Download, print and study this document offline |
Page 1 Fault Analysis Symmetrical Components For an unbalanced 3 – phase system, the analysis is done better by means of symmetrical components. a0 V ? Zero sequence components a1 V ? Positive sequence components a2 V ? Negative sequence components a0 a 2 a1 b 2 a2 c V 1 1 1 V 1 V 1 V 3 V 1 V ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ?? ; Where 0 j120 e ?? ? ? ? ? 1 sp V A V ? ?? ? ?? p V = phase voltage s V = Symmetrical component 2 2 1 1 1 A1 1 ?? ?? ? ? ? ?? ?? ?? ?? Power in terms of symmetrical components a1 a1 a2 a2 a3 a0 P 3 V I V I V I ? ? ? ?? ? ? ? ?? Remember, same transformation exist for current also. Sequence Network Alternators ? Positive Sequence Network 1 Z positive sequence impedance " 1d Z jX ? Page 2 Fault Analysis Symmetrical Components For an unbalanced 3 – phase system, the analysis is done better by means of symmetrical components. a0 V ? Zero sequence components a1 V ? Positive sequence components a2 V ? Negative sequence components a0 a 2 a1 b 2 a2 c V 1 1 1 V 1 V 1 V 3 V 1 V ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ?? ; Where 0 j120 e ?? ? ? ? ? 1 sp V A V ? ?? ? ?? p V = phase voltage s V = Symmetrical component 2 2 1 1 1 A1 1 ?? ?? ? ? ? ?? ?? ?? ?? Power in terms of symmetrical components a1 a1 a2 a2 a3 a0 P 3 V I V I V I ? ? ? ?? ? ? ? ?? Remember, same transformation exist for current also. Sequence Network Alternators ? Positive Sequence Network 1 Z positive sequence impedance " 1d Z jX ? ? Negative Sequence Network a2 a2 2 V I Z ?? 2 Z : Negative sequence impedance dq 2 X " X " Zj 2 ? ?? ? ?? ?? ? Zero Sequence Network ? ? a0 a0 0 n V I Z 3Z ? ? ? 0 Z = Zero sequence impedance n Z =Neutral impedance ( ? in case of delta) 0l Z jX ? l X = leakage reactance Transformers ? Positive Sequence Network 1 Z = Positive sequence impedance 1l Z jX ? ? Negative Sequence Network 2 Z = Negative sequence impedance 2l Z jX ? ? Zero sequence network Depending upon scheme of connection, we close series or shunt connection & method of grounding. Page 3 Fault Analysis Symmetrical Components For an unbalanced 3 – phase system, the analysis is done better by means of symmetrical components. a0 V ? Zero sequence components a1 V ? Positive sequence components a2 V ? Negative sequence components a0 a 2 a1 b 2 a2 c V 1 1 1 V 1 V 1 V 3 V 1 V ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ?? ; Where 0 j120 e ?? ? ? ? ? 1 sp V A V ? ?? ? ?? p V = phase voltage s V = Symmetrical component 2 2 1 1 1 A1 1 ?? ?? ? ? ? ?? ?? ?? ?? Power in terms of symmetrical components a1 a1 a2 a2 a3 a0 P 3 V I V I V I ? ? ? ?? ? ? ? ?? Remember, same transformation exist for current also. Sequence Network Alternators ? Positive Sequence Network 1 Z positive sequence impedance " 1d Z jX ? ? Negative Sequence Network a2 a2 2 V I Z ?? 2 Z : Negative sequence impedance dq 2 X " X " Zj 2 ? ?? ? ?? ?? ? Zero Sequence Network ? ? a0 a0 0 n V I Z 3Z ? ? ? 0 Z = Zero sequence impedance n Z =Neutral impedance ( ? in case of delta) 0l Z jX ? l X = leakage reactance Transformers ? Positive Sequence Network 1 Z = Positive sequence impedance 1l Z jX ? ? Negative Sequence Network 2 Z = Negative sequence impedance 2l Z jX ? ? Zero sequence network Depending upon scheme of connection, we close series or shunt connection & method of grounding. Shunt connection are closed for delta connection & series connection are closed for star connection with grounded neutral. If primary & secondary are inter changed then circuit becomes mirror image. ? Case – 1 If neutral is grounded through an impedance n Z 0 T0 n Z Z 3Z ?? ? Case – 2 ? Case – 3 ? Case – 4 Page 4 Fault Analysis Symmetrical Components For an unbalanced 3 – phase system, the analysis is done better by means of symmetrical components. a0 V ? Zero sequence components a1 V ? Positive sequence components a2 V ? Negative sequence components a0 a 2 a1 b 2 a2 c V 1 1 1 V 1 V 1 V 3 V 1 V ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ?? ; Where 0 j120 e ?? ? ? ? ? 1 sp V A V ? ?? ? ?? p V = phase voltage s V = Symmetrical component 2 2 1 1 1 A1 1 ?? ?? ? ? ? ?? ?? ?? ?? Power in terms of symmetrical components a1 a1 a2 a2 a3 a0 P 3 V I V I V I ? ? ? ?? ? ? ? ?? Remember, same transformation exist for current also. Sequence Network Alternators ? Positive Sequence Network 1 Z positive sequence impedance " 1d Z jX ? ? Negative Sequence Network a2 a2 2 V I Z ?? 2 Z : Negative sequence impedance dq 2 X " X " Zj 2 ? ?? ? ?? ?? ? Zero Sequence Network ? ? a0 a0 0 n V I Z 3Z ? ? ? 0 Z = Zero sequence impedance n Z =Neutral impedance ( ? in case of delta) 0l Z jX ? l X = leakage reactance Transformers ? Positive Sequence Network 1 Z = Positive sequence impedance 1l Z jX ? ? Negative Sequence Network 2 Z = Negative sequence impedance 2l Z jX ? ? Zero sequence network Depending upon scheme of connection, we close series or shunt connection & method of grounding. Shunt connection are closed for delta connection & series connection are closed for star connection with grounded neutral. If primary & secondary are inter changed then circuit becomes mirror image. ? Case – 1 If neutral is grounded through an impedance n Z 0 T0 n Z Z 3Z ?? ? Case – 2 ? Case – 3 ? Case – 4 ? Case – 5 Transmission Lines ? Positive Sequence Network ? Negative Sequence Network ? Zero Sequence Network 1 2 s m Z Z Z Z ? ? ? 0 s m Z Z 2Z ?? s Z = Self impedance m Z = mutual impedance Remembers, all sequence networks are always drawn in per unit & never in actual values. Fault Analysis The following short circuit faults are considered 1. LG (Single Line to ground fault) 2. LL (Line to line fault) 3. LLG (Line to Line to Ground fault) 4. 3-phase short circuit fault. Page 5 Fault Analysis Symmetrical Components For an unbalanced 3 – phase system, the analysis is done better by means of symmetrical components. a0 V ? Zero sequence components a1 V ? Positive sequence components a2 V ? Negative sequence components a0 a 2 a1 b 2 a2 c V 1 1 1 V 1 V 1 V 3 V 1 V ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ? ?? ; Where 0 j120 e ?? ? ? ? ? 1 sp V A V ? ?? ? ?? p V = phase voltage s V = Symmetrical component 2 2 1 1 1 A1 1 ?? ?? ? ? ? ?? ?? ?? ?? Power in terms of symmetrical components a1 a1 a2 a2 a3 a0 P 3 V I V I V I ? ? ? ?? ? ? ? ?? Remember, same transformation exist for current also. Sequence Network Alternators ? Positive Sequence Network 1 Z positive sequence impedance " 1d Z jX ? ? Negative Sequence Network a2 a2 2 V I Z ?? 2 Z : Negative sequence impedance dq 2 X " X " Zj 2 ? ?? ? ?? ?? ? Zero Sequence Network ? ? a0 a0 0 n V I Z 3Z ? ? ? 0 Z = Zero sequence impedance n Z =Neutral impedance ( ? in case of delta) 0l Z jX ? l X = leakage reactance Transformers ? Positive Sequence Network 1 Z = Positive sequence impedance 1l Z jX ? ? Negative Sequence Network 2 Z = Negative sequence impedance 2l Z jX ? ? Zero sequence network Depending upon scheme of connection, we close series or shunt connection & method of grounding. Shunt connection are closed for delta connection & series connection are closed for star connection with grounded neutral. If primary & secondary are inter changed then circuit becomes mirror image. ? Case – 1 If neutral is grounded through an impedance n Z 0 T0 n Z Z 3Z ?? ? Case – 2 ? Case – 3 ? Case – 4 ? Case – 5 Transmission Lines ? Positive Sequence Network ? Negative Sequence Network ? Zero Sequence Network 1 2 s m Z Z Z Z ? ? ? 0 s m Z Z 2Z ?? s Z = Self impedance m Z = mutual impedance Remembers, all sequence networks are always drawn in per unit & never in actual values. Fault Analysis The following short circuit faults are considered 1. LG (Single Line to ground fault) 2. LL (Line to line fault) 3. LLG (Line to Line to Ground fault) 4. 3-phase short circuit fault. 3-phase short circuit fault comes under the category of symmetrical SC fault whereas other 3 faults are called as unsymmetrical SC fault. Order of severity LG < LL < LLG < 3 - ? SC But if faults occur at terminal of alternator then LG fault is most severe. Occurrence of SC fault LG > LL > LLG > 3 - ? SC Transient on a Transmission line Equivalent Circuit ? ? t ss i t i i ?? ? ? ? ? Rt mm L VV sin e sin wt ZZ ? ? ? ? ? ? ? ? ? ? ? ? 2 12 L tan ; Z R L R ? ?? ?? ?? ? ? ? ? ? ? Maximum momentary current ? ? m mm 2V i sin Z ? ? ? ? If resistance is neglected, 0 90 ?? m mm i 2V cos Z ?? Short circuit model of a synchronous machine During initial SC period for 1-2 cycles, current are induced in field & damper winding of machine so reactance at least & called as sub transient reactance ? ? d X" After initial sub-transient period, current in damper winding in reduced to zero, and this period is called as transient period & reactance of machine is called as Transient Reactance ? ? d X"Read More
|
Explore Courses for Electrical Engineering (EE) exam
|