Electrical Engineering (EE) Exam  >  Electrical Engineering (EE) Notes  >  Lecture 15 - Controller types

Lecture 15 - Controller types - Electrical Engineering (EE) PDF Download

Lecture 15 -Controller types, Control Systems

 

If we remember the controller design in continuous domain using root locus, we see that the design is based on the approximation that the closed loop system has a complex conjugate pole pair which dominates the system behavior. Similarly for a discrete time case also the controller will be designed based on the concept of a dominant pole pair.

Controller types: We have already studied different variants of controllers such as PI, PD, PID etc. We know that PI controller is generally used to improve steady state performance whereas PD controller is used to improve the relative stability or transient response. Similarly a phase lead compensator improves the dynamic performance whereas a lag compensator improves the steady state response.
Pole-Zero cancellation A common practice in designing controllers in s-plane or z-plane is to cancel the undesired poles or zeros of plant transfer function by the zeros and poles of controller. New poles and zeros can also be added in some advantageous locations. However, one has to keep in mind that pole-zero cancellation scheme does not always provide satisfactory solution. Moreover, if the undesired poles are near j ω axis, inexact cancellation, which is almost inevitable in practice, may lead to a marginally stable or even unstable closed loop system. For this reason one should never try to cancel an unstable pole.

Design Procedure: Consider a compensator of the form K z + a z + b . It will be a lead com-  pensator if the zero lies on the right of the pole.

1. Calculate the desired closed loop pole pairs based on design criteria.

2. Map the s-domain poles to z-domain.

3. Check if the sampling frequency is 8−10 times the desired damped frequency of oscillation.

4. Calculate the angle contributions of all open loop poles and zeros to the desired closed loop pole.

5. Compute the required contribution by the controller transfer function to satisfy angle criterion.

6. Place the controller zero in a suitable location and calculate the required angle contribution of the controller pole.

7. Compute the location of the controller pole to provide the required angle.

8. Find out the gain K from the magnitude criterion.

The following example will illustrate the design procedure.

 

An Example on Controller Design 

Consider the closed loop discrete control system as shown in Figure 1. Design a digital controller

Lecture 15 - Controller types - Electrical Engineering (EE)Lecture 15 - Controller types - Electrical Engineering (EE)

Figure 1: A discrete time control system such that the dominant closed loop poles have a damping ratio ξ = 0.5 and settling time ts = 2 sec for 2% tolerance band. Take the sampling period as T = 0.2 sec. The dominant pole pair in continuous domain is 

Lecture 15 - Controller types - Electrical Engineering (EE) where ωn is the natural undamped frequency.

Given that settling time t=Lecture 15 - Controller types - Electrical Engineering (EE)

Thus, ωn = 4

Damped frequency ωLecture 15 - Controller types - Electrical Engineering (EE)

Sampling frequency ωs =Lecture 15 - Controller types - Electrical Engineering (EE)

Since Lecture 15 - Controller types - Electrical Engineering (EE)= 9.07, we get approximately 9 samples per cycle of the damped oscillation.
The closed loop poles in s-plane

Lecture 15 - Controller types - Electrical Engineering (EE)

Thus the closed loop poles in z-plane

Lecture 15 - Controller types - Electrical Engineering (EE)

Lecture 15 - Controller types - Electrical Engineering (EE)

Lecture 15 - Controller types - Electrical Engineering (EE)

Figure 2: Root locus of uncompensated system

The root locus of the uncompensated system (without controller) is shown in Figure 2. It is clear from the root locus plot that the uncompensated system is stable for a very small range of K .

Lecture 15 - Controller types - Electrical Engineering (EE)

Figure 3: Pole zero map to compute angle contributions

Pole zero map of the uncompensated system is shown in Figure 3. Sum of angle contributions at the desired pole is A = θ1 − θ− θ3, where θ1 is the angle by the zero, −0.93, and θ2 and θ3 are the angles contributed by the two poles, 0.82 and 1 respectively.

From the pole zero map as shown in Figure 3, the angles can be calculated as θ1 = 16.5o, θ2 = 124.9o and θ= 138.1o.
Net angle contribution is A = 16.5o − 124.9o − 138.1o = −246.5o.

But from angle criterion a point will lie on root locus if the total angle contribution at that point is ±180o . Angle deficiency is −246.5o + 180o = −66.5o Controller pulse transfer function must provide an angle of 66.5o. Thus we need a Lead Compensator. Let us consider the following compensator.

Lecture 15 - Controller types - Electrical Engineering (EE)

If we place controller zero at z = 0.82 to cancel the pole there, we can avoid some of the calculations involved in the design. Then the controller pole should provide an angle of 124.9o − 66.5= 58.4o.

Once we know the required angle contribution of the controller pole, we can easily calculate the pole location as follows.

The pole location is already assumed at z = −b. Since the required angle is greater than tan−1(0.43/0.52) = 39.6o we can easily say that the pole must lie on the right half of the unit circle. Thus b should be negative. To satisfy angle criterion,

Lecture 15 - Controller types - Electrical Engineering (EE)

Thus, b = −0.253

The controller is then written as  G(z) =Lecture 15 - Controller types - Electrical Engineering (EE).The root locus of the compensated
system (with controller) is shown in Figure 4.
If we compare Figure 4 with Figure 2, it is evident that stable region of K is much larger for the compensated system than the uncompensated system. Next we need to calculate K from the magnitude criterion.

Magnitude criterion :Lecture 15 - Controller types - Electrical Engineering (EE)

Lecture 15 - Controller types - Electrical Engineering (EE)

Lecture 15 - Controller types - Electrical Engineering (EE)

Figure 4: Root locus of the compensated system

Thus the required controller is GD (z) =  Lecture 15 - Controller types - Electrical Engineering (EE) The SIMULINK block to compute the output response is shown in Figure 5. All discrete blocks in the SIMULINK model should have same sampling period which is 0.2 sec in this example. The scope output is shown in Figure 6.

Lecture 15 - Controller types - Electrical Engineering (EE)

Figure 5: Simulink diagram of the closed loop system

Lecture 15 - Controller types - Electrical Engineering (EE)

Figure 6: Output response of the closed loop system

The document Lecture 15 - Controller types - Electrical Engineering (EE) is a part of Electrical Engineering (EE) category.
All you need of Electrical Engineering (EE) at this link: Electrical Engineering (EE)
Are you preparing for Electrical Engineering (EE) Exam? Then you should check out the best video lectures, notes, free mock test series, crash course and much more provided by EduRev. You also get your detailed analysis and report cards along with 24x7 doubt solving for you to excel in Electrical Engineering (EE) exam. So join EduRev now and revolutionise the way you learn!
Sign up for Free Download App for Free

FAQs on Lecture 15 - Controller types - Electrical Engineering (EE)

1. What are the different types of controllers?
Ans. There are several types of controllers, including proportional controllers, integral controllers, derivative controllers, and PID controllers. Each type has its own unique characteristics and applications in control systems.
2. How does a proportional controller work?
Ans. A proportional controller adjusts the output based on the difference between the desired setpoint and the actual process variable. The controller output is proportional to this error, which means that the larger the error, the larger the controller output. This type of controller provides a simple and straightforward control action.
3. What is an integral controller?
Ans. An integral controller continuously sums the errors over time to determine the control output. It eliminates steady-state errors by integrating the error signal, which allows it to gradually reduce the error to zero. This type of controller is commonly used for controlling systems with constant disturbances.
4. How does a derivative controller work?
Ans. A derivative controller calculates the rate of change of the error signal and adjusts the control output accordingly. It anticipates the future behavior of the system based on the current rate of change of the error. This type of controller is effective in reducing overshoot and improving stability in control systems.
5. What is a PID controller?
Ans. A PID controller combines proportional, integral, and derivative control actions to achieve optimal control performance. It uses the error, its integral, and its derivative to calculate the control output. PID controllers are widely used in various industries and applications due to their ability to handle complex control tasks and provide robust control.
Download as PDF
Related Searches

Free

,

Semester Notes

,

practice quizzes

,

Summary

,

Viva Questions

,

Exam

,

past year papers

,

Objective type Questions

,

video lectures

,

Previous Year Questions with Solutions

,

Sample Paper

,

Lecture 15 - Controller types - Electrical Engineering (EE)

,

Important questions

,

ppt

,

study material

,

Lecture 15 - Controller types - Electrical Engineering (EE)

,

pdf

,

mock tests for examination

,

MCQs

,

Extra Questions

,

shortcuts and tricks

,

Lecture 15 - Controller types - Electrical Engineering (EE)

;