Restarts: 2 starts cold, 1 start hot within 1 hour (general rule)

9.4 Motor Short Circuit Protection

9.4 Motor Short Circuit Protection

10. Bus Protection

10.1 Bus Protection Schemes

10.1 Bus Protection Schemes

10.2 High Impedance Differential

10.2 High Impedance Differential

10.3 Low Impedance Differential

  • Operating Current: Iop = |ΣI| (vector sum of all CT currents)
  • Restraint Current: Ires = max(|I1|, |I2|, ..., |In|) or (|I1| + |I2| + ... + |In|) / n
  • Minimum Pickup: 0.2-0.5A secondary; primary consideration is CT error
  • Slope 1: 10-30% for normal through current range
  • Slope 2: 50-80% for high through-fault CT saturation region
  • Unrestrained Instantaneous: 8-10× maximum load; operates without restraint
  • Operating Time: <30ms including="" breaker="" failure="">

10.4 Breaker Failure Protection (50BF)

10.4 Breaker Failure Protection (50BF)

11. Special Protection Schemes

11.1 Reclosing (79)

11.1 Reclosing (79)

11.2 Sync Check Relay (25)

11.2 Sync Check Relay (25)

11.3 Underfrequency Load Shedding (81U)

  • Purpose: Restore generation/load balance during frequency decay; prevent system collapse
  • Typical Stages: 59.5 Hz (10% load), 59.0 Hz (10%), 58.7 Hz (15%), 58.5 Hz (15%)
  • Time Delays: 0.1-1.0s per stage; prevents nuisance tripping for momentary swings
  • Rate of Change: df/dt supervision optional; -0.5 to -1.0 Hz/s indicates severe deficit
  • Restoration: Manual or automatic after frequency recovers to >59.8 Hz for 5 min
  • Load Selection: Non-essential loads first; avoid critical infrastructure

11.4 Overvoltage/Undervoltage Protection

11.4 Overvoltage/Undervoltage Protection

11.5 Frequency Relay Applications

11.5 Frequency Relay Applications

12. Relay Coordination Principles

12.1 Coordination Time Intervals

12.1 Coordination Time Intervals

12.2 Coordination Study Steps

  • 1. One-Line Diagram: Complete with all protective devices, ratings, impedances
  • 2. Fault Study: Calculate maximum and minimum fault currents at all buses
  • 3. Device Selection: Choose relay types, curves, CT/PT ratios
  • 4. Starting Point: Begin at load end (furthest downstream device)
  • 5. Work Upstream: Each upstream device must coordinate with downstream
  • 6. Check Instantaneous: Set at 150-200% of maximum through fault current
  • 7. Plot Curves: Verify CTI on time-current curve (TCC) plot
  • 8. Sensitivity Check: Verify operation for minimum fault current

12.3 Common Coordination Issues

12.3 Common Coordination Issues

12.4 Relay Setting Calculations

12.4 Relay Setting Calculations

13. ANSI Device Numbers

13.1 Common Device Functions

13.1 Common Device Functions

13.2 Suffix Letters

13.2 Suffix Letters
The document Cheatsheet: Protection Systems is a part of the PE Exam Course Electrical & Computer Engineering for PE.
All you need of PE Exam at this link: PE Exam

Top Courses for PE Exam

Related Searches
Important questions, Free, MCQs, shortcuts and tricks, Objective type Questions, study material, pdf , past year papers, mock tests for examination, Summary, Viva Questions, video lectures, practice quizzes, Cheatsheet: Protection Systems, Cheatsheet: Protection Systems, Sample Paper, Semester Notes, Extra Questions, Cheatsheet: Protection Systems, ppt, Exam, Previous Year Questions with Solutions;