Electrical Engineering (EE) Exam  >  Electrical Engineering (EE) Test  >  Power Systems  >  Test: Surge Impedance Loading - Electrical Engineering (EE) MCQ

Surge Impedance Loading - Free MCQ Practice Test with solutions, GATE EE


MCQ Practice Test & Solutions: Test: Surge Impedance Loading (10 Questions)

You can prepare effectively for Electrical Engineering (EE) Power Systems with this dedicated MCQ Practice Test (available with solutions) on the important topic of "Test: Surge Impedance Loading". These 10 questions have been designed by the experts with the latest curriculum of Electrical Engineering (EE) 2026, to help you master the concept.

Test Highlights:

  • - Format: Multiple Choice Questions (MCQ)
  • - Duration: 20 minutes
  • - Number of Questions: 10

Sign up on EduRev for free to attempt this test and track your preparation progress.

Test: Surge Impedance Loading - Question 1

An overhead line with surge impedance of 400 Ω is terminated through a resistance R. A surge travelling over the line does not suffer any reflection at the junction, if the value of R is

Detailed Solution: Question 1

When a loss-free overhead transmission line is terminated through a resistance equal to surge Impedance of the line, there will be no reflection of travelling wave hence the value of R is 400 Ω.

Important Points:

The surge impedance or characteristic impedance of a long transmission line is given by,

Z is series impedance per unit length per phase

Y is shunt admittance per unit length per phase

Surge Impedance for the transmission line is about 400 ohms it is around 40 ohms for underground cables.

Surge impedance loading (SIL):

Surge impedance loading is defined as the power load in which the total reactive power of the lines becomes zero. The reactive power generated by the shunt capacitance is consumed by the series inductance of the line.

Test: Surge Impedance Loading - Question 2

What is the approximate value of the surge impedance loading of a 400 kV, 3-phase 50 Hz overhead single circuit transmission line

Detailed Solution: Question 2

Concept:

The surge impedance or characteristic impedance of a long transmission line is given by,

Z is series impedance per unit length per phase

Y is shunt admittance per unit length per phase

The surge Impedance for the transmission line is about 400 ohms it is around 40 ohms for underground cables.

Surge impedance loading (SIL):

Surge impedance loading is defined as the power load in which the total reactive power of the lines becomes zero. The reactive power generated by the shunt capacitance is consumed by the series inductance of the line.

Calculation:

Surge impedance (ZC) = 400 Ω

Voltage (V) = 400 kV

Surge impedance loading 

Test: Surge Impedance Loading - Question 3

Surge impedance loading of a transmission line is also known as:

Detailed Solution: Question 3

The surge impedance or characteristic impedance of a long transmission line is given by,

Z is series impedance per unit length per phase

Y is shunt admittance per unit length per phase

Surge impedance loading (SIL):

Surge impedance loading is defined as the power load in which the total reactive power of the lines becomes zero. The reactive power generated by the shunt capacitance is consumed by the series inductance of the line.

Test: Surge Impedance Loading - Question 4

The surge impedance of 100 km long underground cable is 50 Ω. The surge impedance for 50 km length of similar cable would be:

Detailed Solution: Question 4

Surge impedance:

The surge impedance or characteristic impedance of a long transmission line is given by,

Where,

Z is series impedance per unit length per phase

Y is shunt admittance per unit length per phase

In case of a lossless line (i.e. R = 0, G = 0), the surge impedance is given by

  • Surge impedance does not depend upon the length of the transmission line.
  • Surge impedance depends on the characteristics of the transmission line like diameter & spacing between the conductors.
  • So that surge impedance of 100 km and 50km long underground cable is 50 Ω.
     

Important Points

​Surge impedance loading (SIL):

Surge impedance loading is defined as the power load in which the total reactive power of the lines becomes zero. The reactive power generated by the shunt capacitance is consumed by the series inductance of the line.

Test: Surge Impedance Loading - Question 5

Surge impedance of Phase, 400 kV transmission line is 200 Ω. The surge impedance loading of the transmission line is

Detailed Solution: Question 5

Concept:

The surge impedance or characteristic impedance of a long transmission line is given by,

Z is series impedance per unit length per phase

Y is shunt admittance per unit length per phase

Surge impedance loading (SIL):

Surge impedance loading is defined as the power load in which the total reactive power of the lines becomes zero. The reactive power generated by the shunt capacitance is consumed by the series inductance of the line.

Calculation:

Given that, surge impedance (ZC) = 200 Ω

Voltage (V) = 400 kV

Test: Surge Impedance Loading - Question 6

The surge impedance of a 50-mile-long underground cable is 50 ohms. It will be _________ for a length of 25 miles.

Detailed Solution: Question 6

Surge impedance:

The surge impedance or characteristic impedance of a long transmission line is given by,

Where,

Z is series impedance per unit length per phase

Y is shunt admittance per unit length per phase

In case of a lossless line (i.e. R = 0, G = 0), the surge impedance is given by

  • Surge impedance does not depend upon the length of the transmission line.
  • Surge impedance depends on the characteristics of the transmission line like diameter & spacing between the conductors.
  • So that surge impedance of 50 miles and 25 miles long underground cable is 50 Ω.
     

Important Points

​Surge impedance loading (SIL):

Surge impedance loading is defined as the power load in which the total reactive power of the lines becomes zero. The reactive power generated by the shunt capacitance is consumed by the series inductance of the line.

Test: Surge Impedance Loading - Question 7

Generally characteristic impedance of cable is taken as _______

Detailed Solution: Question 7

Concept:

The surge impedance or characteristic impedance of a long transmission line is given by,

Z is series impedance per unit length per phase

Y is shunt admittance per unit length per phase

The surge Impedance for the transmission line is about 400 ohms it is around 40 ohms for underground cables.

For overhead line surge impedance is given by 100 - 200  Ω

For underground cable surge impedance is given by 40 - 60 Ω

Test: Surge Impedance Loading - Question 8

What is the nature of power factor if surge impedance loading is less than load?

Detailed Solution: Question 8

Surge Impedance Loading (SIL):

  • It is the loading on the line whenever the load impedance is exactly matching to surge impedance of the transmission line.
  • It is also known as characteristic impedance loading or ideal loading or ideal power transfer capability.
  • So, at SIL the load impedance is equal to characteristic impedance (ZL = ZC).

Surge impedance loading 

Where, ZC = Characteristic impedance = √(z/y)

Case 1: If loading is equal to SIL

  • Load impedance is equal to characteristic impedance.
  • The transmission line will act as neither sink nor source of reactive power.
  • Receiving end voltage is equal to sending end voltage.
  • Sending end current is equal to receiving end current.
  • Both sending end and receiving end power factors are unity

Case 2: If loading is greater than SIL

  • Load impedance is less than the characteristic equation.
  • The transmission line will act as a sink of reactive power.
  • Receiving end voltage is less than the sending end voltage
  • Receiving current is more than sending end current.
  • Receiving end power factor is unity but sending end power factor is lagging.

Case 3: If loading is less than SIL

  • Load impedance is greater than the characteristic equation.
  • The transmission line will act as a source of reactive power.
  • Receiving end voltage is greater than the sending end voltage
  • Receiving current is less than sending end current.
  • Receiving end power factor is unity but sending end power factor is leading.

Test: Surge Impedance Loading - Question 9

The SIL (Surge Impedance Loading) of the transmission line for given configuration 3-phase, 200 kV, 400 ohm is:

Detailed Solution: Question 9

Concept:

The surge impedance or characteristic impedance of a long transmission line is given by,

Z is series impedance per unit length per phase

Y is shunt admittance per unit length per phase

  • The surge Impedance for the transmission line is about 400 ohms it is around 40 ohms for underground cables.
     

Surge impedance loading (SIL):

  • Surge impedance loading is defined as the power load in which the total reactive power of the lines becomes zero.
  • The reactive power generated by the shunt capacitance is consumed by the series inductance of the line.
     

Calculation:

Given:

Surge impedance (ZC) = 400 Ω

Voltage (V) = 200 kV

Test: Surge Impedance Loading - Question 10

Consider the following statements:

1. If loading is less than SIL the transmission line will act as a source of reactive power.

2. If loading is more than the SIL receiving current is more than sending end current.

3. Both sending end and receiving end power factors are unity whenever loading is equal to surge impedance loading (SIL)

Which of the above statement(s) is/are correct?

Detailed Solution: Question 10

Surge Impedance Loading (SIL):

  • It is the loading on the line whenever the load impedance is exactly matching to surge impedance of the transmission line.
  • It is also known as characteristic impedance loading or ideal loading or ideal power transfer capability.
  • So, at SIL the load impedance is equal to characteristic impedance (ZL = ZC).

Surge impedance loading 
Where, Z= Characteristic impedance = √(z/y)

Case 1: If loading is equal to SIL

  • Load impedance is equal to characteristic impedance.
  • The transmission line will act as neither sink nor source of reactive power.
  • Receiving end voltage is equal to sending end voltage.
  • Sending end current is equal to receiving end current.
  • Both sending end and receiving end power factors are unity


Case 2: If loading is greater than SIL

  • Load impedance is less than the characteristic equation.
  • The transmission line will act as a sink of reactive power.
  • Receiving end voltage is less than the sending end voltage
  • Receiving current is more than sending end current.
  • Receiving end power factor is unity but sending end power factor is lagging.


Case 3: If loading is less than SIL

  • Load impedance is greater than the characteristic equation.
  • The transmission line will act as a source of reactive power.
  • Receiving end voltage is greater than the sending end voltage
  • Receiving current is less than sending end current.
  • Receiving end power factor is unity but sending end power factor is leading.

21 videos|112 docs|45 tests
Information about Test: Surge Impedance Loading Page
In this test you can find the Exam questions for Test: Surge Impedance Loading solved & explained in the simplest way possible. Besides giving Questions and answers for Test: Surge Impedance Loading, EduRev gives you an ample number of Online tests for practice
21 videos|112 docs|45 tests
Download as PDF