Round the clock cooling of an apartment having a load of 300 MJ/day requires and air conditioning plant of capacity about
[1993]
In a vapour compression refrigeration system, liquids to suction heat exchanger is used to
[2000]
1 Crore+ students have signed up on EduRev. Have you? Download the App |
A refrigerator based on ideal vapour compression cycle operates between the temperature limits of –20°C and 40°C. The refrigerant enters the condenser as saturated vapour and leaves as saturated liquid. The enthalpy and entropy values for saturated liquid and vapour at these temperatures are given in the table below.
If refrigerant circulation rate is 0.025 kg/s, the refrigeration effect is equal to
[2003]
A refrigerator based on ideal vapour compression cycle operates between the temperature limits of –20°C and 40°C. The refrigerant enters the condenser as saturated vapour and leaves as saturated liquid. The enthalpy and entropy values for saturated liquid and vapour at these temperatures are given in the table below.
The COP of the refrigerator is
[2003]
In the window air conditioner, the expansion device used is
[2004]
A R-12 refrigerant reciprocating compressor operates between the condensing temperature of 30º and evaporator temperature of –20ºC. The clearance volume ratio of the compressor is 0.03. Specific heat ratio of the vapour is 1.15 and the specific volume at the suction is 0.1089 m3/kg. Other properties at various states are given in the figure. To realize 2 tons of refrigeration, the actual volume displacement rate considering the effect of clearance is
[2004]
The vapour compression refrigeration cycle is represented as shown in the figure below, with state 1 being the exit of the evaporator. The coordinate system used in this figure is
[2005]
In an ideal vapour compression refrigeration cycle, the specific enthalpy of refrigerant (in kJ/kg) at the following states is given as:
Inlet of condenser : 283
Exit of condenser : 116
Exit of evaporator : 232
The COP of this cycle is
[2009]
A refrigerator operates between 120 kPa and 800 kPa in an ideal vapor compression cycle with R-134a as the refrigerant. The refrigerant enters the compressor as saturated vapor and leaves the condenser as saturated liquid. The mass flow rate of the refrigerant is 0.2 kg/s.
Properties for R -134a are as follows: Saturated R-134a
The rate at which heat is extracted, in kJ/s from the refrigerated space is
[2012]
A refrigerator operates between 120 kPa and 800 kPa in an ideal vapor compression cycle with R-134a as the refrigerant. The refrigerant enters the compressor as saturated vapor and leaves the condenser as saturated liquid. The mass flow rate of the refrigerant is 0.2 kg/s.
Properties for R -134a are as follows: Saturated R-134a
The power required for compressor in kW is
[2016]
Consider an ideal vapor compression refrigeration cycle. If the throttling process is replaced by an isentropic expansion process, keeping all the other processes unchanged, which one of the following statements is true for the modified cycle?
[2019]
Environment friendly refrigerant R134a is used in the new generation domestic refrigerators.Its Chemical formula is
[2004]
Which one of the following is a CFC refrigerant?
[2015]