A 50 KVA, 11000/400 V Δ-Y distribution transformer has a resistance of 1% and reactance of 7% per unit. What is the transformer phase impedance referred to the high-voltage side?
An auto transformer is used to connect a 12.6 kV distribution line to a 13.8 kV distribution line. It must be capable of handling 2000 kVA. There are three phases, connected Y-Y with their neutrals solidly grounded. What must the NC/NSE turn ratio be to accomplish this connection? (NC→ common turn, NSE → Series turn)
1 Crore+ students have signed up on EduRev. Have you? Download the App |
A 3-phase bank of three single phase transformer are fed from 3 phase 33 kV (L-L). It supplies a load of 5000 kVA at 11 kV (L-L). Both supply and load three wire. Calculate the voltage rating of single phase transformer for start-delta connection.
Three single phase transformers are connected to form a3 - ϕ transformer bank the transformer are connected in the following manner.
the transformer connecting will be represented by
A 100,000-KVA 230/115 – kV Δ-Δ three phase power transformer has a per-unit resistance of 0.02 PU and a per unit reactance of 0.055. The excitation branch element are RC = 110 PU and XM = 20 PU. If this transformer supplies a load of 80 MVA at 0.85 P.F lagging. Find the voltage regulation (in %) of the transformer bank under these conditions.
The terminal voltage on the secondary side when supplying full load at 0.8 lagging P.F. is 440 V. the equivalent Resistance and reactance drops for the transformer are 1% and 5% respectively.
Find Induced voltage per phase (in volt) at the secondary side.
A1 ϕ 33 kVA, 3300 V/330 V, 50 Hz, distribution transformer is to be connected as an auto-transformer to get an output voltage of 3630 V. It maximum kVA rating as an auto-transformer is________kVA
A 50 Hz, 3ϕ core type star-delta transformer has a line valtage ratio of 11,000/440 volts. The cross-section of the core is square with a circumscribing circle of 0.5 m diameter. If maximum flux density of 1.30 ωb/m2 then find the number of turns per phase on high voltage windings. Assume insulation occupies 8% of the total core area.
In a Star\Delta 3 phase transformer connection, the turns ratio is N1/N2 with N1 being primary side turns and N2 being secondary side turns. What is the value of line voltage and current on secondary side, if the same for primary side are V & I respectively ?
A 3 – phase, Δ – Y, 33000 / 660 V, 150 kVA, 50Hz transformer is having resistance per phase of 4 Ω on primary side and 0.15 Ω on secondary side. If the efficiency of transformer and half load is 96.5% at 0.85 pf (lagging), then what are the iron losses?
25 docs|247 tests
|
25 docs|247 tests
|