Frequency of an A.C. synchronous generator
Commercial a.c. synchronous generators can have many poles and operate at various shaft speeds depending on the prime mover and application. For a two-pole machine, one complete mechanical revolution produces one electrical cycle; hence the output frequency is directly proportional to the mechanical speed (revolutions per second). When the machine has P poles, the number of electrical cycles produced per mechanical revolution equals the number of pole pairs (P/2). Therefore the usual relationship between electrical frequency, number of poles and speed is:
(18)
where:
P is the number of poles; N is the speed in rpm (rev/min); f is the frequency in hertz (cycles per second); ωm is the mechanical angular speed in rad/s; ωe is the electrical angular speed in rad/s.
In formula form the commonly used relations are:
f = (P × N) / 120
ωm = 2πN / 60
ωe = (P / 2) ωm
The field windings of a synchronous machine are carried on the rotor. For large three-phase synchronous generators there are two principal rotor constructions:
Figure 14 (next group of images) illustrates two- and four-pole cylindrical rotors and a developed view of field winding for a pair of poles, together with a single salient pole and its field coil. The stator slots (which contain the armature winding) are omitted for clarity. The approximate path of the main field flux (excluding leakage) is shown by dashed lines in the illustration.
Figure 14: Synchronous machines with stator slots and armature windings omitted (a) Two-pole cylindrical rotor, (b) Four-pole cylindrical rotor, (c) Developed view of two-pole cylindrical rotor field structure, (d) Salient pole and field coil
Figure 15: Cylindrical rotor m.m.f. wave and its fundamental of a synchronous machine
When the field winding conductors are considered in the slots and nearly fill the slot area, the resultant magnetomotive-force (m.m.f.) distribution across the air gap is a stepped waveform. Its fundamental component is approximately sinusoidal (dashed sine in Fig. 15). For cylindrical rotors the air-gap is almost uniform, so the stepped m.m.f. produces a flux density space-wave that is closer to sinusoidal because of fringing effects. However, in regions of high m.m.f. the iron may saturate and flatten the flux-density peak.
Direct current must be supplied to the rotor field winding to produce the main field flux. Several excitation arrangements are in use; the choice depends on machine size, dynamic requirements of the power system and reliability needs. Common methods are:
Typical excitation voltages are about 125 V for units up to around 50 kW, with higher voltages for larger machines. Faster response (important during system disturbances) can be obtained by multi-stage arrangements such as a pilot exciter that drives the main exciter field, providing quicker changes in field current.
A brushless system removes the commutator/collector rings and brushes, improving reliability and reducing maintenance. A typical arrangement consists of:
Figure 17: Brushless excitation system
Brushless excitation is widely used in turbo-generators and aircraft generators where reduced maintenance, elimination of brushes in low pressure environments, and high mechanical simplicity are advantageous.
When a synchronous generator supplies an external load the armature currents alter the air-gap flux distribution produced by the rotor field. The relative phase of the armature current and the induced e.m.f. depends on the load power factor (p.f.):
For simplicity many treatments assume:
Under these idealisations the induced e.m.f. equals the terminal voltage and the phase angle between current and e.m.f. is determined solely by the external load power factor.
The term armature reaction denotes the effect of the armature (stator) currents on the main field flux. Consider the stretched-out (developed) view of a synchronous machine showing fixed stator armature windings and a rotating field (rotor) carrying dc field windings. When the induced e.m.f. in a given stator coil is at maximum, the coil may carry a current depending on the load p.f. The ampere-turns of this coil distort the main flux: they strengthen the flux on one side of a pole and weaken it on the other, causing a displacement and distortion of the main flux distribution.
For a resistive (unit p.f.) generator load the armature mmf distorts the field so that the resultant main flux axis is shifted slightly against the direction of rotation. The induced e.m.f. E produced by the distorted flux is displaced by an angle δ from the position E0 the e.m.f. would have if no armature current flowed. This shift is often referred to as cross-magnetization.
Figure 19: Stretched out synchronous motor
When the machine operates as a motor at unity p.f. the armature current direction reverses and the armature mmf distorts the main flux in the opposite sense. The e.m.f. E is then displaced ahead of E0 by an angle δ (see adjacent phasor diagrams).
For a purely inductive load (current lags E by 90°) the stator ampere-turns act directly to oppose the rotor field ampere-turns, reducing total flux and induced e.m.f. No torque results from the cross-magnetizing component in this case and hence no mechanical power is produced (E and I are in quadrature so VI = 0 for idealised lossless machine).
Figure 20: Stretched out synchronous generator (inductive load)
For a purely capacitive load (current leads E by 90°) the stator ampere-turns assist the rotor field ampere-turns and the total flux and induced e.m.f. increase.
Figure 21: Stretched out synchronous generator (capacitive load)
For intermediate power factors both direct-magnetizing (which increases or decreases net flux depending on sign) and cross-magnetizing (which distorts and shifts the flux axis) components exist simultaneously. The overall effect influences the terminal voltage, the required excitation current and, for motors, the operating power factor.
Summarising the basic working:
Figure 22: Synchronous generator supplying a lagging p.f. load
For cylindrical (non-salient) rotor machines with nearly uniform air-gap the armature reaction can be divided conveniently into two orthogonal components: the cross-magnetizing component and the direct-magnetizing component. The armature reaction m.m.f. Fa is resolved into Faq (quadrature, cross) and Fad (direct), where Fad either demagnetizes (lagging currents) or magnetizes (leading currents) the main field, and Faq shifts the resultant flux axis.
Figure 23: Sinusoidal distribution of the components of armature reaction in a synchronous generator
Figure 24: Elementary synchronous motor action - Attraction of unlike poles keeps the rotor locked to the rotating stator field
To model the effect of armature reaction in circuit form the concept of synchronous reactance is introduced. The resultant flux linkage of an armature phase is split into two components: the flux due to the rotor (field) current alone and that due to the armature current alone. This superposition is approximately valid when the magnetic circuit permeability is constant (i.e. low saturation).
The simplifying assumptions commonly used are:
Under these assumptions the effect of armature reaction can be represented by a phasor voltage Er that is in quadrature with the armature current Ia and proportional to it. Writing the actual induced e.m.f. per phase as E, and the no-load induced e.m.f. (due to field only) as Eo, we have the phasor relation:
E = Eo + Er (19)
Er behaves like the voltage across an inductive reactance caused by the armature current. Define the fictitious reactance of the armature reaction as
xa = Er / Ia
The armature leakage reactance is xl. The sum
xs = xa + xl
is the synchronous reactance. The per-phase synchronous impedance is then
Zs = ra + j xs
where ra is the armature resistance. For most machines xs ≫ ra, so the synchronous impedance magnitude is dominated by xs. The synchronous reactance model leads to the usual per-phase equivalent circuit for a synchronous machine from which voltage regulation, short-circuit behaviour and power angle relations can be derived.
In practice the magnetic circuit is saturated under normal operation, so the linear assumptions are only approximate. A useful approximate synchronous reactance can be obtained from open-circuit and short-circuit tests carried out on the machine. The saturated synchronous reactance is normally determined from rated open-circuit voltage and the short-circuit current produced by the same field current.
Graphically, using the open-circuit characteristic (O.C.C., magnetization curve) and the short-circuit characteristic (S.C.C.), the synchronous impedance Zs (per phase) under test conditions is approximately the ratio of the open-circuit per-phase voltage to the short-circuit per-phase current obtained for the same field current. This gives a practical estimate of Zs that accounts approximately for the machine saturation in service.
(20)
Because synchronous reactance varies with saturation, the value obtained from tests is an approximation adequate for many engineering uses.
Open-circuit and short-circuit tests provide the data necessary to obtain the magnetisation (O.C.C.) and short-circuit characteristics. These curves show the effect of saturation and are employed to estimate the saturated synchronous reactance.
Figure 26: Synchronous generator (a) Open circuit (b) Short circuit
When a constant voltage source has constant impedance, the impedance equals the open-circuit terminal voltage divided by the short-circuit current. However, for a synchronous machine the impedance depends on flux saturation; thus both O.C. and S.C. characteristics are required.
With the machine driven at rated speed and the armature terminals open, line-to-line voltage is measured for various values of field current. The O.C.C. (voltage versus field current) shows the magnetisation curve and the effect of iron saturation. The ideal linear (air-gap) line is the unsaturated reference; per-unit representation is often used so that 1.0 p.u. field current corresponds to the field current that would produce rated voltage if there were no saturation.
Figure 27: (a) Open circuit characteristic and (b) Short-circuit characteristic
For the short-circuit test, the three armature terminals are shorted (usually through current transformers and ammeters) and the machine is driven at rated speed. Armature currents are measured for various field currents, typically up to and somewhat beyond the rated armature current. The S.C.C. (armature current versus field current) is approximately linear up to rated currents for conventional synchronous machines because the iron remains largely unsaturated under short-circuit flux distributions.
Figure 28: Connections for short-circuit test
Plotting the O.C.C. and S.C.C. together (often in per-unit) allows determination of the unsaturated synchronous reactance. For a given field current the open-circuit (air-gap) line gives the corresponding voltage and the short-circuit curve gives the armature current. The unsaturated synchronous reactance per phase (for a star-connected armature) is therefore given approximately by the ratio of the per-phase air-gap voltage to the per-phase short-circuit current produced by the same field current.
Figure 29: Open-circuit and short-circuit characteristic
In symbols (per phase):
(23)
When the O.C.C., air-gap line and S.C.C. are plotted in per-unit, the per-unit unsaturated synchronous reactance equals the per-unit value on the air-gap line corresponding to the field current that produces rated short-circuit current (1.0 p.u.). This per-unit approach makes comparisons between different machines straightforward.
Key practical points:
Summary
The frequency of a synchronous machine is determined by speed and number of poles. Rotor construction (cylindrical or salient) is chosen according to speed and mechanical stresses. Excitation systems supply the dc field current; brushless systems avoid brushes and slip-rings. When loaded, the stator currents produce armature reaction that distorts and/or changes the magnitude of the main flux; its effect is modelled by the synchronous reactance and synchronous impedance. Open-circuit and short-circuit tests provide practical data for estimating synchronous reactance, taking account of saturation.
23 videos|95 docs|42 tests |
| 1. What are armature windings in a synchronous machine? | ![]() |
| 2. How are armature windings connected in a synchronous machine? | ![]() |
| 3. What is the purpose of armature windings in a synchronous machine? | ![]() |
| 4. How are armature windings designed in a synchronous machine? | ![]() |
| 5. What are some common types of armature windings used in synchronous machines? | ![]() |
23 videos|95 docs|42 tests |
![]() | Explore Courses for Electrical Engineering (EE) exam |