| Table of contents | |
| Parallel connection when no-load voltages differ (slightly different turns ratios) | |
| Worked numerical example (step-by-step solution) | |
| Discussion of example and practical points | |
| Summary |
Load on a distribution or other practical transformer usually grows over time. When a transformer approaches or exceeds its rated load during its life, two practical responses are possible. One option is to replace the transformer by a larger rating; this has limits because the new transformer must be planned for future expansion and will often operate at light load for long periods, reducing utilisation efficiency. The second option is to connect another transformer in parallel with the existing one. Parallel operation has advantages: it allows growth in load without a single very large transformer, permits one transformer to be left out of service when loading is light, and simplifies maintenance because a single spare transformer of similar rating suffices.
When two single-phase transformers are connected in parallel, their primaries are connected to the same source and their secondaries supply the same load. The following conditions must be observed before paralleling:
Assume two single-phase transformers with their secondaries connected in parallel and that their induced (no-load) secondary voltages are identical. With the secondary side as reference, each transformer can be represented by its series equivalent impedance.
Let the series impedances be Z1 = R1 + jX1 and Z2 = R2 + jX2. Let the currents supplied by the two transformers be I1 and I2, and the total load current be IL. The series impedances appear effectively in parallel as seen by the load, and the following relations hold:
Phasor relations: if VL is the load voltage phasor and IL its current phasor, then VL = I1·Z1 = I2·Z2. The phasor diagram shows I1 and I2 such that their vector sum is IL. From the relations above we see:
If the condition |Z2| / |Z1| = S1,rated / S2,rated is not satisfied, one transformer will reach rated KVA before the other. Suppose S2 reaches its rated KVA first. Let SL,max denote the total load KVA when S2 = S2,rated. Then
If (|Z2| / |Z1|) is less than (S1,rated / S2,rated) then S1 < s1,rated when s2 reaches s2,rated. thus the parallel group cannot be further loaded even though one transformer still has spare capacity, and the combined capacity of the two is not fully exploited. for maximum combined usable kva it is therefore desirable to ensure equal per-unit impedances and equal impedance
In practice, two transformers to be paralleled may have slightly different turns ratios and hence slightly different induced secondary (no-load) voltages. When the induced voltages differ, the simple parallel equivalent with impedances directly in parallel no longer strictly applies; there will be internal voltage differences and circulating currents between transformers even before external load is applied.
Represent the two transformer equivalent circuits on the common secondary (load) side. Let the induced (open-circuit) secondary phasors referred to the secondary terminals be E1′ and E2′ respectively. Let the series impedances referred to the secondary be Z1 and Z2. The load admittance is YL = 1/ZL, and transform admittances are Y1 = 1/Z1 and Y2 = 1/Z2. If the load terminal voltage phasor is VL, node KCL at the load node gives:
From these equations individual currents and the KVA supplied by each transformer can be determined for any given load. When E1′ ≠ E2′, circulating magnetising or short-circuit currents flow between transformers; their magnitude is determined by the difference E1′ - E2′ and the series impedances.
Problem statement (as given): Two single-phase transformers have identical open circuit secondary voltage rating 11 kV/3.3 kV. Short-circuit test (HV winding shorted) data are:
These two transformers are connected in parallel and supply a load current IL = 750 A at 0.8 power factor lagging. Find the KVA supplied by each transformer and the load terminal voltage.
Solution (computations given stepwise; each numerical step on a separate line followed by a short explanation):
Modulus of series impedance of transformer 1: 0.5 Ω = 200 V ÷ 400 A
This is |Z1| from the short-circuit test.
Series resistance of transformer 1: 0.094 Ω = 15 000 W ÷ (400 A)²
R1 is obtained from the measured power loss during the short-circuit test.
Leakage reactance of transformer 1: 0.491 Ω = √(0.5² - 0.094²)
X1 is found from |Z1|² = R1² + X1².
Modulus of series impedance of transformer 2: 0.25 Ω = 100 V ÷ 400 A
This is |Z2| from transformer 2 short-circuit test.
Series resistance of transformer 2: 0.125 Ω = 20 000 W ÷ (400 A)²
R2 is obtained from the short-circuit power loss for transformer 2.
Leakage reactance of transformer 2: 0.2165 Ω = √(0.25² - 0.125²)
X2 computed from |Z2|² = R2² + X2².
Impedance angles: θ1 = cos⁻¹(R1 / |Z1|) = 79.1°
θ1 is the impedance angle of Z1.
Impedance angles: θ2 = cos⁻¹(R2 / |Z2|) = 60°
θ2 is the impedance angle of Z2.
Complex impedances: Z1 = 0.5 ∠79.1° Ω and Z2 = 0.25 ∠60° Ω
Express Z1 and Z2 in polar form for phasor calculations.
Sum of impedances: Z1 + Z2 = 0.7407 ∠72.8° Ω
Compute Z1 + Z2 by phasor addition (or convert to rectangular and add, then convert back to polar).
Load current phasor: IL = 750 ∠-36.87° A (0.8 p.f. lagging corresponds to cos⁻¹(0.8) = 36.87°)
Reference chosen so that IL angle is -36.87°.
Current supplied by transformer 1: I1 = (Z2 / (Z1 + Z2)) · IL = 253 ∠-49.6° A
Use I1 = (Z2 / (Z1 + Z2)) IL and multiply phasors.
Current supplied by transformer 2: I2 = (Z1 / (Z1 + Z2)) · IL = 506 ∠-30.5° A
Use I2 = (Z1 / (Z1 + Z2)) IL and multiply phasors.
Check: I1 + I2 = IL (vector sum: 253∠-49.6° + 506∠-30.5° = 750∠-36.87°)
The phasor sum recovers the given IL (small differences may be due to rounding).
Determine the secondary terminal voltage magnitude. The referred (induced) secondary voltage magnitude corresponding to 11 kV primary and 3.3 kV secondary is 3.3 kV (given transformer rating). Let V1′ denote the induced secondary phasor magnitude 3300 V at angle δ. Then VL = V1′ - Z1·I1 (phasor equation VL = V1′ - I1·Z1).
Compute phasor drop across Z1: I1·Z1 (numerical phasor multiplication gives magnitude and angle).
The angle difference θ1 - ∠I1 = 79.1° - (-49.6°) = 128.7°; use phasor multiplication to find the real and imaginary components of the drop.
Using the geometry of the phasor diagram and solving for VL and δ yields VL ≈ 3190 V
Detailed phasor algebra gives the load terminal voltage magnitude as about 3.19 kV.
Apparent power supplied by transformer 1: S1 = VL · I1 = 3190 V × 253 A = 807.5 kVA
Compute complex S1 and determine its power factor (S1 shows a lagging power factor of approximately 0.648).
Apparent power supplied by transformer 2: S2 = VL · I2 = 3190 V × 506 A = 1615 kVA
Compute complex S2 and determine its power factor (S2 shows a lagging power factor of approximately 0.862).
Parallel operation of single-phase transformers is a practical method to increase available KVA and to provide flexibility and redundancy. Essential preconditions are correct polarity and closely matched no-load secondary voltages. Desirable additional conditions are equal per-unit series impedances (on own bases) and similar impedance angle (X/R ratio) so that currents are nearly in phase and KVA is shared proportionally to ratings. When induced voltages differ slightly, node equations with admittances yield the exact terminal voltage and individual currents; circulating currents may then exist even with no external load. Practical design and tests (open-circuit and short-circuit tests) provide the impedances and losses needed for correct paralleling and for predicting load sharing.
19 videos|125 docs|25 tests |
| 1. What is parallel operation of single phase transformers? | ![]() |
| 2. How are single phase transformers connected in parallel? | ![]() |
| 3. What precautions should be taken when connecting single phase transformers in parallel? | ![]() |
| 4. What are the advantages of parallel operation of single phase transformers? | ![]() |
| 5. Can different types of single phase transformers be connected in parallel? | ![]() |