Electrical Engineering (EE) Exam  >  Electrical Engineering (EE) Notes  >  Electrical Machines  >  Parallel Operation Of Single Phase Transformers

Parallel Operation Of Single Phase Transformers - Electrical Machines -

Introduction

Load on a distribution or other practical transformer usually grows over time. When a transformer approaches or exceeds its rated load during its life, two practical responses are possible. One option is to replace the transformer by a larger rating; this has limits because the new transformer must be planned for future expansion and will often operate at light load for long periods, reducing utilisation efficiency. The second option is to connect another transformer in parallel with the existing one. Parallel operation has advantages: it allows growth in load without a single very large transformer, permits one transformer to be left out of service when loading is light, and simplifies maintenance because a single spare transformer of similar rating suffices.

Basic connection and essential checks

When two single-phase transformers are connected in parallel, their primaries are connected to the same source and their secondaries supply the same load. The following conditions must be observed before paralleling:

  • Polarity check: The instantaneous polarities (phasing) of the transformer terminals must be the same before paralleling. The corresponding instantaneous positive terminals on both secondaries must be connected together and the other terminals likewise. If polarity is reversed on one transformer, closing the paralleling switch will produce a direct short between windings and cause large short-circuit currents.
  • No-load (open-circuit) secondary voltages: The no-load secondary voltages must be very close in magnitude. If the no-load voltages differ significantly, large circulating currents flow at the instant the paralleling switch is closed; these currents are limited only by the series impedances of the transformers (typically small, 5-10%), and can be dangerously large.
  • Total KVA rating: The combined KVA ratings of the transformers must be at least equal to the expected load KVA; otherwise paralleling will not meet demand.
Basic connection and essential checks

Equivalent circuits and current sharing (identical no-load voltages)

Assume two single-phase transformers with their secondaries connected in parallel and that their induced (no-load) secondary voltages are identical. With the secondary side as reference, each transformer can be represented by its series equivalent impedance.

Let the series impedances be Z1 = R1 + jX1 and Z2 = R2 + jX2. Let the currents supplied by the two transformers be I1 and I2, and the total load current be IL. The series impedances appear effectively in parallel as seen by the load, and the following relations hold:

  • Z1·I1 = Z2·I2 (voltage drops across each series impedance are equal because secondaries are tied together)
  • IL = I1 + I2
  • Solving gives I1 = (Z2 / (Z1 + Z2)) · IL and I2 = (Z1 / (Z1 + Z2)) · IL

Phasor relations: if VL is the load voltage phasor and IL its current phasor, then VL = I1·Z1 = I2·Z2. The phasor diagram shows I1 and I2 such that their vector sum is IL. From the relations above we see:

  • Phase condition for maximum utilisation: For the transformer currents to be in phase (so that magnitudes add algebraically), the ratio I1/I2 must be a real scalar. That requires the impedance angles to be equal: angle(Z1) = angle(Z2), i.e. R1/X1 = R2/X2. This is a desirable (but not strictly essential) condition because when the currents are in phase the pair supplies the greatest possible IL for given transformer current limits.
  • KVA sharing: Multiply the current expressions by VL* (complex conjugate) to obtain complex KVA (apparent power). If SL denotes the complex KVA demanded by the load, then S1 = (Z2 / (Z1 + Z2)) · SL and S2 = (Z1 / (Z1 + Z2)) · SL.
  • Proportional sharing by rated KVA: It is desirable that the transformers share load KVA in proportion to their individual KVA ratings, i.e. S1 / S2 = S1,rated / S2,rated. From the sharing formula this implies |Z2| / |Z1| = S1,rated / S2,rated.
  • Practical rule (per-unit equality): If both transformers have the same rated secondary voltage, then equality of per-unit series impedances on their own bases ensures proportional sharing: Z1 (pu) = Z2 (pu).
Equivalent circuits and current sharing (identical no-load voltages)

Consequences if sharing condition is not met

If the condition |Z2| / |Z1| = S1,rated / S2,rated is not satisfied, one transformer will reach rated KVA before the other. Suppose S2 reaches its rated KVA first. Let SL,max denote the total load KVA when S2 = S2,rated. Then

  • S2,rated = (|Z1| / (|Z1| + |Z2|)) · SL,max
  • Hence SL,max = ((|Z1| + |Z2|) / |Z1|) · S2,rated
  • The load on transformer 1 at that instant is S1 = (|Z2| / (|Z1| + |Z2|)) · SL,max = (|Z2| / |Z1|) · S2,rated

If (|Z2| / |Z1|) is less than (S1,rated / S2,rated) then S1 < s1,rated when s2 reaches s2,rated. thus the parallel group cannot be further loaded even though one transformer still has spare capacity, and the combined capacity of the two is not fully exploited. for maximum combined usable kva it is therefore desirable to ensure equal per-unit impedances and equal impedance 

Consequences if sharing condition is not met

Parallel connection when no-load voltages differ (slightly different turns ratios)

In practice, two transformers to be paralleled may have slightly different turns ratios and hence slightly different induced secondary (no-load) voltages. When the induced voltages differ, the simple parallel equivalent with impedances directly in parallel no longer strictly applies; there will be internal voltage differences and circulating currents between transformers even before external load is applied.

Represent the two transformer equivalent circuits on the common secondary (load) side. Let the induced (open-circuit) secondary phasors referred to the secondary terminals be E1′ and E2′ respectively. Let the series impedances referred to the secondary be Z1 and Z2. The load admittance is YL = 1/ZL, and transform admittances are Y1 = 1/Z1 and Y2 = 1/Z2. If the load terminal voltage phasor is VL, node KCL at the load node gives:

  • VL·YL = (E1′ - VL)·Y1 + (E2′ - VL)·Y2
  • Rearrange to obtain VL·(YL + Y1 + Y2) = E1′·Y1 + E2′·Y2
  • Therefore VL = (Y1·E1′ + Y2·E2′) / (YL + Y1 + Y2)
  • Transformer currents are I1 = Y1·(E1′ - VL) and I2 = Y2·(E2′ - VL)

From these equations individual currents and the KVA supplied by each transformer can be determined for any given load. When E1′ ≠ E2′, circulating magnetising or short-circuit currents flow between transformers; their magnitude is determined by the difference E1′ - E2′ and the series impedances.

Parallel connection when no-load voltages differ (slightly different turns ratios)

Worked numerical example (step-by-step solution)

Problem statement (as given): Two single-phase transformers have identical open circuit secondary voltage rating 11 kV/3.3 kV. Short-circuit test (HV winding shorted) data are:

  • Transformer 1: applied voltage 200 V, circulating current 400 A, power dissipated (on short-circuit) 15 kW.
  • Transformer 2: applied voltage 100 V, circulating current 400 A, power dissipated (on short-circuit) 20 kW.

These two transformers are connected in parallel and supply a load current IL = 750 A at 0.8 power factor lagging. Find the KVA supplied by each transformer and the load terminal voltage.

Worked numerical example (step-by-step solution)

Solution (computations given stepwise; each numerical step on a separate line followed by a short explanation):

Modulus of series impedance of transformer 1: 0.5 Ω = 200 V ÷ 400 A

This is |Z1| from the short-circuit test.

Series resistance of transformer 1: 0.094 Ω = 15 000 W ÷ (400 A)²

R1 is obtained from the measured power loss during the short-circuit test.

Leakage reactance of transformer 1: 0.491 Ω = √(0.5² - 0.094²)

X1 is found from |Z1|² = R1² + X1².

Modulus of series impedance of transformer 2: 0.25 Ω = 100 V ÷ 400 A

This is |Z2| from transformer 2 short-circuit test.

Series resistance of transformer 2: 0.125 Ω = 20 000 W ÷ (400 A)²

R2 is obtained from the short-circuit power loss for transformer 2.

Leakage reactance of transformer 2: 0.2165 Ω = √(0.25² - 0.125²)

X2 computed from |Z2|² = R2² + X2².

Impedance angles: θ1 = cos⁻¹(R1 / |Z1|) = 79.1°

θ1 is the impedance angle of Z1.

Impedance angles: θ2 = cos⁻¹(R2 / |Z2|) = 60°

θ2 is the impedance angle of Z2.

Complex impedances: Z1 = 0.5 ∠79.1° Ω and Z2 = 0.25 ∠60° Ω

Express Z1 and Z2 in polar form for phasor calculations.

Sum of impedances: Z1 + Z2 = 0.7407 ∠72.8° Ω

Compute Z1 + Z2 by phasor addition (or convert to rectangular and add, then convert back to polar).

Load current phasor: IL = 750 ∠-36.87° A (0.8 p.f. lagging corresponds to cos⁻¹(0.8) = 36.87°)

Reference chosen so that IL angle is -36.87°.

Current supplied by transformer 1: I1 = (Z2 / (Z1 + Z2)) · IL = 253 ∠-49.6° A

Use I1 = (Z2 / (Z1 + Z2)) IL and multiply phasors.

Current supplied by transformer 2: I2 = (Z1 / (Z1 + Z2)) · IL = 506 ∠-30.5° A

Use I2 = (Z1 / (Z1 + Z2)) IL and multiply phasors.

Check: I1 + I2 = IL (vector sum: 253∠-49.6° + 506∠-30.5° = 750∠-36.87°)

The phasor sum recovers the given IL (small differences may be due to rounding).

Worked numerical example (step-by-step solution)

Determine the secondary terminal voltage magnitude. The referred (induced) secondary voltage magnitude corresponding to 11 kV primary and 3.3 kV secondary is 3.3 kV (given transformer rating). Let V1′ denote the induced secondary phasor magnitude 3300 V at angle δ. Then VL = V1′ - Z1·I1 (phasor equation VL = V1′ - I1·Z1).

Compute phasor drop across Z1: I1·Z1 (numerical phasor multiplication gives magnitude and angle).

The angle difference θ1 - ∠I1 = 79.1° - (-49.6°) = 128.7°; use phasor multiplication to find the real and imaginary components of the drop.

Using the geometry of the phasor diagram and solving for VL and δ yields VL ≈ 3190 V

Detailed phasor algebra gives the load terminal voltage magnitude as about 3.19 kV.

Worked numerical example (step-by-step solution)

Apparent power supplied by transformer 1: S1 = VL · I1 = 3190 V × 253 A = 807.5 kVA

Compute complex S1 and determine its power factor (S1 shows a lagging power factor of approximately 0.648).

Apparent power supplied by transformer 2: S2 = VL · I2 = 3190 V × 506 A = 1615 kVA

Compute complex S2 and determine its power factor (S2 shows a lagging power factor of approximately 0.862).

Worked numerical example (step-by-step solution)

Discussion of example and practical points

  • Because the impedance angles θ1 and θ2 differ, the currents I1 and I2 are not in phase; their algebraic magnitudes do not add but phasor sum equals IL. This reduces the usable combined current compared with the ideal case where impedance angles match.
  • Transformer 2 in the example supplies approximately twice the KVA of transformer 1 because its series impedance magnitude is smaller; the per-unit impedances are not equal on their own bases, so sharing is not proportional to rated KVA.
  • When paralleling transformers in practice, engineers match polarities, ensure secondary voltages are very close, and prefer equal per-unit impedances and similar X/R ratios to obtain predictable and fair load sharing.
Discussion of example and practical points

Summary

Parallel operation of single-phase transformers is a practical method to increase available KVA and to provide flexibility and redundancy. Essential preconditions are correct polarity and closely matched no-load secondary voltages. Desirable additional conditions are equal per-unit series impedances (on own bases) and similar impedance angle (X/R ratio) so that currents are nearly in phase and KVA is shared proportionally to ratings. When induced voltages differ slightly, node equations with admittances yield the exact terminal voltage and individual currents; circulating currents may then exist even with no external load. Practical design and tests (open-circuit and short-circuit tests) provide the impedances and losses needed for correct paralleling and for predicting load sharing.

Summary
Summary
The document Parallel Operation Of Single Phase Transformers - Electrical Machines - Electrical Engineering (EE) is a part of the Electrical Engineering (EE) Course Electrical Machines.
All you need of Electrical Engineering (EE) at this link: Electrical Engineering (EE)
19 videos|125 docs|25 tests

FAQs on Parallel Operation Of Single Phase Transformers - Electrical Machines - Electrical Engineering (EE)

1. What is parallel operation of single phase transformers?
Ans. Parallel operation of single phase transformers refers to the connection of multiple transformers in parallel to increase the total power capacity or to provide redundancy in case of a failure of one transformer. It allows for the sharing of load and provides flexibility in power distribution systems.
2. How are single phase transformers connected in parallel?
Ans. Single phase transformers can be connected in parallel by connecting their primary windings to a common voltage source and their secondary windings to a common load. It is essential to ensure that the transformers have similar voltage ratios, impedance values, and turns ratios to ensure balanced load sharing.
3. What precautions should be taken when connecting single phase transformers in parallel?
Ans. When connecting single phase transformers in parallel, it is important to consider the following precautions: - Ensure that the transformers have similar voltage ratios, impedance values, and turns ratios to ensure balanced load sharing. - Use appropriate protection devices, such as fuses or circuit breakers, to protect each transformer from short circuits or overloads. - Properly synchronize the transformers to avoid any phase difference or circulating currents. - Regularly monitor the operation of each transformer to detect any abnormalities or imbalances.
4. What are the advantages of parallel operation of single phase transformers?
Ans. The advantages of parallel operation of single phase transformers include: - Increased power capacity: By connecting transformers in parallel, the total power capacity can be increased, allowing for the addition of loads without overloading a single transformer. - Redundancy: In case of a failure of one transformer, the remaining transformers can continue to supply power, ensuring uninterrupted operation. - Load sharing: Parallel operation allows for the sharing of load among multiple transformers, preventing overloading of a single transformer. - Flexibility: It provides flexibility in power distribution systems by allowing for the addition or removal of transformers as per the changing load requirements.
5. Can different types of single phase transformers be connected in parallel?
Ans. While it is possible to connect different types of single phase transformers in parallel, it is not recommended. Different types of transformers may have variations in their voltage ratios, impedance values, and turns ratios, which can lead to imbalanced load sharing and inefficient operation. It is best to connect transformers that are specifically designed for parallel operation to ensure proper load sharing and compatibility.
Related Searches
Previous Year Questions with Solutions, Parallel Operation Of Single Phase Transformers - Electrical Machines - Electrical Engineering (EE), Extra Questions, Objective type Questions, Parallel Operation Of Single Phase Transformers - Electrical Machines - Electrical Engineering (EE), Semester Notes, Summary, practice quizzes, past year papers, shortcuts and tricks, MCQs, Parallel Operation Of Single Phase Transformers - Electrical Machines - Electrical Engineering (EE), Important questions, pdf , mock tests for examination, Sample Paper, Viva Questions, ppt, Exam, Free, study material, video lectures;