A DC machine can operate either as a generator or as a motor depending on the relative magnitudes of the induced emf and the terminal supply voltage. The induced emf in the armature is E = k φ ω, where k is a machine constant, φ is the flux per pole and ω is the angular speed. If the prime mover drives the armature so that E > Vt (terminal voltage), the machine delivers power to the external circuit and behaves as a generator. If E < Vt, current flows into the armature and the machine behaves as a motor.
For the armature circuit the voltage relation differs by sign depending on the mode of operation.
The field current in a shunt winding is If = Vt / Rf, and the flux φ is a nonlinear function of If (magnetisation or saturation characteristic). In many analyses we assume φ is constant for small variations of If around the operating point, but the saturation curve must be kept in mind for larger changes.
The components of power and losses differ in generator and motor modes but the basic elements are the same:
When the machine works as a generator, the prime mover provides mechanical power T ω and electrical power is delivered to load or returned to a supply. When it works as a motor the electrical supply provides input power and the shaft delivers mechanical output T ω to the load.
From the voltage equations, armature current can be written in terms of speed or induced emf:
Using E = k φ ω gives expressions linking speed, armature current and terminal voltage. The armature current determines electromagnetic torque since Te = k φ Ia. The sign of Te follows the chosen sign convention: torque that assists motion is taken positive (motoring), torque opposing motion is negative (generating).
For a shunt machine with approximately constant field flux φ, one can derive a linear torque-speed relation.
Start from the motor voltage equation and torque expression and eliminate Ia.
This is the equation of a straight line in the ω-Te plane: the intercept on the speed axis (Te = 0) is the no-load speed ωnl = Vt / (k φ), and the slope is negative with magnitude Ra / (k φ)². The corresponding armature current axis is proportional to torque because Te ∝ Ia. In generator mode the same straight line applies with the appropriate sign convention for torque.
Consider two separately supplied DC machines coupled on a common shaft and running at the same speed ω. Let the applied terminal voltages be Vt1 and Vt2, with field fluxes φf1 and φf2, armature resistances Ra1, Ra2, and armature currents Ia1, Ia2. The torque expressions are:
Since the two machines are mechanically coupled and rotate together, the algebraic sum of torques must balance the load torque and shaft inertias. For steady state with no net accelerating torque the condition is:
Graphically, plotting Te1(ω) and -Te2(ω) on the same axes yields the intersection point giving the operating speed and the sign of torque for each machine. If Te is positive (assisting motion) the machine is motoring; if Te is negative (opposing motion) the machine is generating. Thus, whichever machine's torque-speed line lies above the other will tend to drive the coupled system and the other will act as a generator.
By convention used here, torque that assists motion (in the direction of rotation) is positive; torque opposing motion is negative. If a machine produces a positive developed torque its electrical input is partly converted to mechanical output and the machine behaves as a motor. If the developed torque opposes motion, mechanical power is being delivered to the machine and it acts as a generator.
Key features of the torque-speed characteristic for a shunt machine with field flux φ fixed:
Because armature current is limited by rating, the machine cannot be operated beyond the vertical limits corresponding to Ia,max. Two important operating regions are:
The practical operating point of a shunt machine must lie within the current limits so that armature heating is controlled and equipment ratings are not exceeded.
Armature reaction is the distortion and partial demagnetisation of the main field produced by the armature mmf when armature current flows. The net effect is that the effective field flux per pole φeq is reduced as armature current increases. A simple representation is:
Consequences of armature reaction:
Problem statement (preserved facts): A DC machine rated 8 kW, 230 V, 1200 RPM has armature resistance Ra = 0.7 Ω. The no-load terminal voltage set is 250 V. The motor runs at no-load speed Nnl = 1250 rpm and draws armature current Ia,nl = 1.6 A. Under a particular load the armature current becomes Ia,load = 40 A and the speed falls to Nload = 1150 rpm. Find the percentage reduction in flux per pole Δφf / φf (due to armature reaction).
Solution:
Use the relation between induced emf, terminal voltage and armature drop:
E = Vt - Ia Ra (motor equation).
Also E = k φ N if N is speed in rpm and k includes the conversion factor between ω and N; here k is the same constant in both cases.
Compute flux at no load (φnl):
Vt = 250 V, Ia,nl = 1.6 A, Ra = 0.7 Ω, Nnl = 1250 rpm.
Enl = Vt - Ia,nl Ra
Enl = 250 - (1.6 × 0.7)
Enl = 250 - 1.12 = 248.88 V
Therefore φnl = Enl / (k Nnl) = 248.88 / (k × 1250) = 0.199104 / k ≈ 0.1991 / k
Compute flux under load (φload):
Ia,load = 40 A, Nload = 1150 rpm.
Eload = Vt - Ia,load Ra
Eload = 250 - (40 × 0.7)
Eload = 250 - 28 = 222 V
Therefore φload = Eload / (k Nload) = 222 / (k × 1150) = 0.1930435 / k ≈ 0.1930 / k
Change in flux and percentage reduction:
Δφ = φnl - φload
Δφ = (0.199104 / k) - (0.193044 / k) = 0.00606 / k
Percentage reduction = (Δφ / φnl) × 100%
Percentage reduction = (0.00606 / 0.199104) × 100% ≈ 3.0% (rounded)
Note: Using the rounded values reported in the source calculation gives approximately 3.5%. Small differences arise from rounding of the intermediate numerical values or interpretation of the given no-load set voltage; the important point is that the flux reduction due to armature reaction is small (a few percent) for this loading but not negligible for accurate performance prediction.
Key practical points for DC shunt motors:
For a DC shunt machine with essentially constant field flux, the torque-speed characteristic is approximately linear with slope determined by armature resistance and field flux. The no-load speed is proportional to armature voltage and inversely proportional to flux. Armature reaction reduces the effective flux at higher armature currents, slightly modifying the ideal linear characteristics. Limits on armature current create distinct operating zones (constant-torque and constant-power) that determine safe and practical machine operation. Careful selection of armature voltage, field current and added resistances allows control of speed and torque to meet application requirements.
19 videos|124 docs|25 tests |
| 1. What are the main characteristics of DC shunt motors? | ![]() |
| 2. How does the speed of a DC shunt motor vary with field current? | ![]() |
| 3. What is the starting torque of a DC shunt motor? | ![]() |
| 4. How does a DC shunt motor maintain a constant speed under varying loads? | ![]() |
| 5. What are the typical applications of DC shunt motors? | ![]() |