| Property | Definition & Formula |
|---|---|
| Dry Bulb Temperature (DBT) | Air temperature measured by standard thermometer, °F or °C |
| Wet Bulb Temperature (WBT) | Temperature measured with wet wick over thermometer bulb; measures evaporative cooling effect |
| Dew Point Temperature (DPT) | Temperature at which water vapor begins to condense at constant pressure |
| Humidity Ratio (W) | Mass of water vapor per mass of dry air, W = 0.622(Pv/(P - Pv)), lb water/lb dry air |
| Relative Humidity (φ) | φ = (Pv/Psat) × 100%, ratio of actual vapor pressure to saturation vapor pressure |
| Specific Volume (v) | Volume per unit mass of dry air, v = 0.754(T + 460)/P, ft³/lb dry air |
| Enthalpy (h) | h = 0.240T + W(1061 + 0.444T), Btu/lb dry air; T in °F |
| Process | Description |
|---|---|
| Sensible Heating | Horizontal line to right; increases DBT, constant W |
| Sensible Cooling | Horizontal line to left; decreases DBT, constant W |
| Humidification | Vertical line upward; increases W, constant DBT (adiabatic adds moisture and heat) |
| Dehumidification | Line toward saturation curve then along it; cooling below dew point removes moisture |
| Evaporative Cooling | Line along constant WBT toward saturation; decreases DBT, increases W |
| Heating & Humidifying | Diagonal line upward to right; increases DBT and W |
| Cooling & Dehumidifying | Line toward and along saturation curve; decreases DBT and W |
| Parameter | Formula |
|---|---|
| Sensible Heat (qs) | qs = 1.08 × CFM × ΔT, Btu/hr; or qs = 60 × ṁ × cp × ΔT |
| Latent Heat (ql) | ql = 0.68 × CFM × ΔW, Btu/hr; or ql = 60 × ṁ × hfg × ΔW |
| Total Heat (qt) | qt = 4.5 × CFM × Δh, Btu/hr; or qt = qs + ql |
| Sensible Heat Ratio (SHR) | SHR = qs/qt |
| Mixing of Air Streams | Weighted average: T3 = (ṁ1×T1 + ṁ2×T2)/(ṁ1 + ṁ2); same for W, h |
| Component | Description |
|---|---|
| External Sensible | Solar radiation through windows, conduction through walls/roof/floors |
| Internal Sensible | People, lights, equipment, appliances |
| Latent Load | Moisture from people, infiltration, ventilation, equipment |
| Ventilation Load | Outdoor air for IAQ requirements (sensible + latent) |
| Type | Formula |
|---|---|
| Conduction | Q = U × A × ΔT, Btu/hr; U = overall heat transfer coefficient, Btu/(hr·ft²·°F) |
| Solar Heat Gain | Q = A × SHGC × SC × CLF, where SHGC = solar heat gain coefficient, SC = shading coefficient, CLF = cooling load factor |
| People Load (Sensible) | qs = N × qs,person × CLF, qs,person = 250 Btu/hr (seated, light work) |
| People Load (Latent) | ql = N × ql,person, ql,person = 200 Btu/hr (seated, light work) |
| Lighting Load | Q = 3.41 × W × Fut × Fsb × CLF, W in watts |
| Equipment Load | Q = 3.41 × W × Fload × Frad × CLF (electric); Q = Fu × Qinput (gas) |
| Infiltration | qs = 1.08 × CFM × ΔT; ql = 0.68 × CFM × ΔW |
| System Type | Characteristics |
|---|---|
| Single Zone Constant Volume | One thermostat controls entire system; simple, low cost; suited for single space |
| Multi-Zone | Central unit with hot and cold decks; mixing dampers for each zone; limited to 12-15 zones |
| Variable Air Volume (VAV) | Varies airflow to maintain temperature; terminal boxes with dampers; energy efficient |
| Dual Duct | Separate hot and cold air ducts; mixing boxes at zones; high energy use, flexible |
| Reheat | Cool air to all zones, reheat coils for individual control; poor energy efficiency |
| System Type | Characteristics |
|---|---|
| Two-Pipe | One supply, one return; heating or cooling only at one time |
| Three-Pipe | Hot supply, cold supply, common return; simultaneous heating/cooling; energy waste in return |
| Four-Pipe | Separate hot/cold supply and return; most flexible, highest cost, best energy performance |
| Fan Coil Units | Individual room units with fan and coil; simple control, local maintenance |
| System Type | Characteristics |
|---|---|
| Split System | Outdoor condensing unit, indoor evaporator; residential and light commercial |
| Package Unit | All components in single cabinet; rooftop or ground-mounted |
| Variable Refrigerant Flow (VRF) | One outdoor unit, multiple indoor units; variable capacity compressor; heat recovery option |
| Heat Pump | Reversible refrigeration cycle; heating and cooling from one unit |
| Method | Description |
|---|---|
| Equal Friction | Constant pressure drop per unit length throughout system; simplest method |
| Static Regain | Velocity reduction in downstream sections regains static pressure; self-balancing |
| Total Pressure | Optimizes total pressure at each section; most complex, best for long runs |
| Parameter | Formula/Value |
|---|---|
| Velocity (V) | V = Q/A, Q = volumetric flow (CFM), A = area (ft²), V in ft/min (FPM) |
| Pressure Drop | ΔP = f × (L/D) × (V²/2g) × (ρ/12), in. w.g.; simplified: ΔP = C × L, C = friction rate |
| Velocity Pressure (VP) | VP = (V/4005)², in. w.g.; V in FPM |
| Total Pressure (TP) | TP = SP + VP, SP = static pressure |
| Equivalent Diameter (De) | De = 1.30 × [(a × b)^0.625] / [(a + b)^0.25], rectangular duct, a and b in inches |
| Application | Main Ducts (FPM) |
|---|---|
| Residential | 700-900 |
| Commercial Low Velocity | 1000-1800 |
| Commercial High Velocity | 2000-3000 |
| Industrial | 1800-3000 |
| Device | Application |
|---|---|
| Diffusers (Ceiling) | Supply air; circular, square, or linear; low velocity for comfort |
| Grilles | Return or exhaust air; fixed or adjustable vanes |
| Registers | Supply air; adjustable vanes for directional control |
| Slot Diffusers | Linear supply; architectural integration; perimeter heating |
| Type | Characteristics |
|---|---|
| Fire-Tube | Hot gases pass through tubes surrounded by water; lower pressure (<300 psig);="" smaller="">300> |
| Water-Tube | Water flows through tubes heated externally; higher pressure (>300 psig); larger capacity |
| Condensing | Extracts latent heat from flue gas; efficiency >90%; requires corrosion-resistant materials |
| Non-Condensing | Standard efficiency 75-85%; flue gas above dew point |
| Term | Definition |
|---|---|
| Thermal Efficiency | η = Qout/Qin = (ṁ × cp × ΔT) / (ṁfuel × HHV) |
| Combustion Efficiency | Based on flue gas temperature and composition; 80-85% typical |
| Annual Fuel Utilization Efficiency (AFUE) | Accounts for cycling losses; seasonal average; residential rating |
| Component | Function |
|---|---|
| Expansion Tank | Accommodates water volume change with temperature; diaphragm or compression type |
| Circulating Pump | Moves water through system; head (ft) = pressure drop; centrifugal type |
| Air Separator | Removes entrained air to prevent corrosion and noise |
| Pressure Relief Valve | Safety device; set at 30 psig for low-pressure systems |
| Mixing Valve | Blends supply and return water for temperature control |
| Type | Description |
|---|---|
| Series Loop | Single continuous pipe through all terminals; simplest, no individual control |
| One-Pipe | Supply main with diverting tees to terminals; poor balance |
| Two-Pipe Direct Return | Separate supply and return; first terminal has shortest circuit; balancing required |
| Two-Pipe Reverse Return | All circuits equal length; self-balancing; more piping |
| Primary-Secondary | Decouples production from distribution; separate pumps; allows variable flow |
| Type | Characteristics |
|---|---|
| Gas-Fired | Natural gas or propane; AFUE 80-97%; atmospheric or forced draft burner |
| Oil-Fired | Fuel oil atomization; AFUE 80-90%; pressure burner |
| Electric Resistance | 100% efficient at point of use; high operating cost; no combustion |
| Heat Pump | COP = 2-4; electric backup; economical in mild climates |
| Process | Component & Description |
|---|---|
| 1-2: Compression | Compressor; isentropic compression of superheated vapor; work input |
| 2-3: Condensation | Condenser; rejects heat to cooling medium; high-pressure vapor to liquid |
| 3-4: Expansion | Expansion valve; isenthalpic throttling; pressure and temperature drop |
| 4-1: Evaporation | Evaporator; absorbs heat from space; low-pressure liquid to vapor |
| Term | Formula |
|---|---|
| Coefficient of Performance (COP) | COP = Qevap / Wcomp = (h1 - h4) / (h2 - h1) |
| Energy Efficiency Ratio (EER) | EER = Cooling capacity (Btu/hr) / Power input (W); steady-state rating |
| Seasonal Energy Efficiency Ratio (SEER) | Seasonal average cooling output / electrical input; accounts for cycling; minimum 13-14 for residential |
| Integrated Part Load Value (IPLV) | Weighted efficiency at 100%, 75%, 50%, 25% load; commercial chiller rating |
| Tons of Refrigeration | 1 ton = 12,000 Btu/hr = 3.517 kW |
| Type | Characteristics |
|---|---|
| Reciprocating | Positive displacement; piston and cylinder; 5-200 tons; capacity control via cylinder unloading |
| Scroll | Positive displacement; two spiral scrolls; 1-20 tons; quiet, efficient, few moving parts |
| Screw | Positive displacement; twin helical rotors; 20-750 tons; continuous capacity modulation |
| Centrifugal | Dynamic; impeller imparts velocity; 100-10,000 tons; variable speed, efficient at full load |
| Type | Description |
|---|---|
| Air-Cooled | Air-cooled condenser; no cooling tower; lower efficiency; less maintenance |
| Water-Cooled | Water-cooled condenser; requires cooling tower; higher efficiency; more maintenance |
| Evaporatively-Cooled | Spray water on condenser; intermediate efficiency; lower water use than cooling tower |
| Absorption | Heat-driven cycle; LiBr-H2O or NH3-H2O; COP 0.6-1.2; uses waste heat or gas |
| Refrigerant | Characteristics |
|---|---|
| R-22 (HCFC) | Phased out; ODP = 0.055; residential and commercial legacy systems |
| R-410A (HFC) | Replacement for R-22; ODP = 0, GWP = 2088; higher pressure; not drop-in replacement |
| R-134a (HFC) | Automotive and chillers; ODP = 0, GWP = 1430; lower pressure |
| R-32 (HFC) | Lower GWP = 675; higher efficiency; mildly flammable (A2L) |
| R-717 (NH3) | Ammonia; natural refrigerant; ODP = 0, GWP = 0; toxic, industrial use |
| R-744 (CO2) | Natural refrigerant; ODP = 0, GWP = 1; transcritical cycle; high pressure |
| Type | Description |
|---|---|
| Induced Draft | Fan at top pulls air through; counterflow or crossflow; most common |
| Forced Draft | Fan at bottom pushes air through; lower height; higher recirculation risk |
| Natural Draft | Hyperbolic shape; no fan; very large; power plants |
| Open Circuit | Direct water-air contact; evaporative cooling; high efficiency |
| Closed Circuit | Coil separates process water from spray water; less evaporation; protects process fluid |
| Space Type | CFM per Person |
|---|---|
| Office Space | 5 |
| Conference Room | 5 |
| Classroom | 10 |
| Retail | 7.5 |
| Restaurant Dining | 7.5 |
| Gymnasium | 20 |
| Contaminant | Source & Control |
|---|---|
| CO2 | Occupant respiration; indicator of ventilation adequacy; <1000 ppm="">1000> |
| CO | Combustion; garage exhaust; <9 ppm="" 8-hr="">9> |
| Particulate Matter | Outdoor air, activities; filtration MERV 8-13 |
| VOCs | Building materials, furnishings, cleaning; source control, ventilation |
| Radon | Soil gas; sub-slab depressurization; <4>4> |
| Biological | Moisture, HVAC systems; humidity control <60% rh,="">60%> |
| MERV Rating | Application |
|---|---|
| 1-4 | Residential; removes particles >10 μm |
| 5-8 | Commercial buildings; removes particles 3-10 μm |
| 9-12 | Superior commercial, hospital; removes particles 1-3 μm |
| 13-16 | Hospital, general surgery; removes particles 0.3-1 μm |
| 17-20 | HEPA; cleanrooms; removes particles <0.3 μm;="" 99.97%="" efficient="" at="" 0.3="">0.3> |
| Device | Description |
|---|---|
| Heat Recovery Ventilator (HRV) | Sensible heat transfer only; air-to-air heat exchanger; heating climates |
| Energy Recovery Ventilator (ERV) | Sensible and latent heat transfer; enthalpy wheel or membrane; humid climates |
| Run-Around Loop | Coils in exhaust and outdoor air streams; pumped glycol loop; separated airstreams |
| Heat Pipe | Passive refrigerant transfer; no moving parts; limited capacity |
| Type | Characteristics |
|---|---|
| Pneumatic | Compressed air 15-20 psig; reliable, simple; legacy systems |
| Electric | 24V AC or 120V AC; two-position or modulating; low cost |
| Electronic (Analog) | 0-10V DC or 4-20 mA signals; modulating control; accurate |
| Direct Digital Control (DDC) | Microprocessor-based; communication networks; complex sequences; remote monitoring |
| Mode | Description |
|---|---|
| On-Off (Two-Position) | Binary control; simple, low cost; temperature swings; residential thermostats |
| Proportional (P) | Output proportional to error; offset remains; throttling range (TR) = change in controlled variable for full actuator stroke |
| Proportional-Integral (PI) | Eliminates offset; integral time Ti; most common HVAC control |
| Proportional-Integral-Derivative (PID) | Adds derivative (rate) action; faster response; complex tuning; less common in HVAC |
| Strategy | Description |
|---|---|
| Discharge Air Temperature Reset | Increase supply air temperature as load decreases; reduces reheat, improves efficiency |
| Static Pressure Reset | Reduce fan speed as VAV dampers open; saves fan energy |
| Chilled Water Temperature Reset | Increase CHW supply temperature at part load; improves chiller efficiency |
| Hot Water Temperature Reset | Outdoor air temperature reset; lower HW temperature in mild weather; reduces losses |
| Demand-Controlled Ventilation | Modulate outdoor air based on CO2 sensors; reduces ventilation energy at low occupancy |
| Optimal Start/Stop | Adaptive algorithm learns building thermal mass; starts equipment at latest time to meet setpoint |
| Night Setback | Raise cooling setpoint or lower heating setpoint during unoccupied periods |
| Device | Type & Application |
|---|---|
| Temperature Sensor | Thermistor, RTD, thermocouple; accuracy ±0.5-2°F |
| Humidity Sensor | Capacitive, resistive; accuracy ±3-5% RH |
| Pressure Sensor | Diaphragm, piezoelectric; static pressure, differential pressure |
| Flow Sensor | Differential pressure, thermal, ultrasonic; air or water flow measurement |
| CO2 Sensor | NDIR (non-dispersive infrared); demand-controlled ventilation; accuracy ±50 ppm |
| Control Valve | Two-way or three-way; modulating; hydronic systems; equal percentage or linear characteristic |
| Damper Actuator | Spring return or non-spring return; modulating or two-position; air systems |
| Variable Frequency Drive (VFD) | Modulates motor speed; fans and pumps; affinity laws apply |
| Parameter | Formula |
|---|---|
| Head (H) | H = (P2 - P1) / (ρ × g) + z2 - z1 + hL, ft; P = pressure, z = elevation, hL = losses |
| Pump Power (Water) | BHP = (GPM × H × SG) / (3960 × ηp), BHP in hp; ηp = pump efficiency |
| System Curve | H = Hstatic + K × Q², K depends on pipe friction |
| Affinity Laws (Speed) | Q2/Q1 = N2/N1; H2/H1 = (N2/N1)²; P2/P1 = (N2/N1)³ |
| Affinity Laws (Impeller Diameter) | Q2/Q1 = D2/D1; H2/H1 = (D2/D1)²; P2/P1 = (D2/D1)³ |
| Net Positive Suction Head (NPSH) | NPSH available > NPSH required to prevent cavitation |
| Type | Characteristics |
|---|---|
| End Suction Centrifugal | Single inlet; horizontal or vertical; 10-5000 GPM; most common HVAC pump |
| Inline Centrifugal | Suction and discharge in line; space-saving; 10-1000 GPM |
| Split Case | Horizontal split casing; double suction; 500-10,000 GPM; high efficiency, low NPSH |
| Vertical Turbine | Multistage; sump or tank mounting; high head applications |
| Parameter | Formula |
|---|---|
| Fan Total Pressure (FTP) | FTP = TP_discharge - TP_inlet, in. w.g. |
| Fan Static Pressure (FSP) | FSP = FTP - VP_discharge |
| Fan Power | BHP = (CFM × FTP) / (6356 × ηf), BHP in hp; ηf = fan efficiency |
| Affinity Laws (Speed) | Q2/Q1 = N2/N1; P2/P1 = (N2/N1)²; BHP2/BHP1 = (N2/N1)³ |
| Affinity Laws (Density) | Q2/Q1 = 1; P2/P1 = ρ2/ρ1; BHP2/BHP1 = ρ2/ρ1 |
| Type | Characteristics |
|---|---|
| Forward Curved Centrifugal | Low speed, quiet; low efficiency 60-65%; space constraints; overloading power curve |
| Backward Inclined Centrifugal | High efficiency 75-80%; non-overloading; general HVAC; moderate noise |
| Airfoil Centrifugal | Highest efficiency 80-85%; low noise; premium cost; clean air only |
| Radial Blade Centrifugal | Material handling; erosion resistant; low efficiency; industrial |
| Vane Axial | Guide vanes; medium efficiency 65-75%; high pressure; compact |
| Tube Axial | Propeller in cylinder; efficiency 60-70%; low-medium pressure; inline installation |
| Propeller | No housing; low pressure; high volume; exhaust applications |
| Standard | Scope |
|---|---|
| ASHRAE 90.1 | Energy Standard for Buildings Except Low-Rise Residential; prescriptive and performance paths |
| IECC | International Energy Conservation Code; adopted by most states; residential and commercial |
| Title 24 (California) | State energy code; stricter than ASHRAE 90.1; mandatory compliance |
| ASHRAE 189.1 | Standard for High-Performance Green Buildings; voluntary; beyond 90.1 |
| Method | Description |
|---|---|
| Simplified (Bin Method) | Weather data in temperature bins; steady-state calculations; quick estimates |
| Detailed Simulation | Hourly time-step; dynamic thermal response; EnergyPlus, eQUEST, TRACE; accurate predictions |
| Performance Rating Method | ASHRAE 90.1 Appendix G; proposed design vs. baseline; % better than code |
| Measure | Typical Savings |
|---|---|
| Economizer | 10-30% cooling energy |
| VFD on Fans/Pumps | 30-50% fan/pump energy |
| Demand-Controlled Ventilation | 10-25% ventilation energy |
| Heat Recovery | 30-50% heating/cooling of ventilation air |
| High-Efficiency Equipment | 10-30% depending on baseline |
| Improved Controls | 5-15% overall HVAC energy |
| Duct Sealing | 10-30% distribution losses |
| Night Setback | 5-15% heating energy |
| Phase | Activities |
|---|---|
| Pre-Design | Owner's project requirements (OPR); basis of design (BOD) |
| Design | Review submittals; design intent verification; update BOD |
| Construction | Equipment verification; functional performance tests (FPT); issues log |
| Acceptance | Systems manual; operator training; final report |
| Warranty/Post-Occupancy | Seasonal testing; review operation; re-training |