This chapter develops a practical steady-state model of a single-phase transformer by relaxing the simplifying assumptions of the ideal transformer (lossless windings and no leakage flux). The practical model accounts for
Consider a practical transformer with primary winding turns N1, secondary winding turns N2, primary applied voltage v1(t), and secondary terminal voltage v2(t). Let the winding resistances be r1, r2, and the leakage inductances (series) be l1, l2. The winding currents are i1(t) and i2(t). The induced EMFs in the primary and secondary are e1(t) and e2(t), respectively.
The time-domain voltage equations for each winding (including series resistance and leakage inductance) are
v1(t) = r1 i1(t) + l1 (d i1/d t) + e1(t)
e2(t) = r2 i2(t) + l2 (d i2/d t) + v2(t)
As for an ideal transformer, the induced EMFs are proportional to turns:
e1 : e2 = N1 : N2
Even when the secondary is open (i2 = 0), a practical transformer draws a small current from the supply - the no-load current - because of finite core permeability and the core losses. To model this:
Explanation of phase relationships:
The complete practical equivalent circuit therefore places primary resistance r1 and leakage reactance jXl1 in series with an ideal transformer; across the primary side of the ideal transformer is the shunt branch R0 ∥ jXm. The secondary has its series resistance r2 and leakage reactance jXl2, and the load ZL is connected to the secondary terminals. The no-load current is i0 = im + ic, and the primary line current is the phasor sum of i0 and the current reflected from the load through the ideal transformer.
In phasor notation the winding voltage equations become
V1 = r1I1 + jXl1I1 + E1
E2 = r2I2 + jXl2I2 + V2
And the load relation is
V2 = ZL I2
Magnetizing and core-loss currents (phasors) are
Im = E1 / (jXm)
Ic = E1 / R0
The induced voltages obey
E2 = (N2/N1) E1
The current reflected into the primary by the load current is
I2' = (N2/N1) I2
Take the core flux phasor φm as the reference. Then:
The exact circuit contains an ideal transformer between the two sides. Because an ideal transformer changes voltages and currents, it is awkward to write KCL/KVL equations directly across the transformer. To enable standard circuit analysis, we eliminate the ideal transformer by referring all secondary quantities to the primary side (or vice versa). The referred circuit is algebraically equivalent and preserves voltages, currents and power relations when transformed correctly.
Let a = N1/N2 be the turns ratio (primary turns per secondary turn). The secondary current I2 produces a current in the primary of
I2' = (N2/N1) I2
From the viewpoint of the primary terminals the impedance seen on the secondary (ZL + r2 + jXl2) is referred as follows:
ZL' = a² ZL
and similarly
r2' = a² r2
Xl2' = a² Xl2
Thus the exact equivalent circuit referred to the primary side places r2', jXl2' and the referred load ZL' in series and connects this series branch across the same primary terminals that see E1. The shunt branch R0 ∥ jXm and the primary series elements r1, jXl1 remain as before.
Power preservation check (algebraic demonstration):
I2' = (N2/N1) I2
r2' = (N1/N2)² r2 = a² r2
Therefore
I2'² r2' = [(N2/N1) I2]² · [ (N1/N2)² r2 ]
The scaling factors cancel and
I2'² r2' = I2² r2
So the copper loss in the secondary is preserved in the referred circuit.
Voltage relation for the referred load:
V2' = I2' ZL'
Substitute I2' = (N2/N1) I2 and ZL' = (N1/N2)² ZL
Therefore V2' = (N1/N2) V2
and the apparent power is preserved since V2' I2' = V2 I2.
Similarly, to refer primary quantities to the secondary side define b = N2/N1. Then primary impedances are transformed as follows when referred to the secondary side:
r1' = b² r1
Xl1' = b² Xl1
Xm' = b² Xm
R0' = b² R0
Currents and voltages transform inversely:
I1' = (N1/N2) I1
V1' = (N2/N1) V1
Using these transformations yields the exact equivalent circuit referred to the secondary. This circuit retains the same topological structure as the primary-referred circuit but with the transformed parameter values shown above.
Either of the following exact equivalent circuits may be used for steady-state analysis depending on convenience:
Both circuits are topologically identical after referring (series primary resistance and leakage reactance, shunt branch representing magnetizing and core losses) and differ only in numerical values of the transformed parameters as given in the summary.
Typical procedure for steady-state analysis of a loaded single-phase transformer:
The model and methods given above provide the standard basis for analysing transformer voltages, currents, regulation, efficiency, and losses in steady state and are widely used in power system studies and machine design.
19 videos|124 docs|25 tests |
| 1. What is the purpose of modeling single-phase transformers in electrical engineering? | ![]() |
| 2. What are the main parameters considered in the modeling of single-phase transformers? | ![]() |
| 3. How is the turns ratio of a single-phase transformer determined in its modeling? | ![]() |
| 4. What is the significance of modeling the resistance in single-phase transformer analysis? | ![]() |
| 5. How does modeling the leakage inductance affect the behavior of single-phase transformers? | ![]() |